<5. Function Test>
78
TI 34P02K35-02E Jun. 6, 2018-00
● If FCN/FCJ Simulator Is Used before Migration
In this migration scenario, debugging started using FCN/FCJ Simulator is to be
migrated to the target equipment upon its delivery.
As no hardware setup is done using FCN/FCJ Simulator, test migration from
FCN/FCJ Simulator to target equipment requires only migration of retain data.
The procedure for migration to target equipment depends on the state of retain data.
If the number of variables with retain data option is less, re-enter data on the target
FCN-500 or FCN-RTU without migrating retained data from FCN/FCJ Simulator.
Otherwise, migrate the retain data using the following procedure.
1. Save retain data specified using FCN/FCJ simulator to the CPU module using
the same procedure for a real FCN-500 or FCN-RTU. Retain data of FCN/FCJ
Simulator is saved as a csv format file named "RETAIN.CSV" on the PC in the
following folder:
<FCN/FCJ Simulator's installed path>\WorkSpace\Current
\USERS\STARDOM\RETAIN
If FCN/FCJ Simulator is installed in its default location, this folder corresponds
to:
C:\YOKOGAWA\FCN-FCJ\FCXSim\WorkSpace\Current
\USERS\STARDOM\RETAIN
2. Download Logic Designer projects not used by FCN/FCJ Simulator to the target
FCN-500 or FCN-RTU.
3. Execute FcxBackup command for the target FCN-500 or FCN-RTU. This backs
up data on the CPU module of the target FCN-500 or FCN-RTU to a folder
named “Backup” on the PC.
4. Copy the “RETAIN.CSV” file saved in step 1 to overwrite backup data saved in
step 3. The folder is:
\BACKUP\JEROS\USERS\STARDOM\RETAIN
5. Switch the target FCN-500 or FCN-RTU to Maintenance mode, and restore the
data saved in item 3 using an FcxRestore command. At the same time, retain
data copied in step 4, in other words, retain data used by FCN/FCX Simulator, is
also restored.
6. Reboot the FCN-500 or FCN-RTU. Download the project used by FCN/FCJ
Simulator and perform a warm start.
This procedure restores retain data stored on the CPU module under the same
conditions described under TIP of ”● Behavior of Retain Data on FCN-500, FCN-
RTU Start Mode” of Section 2.2.5, “Retentive Variables (Retain Data)
Considerations”