1-8
<Toc>
<1. Installation>
IM 05E01D02-41E
1st Edition : May 31,2000-00
Control Output
Universal output system, The output type can be selected with the software.
•
Current output
(Standard type: terminals
16
-
17
)
Number of outputs
Output signal
4-20 mA DC
Load resistance
600
or less
Output accuracy
0.3% of span under standard operating
conditions (23
2
C, 55
10% RH,
power frequency of 50/60 Hz)
1 (switched between a voltage pulse output
and current output)
•
Voltage pulse output
(Standard type: terminals
16
-
17
)
Number of outputs
1 (switched between a voltage pulse output
and current output)
Output signal
On-voltage = 12 V or more
(load resistance: 600
Ω
or more)
Off-voltage = 0.1 V DC or less
Resolution
10 ms
•
Relay contact output
(Standard type: terminals
1
-
2
-
3
)
Number of outputs
1
Output signal
Three terminals (NC, NO, and common)
Contact rating
250 V AC or 30 V DC, 3 A (resistance load)
Resolution
10 ms
Contact Inputs
•
Purpose: Run/Reset switching
•
Number of inputs: 2 points
•
Input type: Non-voltage contact or transistor open collector input
•
Input contact rating: 12 V DC, 10 mA or more
•
On/off determination: For non-voltage contact input, contact resistance of 1 k
or less
is determined as “on” and contact resistance of 20 k
or more as “off.”
For transistor open collector input, input voltage of 2 V or less is determined as “on”
and leakage current must not exceed 100
A when “off.”
•
Minimum status detection hold time: About 1 sec.
Contact Outputs
•
Purpose: PV event outputs (2) and time event output (1)
•
Number of outputs: 3 points
•
Relay contact rating: 240 V AC, 1 A, or 30 V DC, 1 A
Display Specifications
•
PV display: 4-digit, 7-segment red LED display, character height of 20 mm
•
Setpoint display: 4-digit, 7-segment red LED display character height of 9.3 mm
•
Status indicating lamps: LEDs
Summary of Contents for UP350
Page 2: ...Blank Page ...
Page 52: ...Blank Page ...
Page 62: ...Blank Page ...
Page 72: ...Blank Page ...
Page 94: ...Blank Page ...
Page 96: ...Blank Page ...