Safety and EMC Standards
•
Safety: Compliant with IEC1010-1: 1990 and EN61010-1: 1992
Approved by CSA1010
CSA1010 installation category (overvoltage category): CATII (IEC1010-1)
Approved by UL508
•
EMC standards: This instrument complies with the following EMC standards (the
instrument continues to operate at a measuring accuracy of within
20% of the range
during tests):
-
EMI (emission), EN61326-1: 1997+Am1: 1998
-
EMS (immunity), EN61326-1: 1997+Am1: 1998
Construction, Installation, and Wiring
•
Construction: Only the front panel is dust-proof and drip-proof (protection class IP55)
For side-by-side close installation the controller loses its dust-proof and drip-proof
protection.
•
Material: ABS resin and polycarbonate
•
Case color: Black
•
Weight: About 1 kg or less
•
Dimensions: 96 (W)
96 (H)
100 (depth from panel face) mm
•
Installation: Panel-mounting type. With top and bottom mounting hardware (1 each)
•
Panel cutout dimensions: 92
0
+0.8
(W)
92
0
+0.8
(H) mm
•
Installation position: Up to 30
upward facing (not designed for facing downward)
•
Wiring: M3.5 screw terminals (for signal wiring and power/ground wiring as well)
Power Supply Specifications
•
Power supply: Rated voltage of 100 to 240 V AC (
10%), 50/60 Hz
•
Power consumption: Max. 20 VA (8.0 W max.)
•
Data backup: Non-volatile memory (can be written to up to 100,000 times)
•
Withstanding voltage
-
Between primary terminals* and secondary terminals**:
At least 1500 V AC for 1 minute (Note)
-
Between primary terminals* and grounding terminal:
At least 1500 V AC for 1 minute (Note)
-
Between grounding terminal and secondary terminals**:
At least 1500 V AC for 1 minute
-
Between secondary terminals**:
At least 500 V AC for 1 minute
*
Primary terminals indicate power terminals and relay output terminals
**
Secondary terminals indicate analog I/O signal, voltage pulse output, and contact
input terminals
Note: The withstanding voltage is specified as 2300 V AC per minute to provide a margin of safety.
•
Insulation resistance: 20 M
or more at 500 V DC between power terminals and
grounding terminal
•
Grounding: Class 3 grounding (grounding resistance of 100
or less)