Signal Isolations
•
PV input terminals: Isolated from other input/output terminals. Not isolated from the
internal circuit.
•
15 V DC loop power supply terminals: Not isolated from 4-20 mA analog output and
voltage pulse control output. Isolated from other input/output terminals and internal
circuit.
•
4-20 mA analog output terminals (for control output and retransmission): Not isolated
between 4-20 mA outputs and from 15 V DC loop power supply and voltage pulse
control output. Isolated from other input/output terminals and internal circuit.
•
Voltage pulse control output terminals: Not isolated from 4-20 mA outputs and 15 V
DC loop power supply. Isolated from other input/output terminals and internal circuit.
•
Relay contact control output terminals: Isolated between contact output terminals and
from other input/output terminals and internal circuit.
•
Contact input terminals: Not isolated between contact input terminals and from com-
munication terminals. Isolated from other input/output terminals and internal circuit.
•
Relay contact event output terminal: Not isolated from each other; isolated from other
input/output terminals and the internal circuit.
•
RS-485 communication terminals: Not isolated from contact input terminals. Isolated
from other input/output terminals and internal circuit.
•
Power terminals: Isolated from other input/output terminals and internal circuit.
•
Grounding terminals: Isolated from other input/output terminals and internal circuit.
Environmental Conditions
•
Normal operating conditions:
Ambient temperature: 0 to 50
C (40
C or less for side-by-side close installation)
Temperature change rate: 10
C/h or less
Ambient humidity: 20 to 90% RH (no condensation allowed)
Magnetic field: 400 A/m or less
Continuous vibration at 5 to 14 Hz: Full amplitude of 1.2 mm or less
Continuous vibration at 14 to 150 Hz: 4.9 m/s
2
or less
Short-period vibration: 14.7 m/s
2
, 15 seconds or less
Shock: 14.7 m/s
2
or less, 11 ms
Installation height: Height above sea level of 2000 m or less
Warm-up time: 30 minutes or more after power on
•
Transportation and storage conditions:
Temperature: -25 to 70
C
Temperature change rate: 20
C/h or less
Humidity: 5 to 95% RH (no condensation allowed)
•
Effects of changes in operating conditions
-
Effects from changes in ambient temperature:
-
On voltage or thermocouple input,
1
V/
C or
0.01% of F.S./
C,
whichever is larger
-
On RTD input,
0.05
C/
C (ambient temperature) or less
-
On analog output,
0.05% of F.S./
C or less
-
Effects from power supply fluctuation (within rated voltage range)
-
On analog input,
1
V/10 V or
0.01% of F.S./10 V, whichever is
larger
-
On analog output,
0.05% of F.S./10 V or less