1-12
<T
oc>
<1. Installation>
IM 05E01D02-41E
1st Edition : May 31,2000-00
■
UP350 Standard Type
1
2
3
4
5
6
7
8
9
10
21
22
23
24
25
26
27
28
29
30
11
12
13
14
15
16
17
18
19
20
12
13
14
15
100
Two-wire transmitter
PV input
0.4 to 2.0 V DC signal
Loop power
supply
14.5 to
18.0 V DC
External
resistor
(Note)
Note: Connecting a 100
resistor to the terminals is optional.
Model: X010-100-2 (resistor with M3.5 crimp-on terminal lugs)
15 V DC Power Supply Wiring to Two-wire Sensor
4-20mADC
OT=0 (factory-set default)
Time proportional control
Relay output (terminals , and )
OT=1
Correspondence
between parameter OT and control output types
Time proportional control
Voltage pulse output (terminals and )
OT=2
Current output
(terminals and )
OT=3
On-off control
Relay output (terminals , and )
* OT is a setup parameter.
You can change the settings of the parameter OT to change the control output types. See “2. Initial Settings,” for more information.
1
2
3
16
17
16
17
1
2
3
Contact rating: 12 V DC, 10 mA or more
19
18
Correspondence between parameter DIS and external contact input functions
20
When DIS=3
DI1
DI2
COM
Common
Start program 1 when DI1 = ON
Reset program 1 when DI1 = OFF
Hold program when DI2 = ON
Cancel hold when DI2 = OFF
When DIS=2
Hide setup parameter lock when DI1 = ON
Show setup parameter lock when DI1 = OFF
Common
When DIS=OFF (Factory-set default)
No function
No function
Common
When DIS=1
Start program 1 when DI1 = ON
Reset program 1 when DI1 = OFF
Start program 2 when DI2 = ON
Reset program 2 when DI2 = OFF
Common
19
18
20
DI1
DI2
COM
+5V
+5V
Contact
Transistor contact
* DIS is a setup parameter.
Changing DIS setpoint allows you to change the function of external contact input.
No function
6
5
Event output
4
7
PVE1
PVE2
TME
COM
Relay contact rating: 240 V AC, 1 A
30 V DC, 1 A (resistance load)
Relay
PV event-1 output
PV event-2 output
Time event output
Common
UP
UP
8
9
Power supply
10
L
N
Allowable range: 100 to 240 V AC (
10%)
(free voltage)
50/60 Hz shared
Power supply
CAUTION
Before carrying out wiring, turn off the power
to the controller and check that cables to be
connected are not alive with a tester or the like
because there is a possibility of electric shock.
16
17
Current/voltage
pulse output
4-20 mA DC,
voltage pulse
(12 V)
Control output
+
-
Note:Select the control output
type from the OT
parameter.
14
15
Retransmission output
4-20 mA DC
14
15
15 V DC loop power supply
14.5-18.0VDC
(21 mA DC max.)
* PV retransmission is configured at factory
before shipment.
Load resistance: 600
Ω
or less
* If 15 V DC loop power supply is used,
retransmission output cannot be used.
-
+
-
+
12
13
TC input
11
12
RTD input
13
12
13
mV/V input
Installation category (overvoltage category): II (IEC1010-1)
A
b
B
NOTE
-
+
-
+
12
13
Note: Connecting a 250
Ω
resistor to the terminals is
optional.
Model: X010-250-2 (resistor with M3.5 crimp-on terminal
lugs)
*
When receiving 4-20 mA DC current signals,
set the PV input type to 1-5 V DC (setpoint “41”).
䊏
Receiving 4-20 mA DC Current
Signals with the Controller
250
Ω
4-20mA
PV input
* Not configured at factory before shipment
See “2. Initial Settings,” for more information.
-
+
23
24
RS-485 communication * Wiring can only be carried out
for controllers with communication
functions.
Maximum baud rate: 9600 bps
25
26
27
SDB(+)
SDA(-)
RDB(+)
RDA(-)
SG
1
2
Relay contact output
3
Control output
NC
NO
COM
Contact rating: 250 V AC, 3 A
30 V DC, 3 A (resistance load)
Note: Select the control output type
from the OT parameter.
* Time proportional PID relay contact
output is configured at factory
before shipment.