<2. Initial Settings>
IM 05E01D02-41E
NOTE
The controller may automatically initialize the registered operating parameter setpoints if
any change is made to the data item PV Input Type (IN), Maximum Value of PV Input
Range (RH), Minimum Value of PV Input Range (RL), PV Input Decimal Point Position
(SDP), Maximum Value of PV Input Scale (SH) or Minimum Value of PV Input Scale (SL).
After a change has been made to any of these data items, be sure to verify the registered
operating parameter setpoints to ensure that they are correct. If any data item has been
changed to its default, set it to a required value.
1st Edition : May 31,2000-00