3-2
<Toc>
<3. Programming>
IM 05E01D02-41E
3.2
Example of Program Pattern Setup Charts
Complete the following setup chart before setting programs in the controller. Filling in the
chart makes it easier for you to input program data into the controller. See “3.8 Program
Pattern Setup Charts” for more details.
In the following chart, fill in the fields with bold-face borders.
1.
Maximum value of PV input range: Setpoint of the “Maximum Value of PV Input Range
(RH)” setup parameter
2.
Minimum value of PV input range: Setpoint of the “Minimum Value of PV Input Range
(RL)” setup parameter
3.
PV input unit: Setpoint of the “PV Input Unit (UNIT)” setup parameter
4.
Program time unit: Setpoint of the “Program Time Unit (TMU)” setup parameter
5.
Segment setting method: Setpoint of the “Segment Setting Method (SEG.T)” setup
parameter
6.
Starting target setpoint: Setpoint of the “Starting Target Setpoint (SSP)” program
parameter
7.
Start code: Setpoint of the “Start Code (STC)” program parameter
8.
Junction code: Setpoint of the “Junction Code (JC)” program parameter
9.
Target setpoint, Segment time, PV events 1 and 2, and Time event: Setpoint of each
program parameter
10. Draw the program pattern.
100%
0%
Maximum value of PV
input range (RH)
Minimum value of PV
input range (RL)
Unit
100
0
°
C
4
5
10
6
7
8
9
Segment No.
Target setpoint (SP)
Segment time (TM)
Event type (AL1)
Event setpoint (A1)
Event type (AL2)
Event setpoint (A2)
On time of time event (EON)
PV event 1
PV event 2
Time event
Off time of time event (EOF)
Deviation upper/lower-limit alarm (setpoint: “7”)
Deviation bandwidth (setpoint: “5
°
C”)
Not used in this example
Not used in this example
The event output turns on 20 minutes after the start of program operation. (setpoint: “20 min”)
The event output turns off 100 minutes after the start of program operation. (setpoint: “1 hr and 40 min”)
Program time unit (TMU)
Segment setting method (SEG.T)
3
1
2
Starting target setpoint (SSP)
Start code (STC)
Junction code (JC)
Hour, minute
Time setting
25
°
C
80
°
C
25
°
C
0
0
1
2
3
4
5
6
7
8
9
10
80
°
C
80
°
C
0
°
C
20 min
1 hr and
20 min
10 min
Not used in this example
Example of Chart Entries
1st Edition : May 31,2000-00