<3. Programming>
3-11
IM 05E01D02-41E
1st Edition : May 31,2000-00
3.6
Lists of Program Parameters
*
Parameters relating to PV or program setpoints should all be set in real numbers.
For example, use temperature values to define program setpoints and PV event
setpoints for temperature input.
*
The “User Setting” column in the table below is provided for the customer to record
setpoints.
*
The “Target Item in CD-ROM” column in the table below provides references from
User’s Manual (Reference) (CD-ROM version) which describes items in more detail
and items that are not contained in this manual.
●
Program-1 Parameters
PV event-1 type
OFF, 1 to 10
1: PV high limit (energized, no stand-by action)
2: PV low limit (energized, no stand-by action)
3: Deviation high limit (energized, no stand-by action)
4: Deviation low limit (energized, no stand-by action)
5: Deviation high limit (de-energized, no stand-by action)
6: Deviation low limit (de-energized, no stand-by action)
7: Deviation high and low limits (energized, no stand-by action)
8: Deviation within high and low limits (energized, no stand-by action)
9: PV high limit (de-energized, no stand-by action)
10: PV low limit (de-energized, no stand-by action)
OFF
PV event-1 setpoint
PV alarm: -100.0 to 100.0% of PV input range
Deviation alarm: -100.0 to 100.0% of PV input range span
Use the “HY1” setup parameter to set the hysteresis of PV event 1.
PV high limit:
0.0% of PV
input range.
Deviation alarm:
0.0% of PV
input range span.
Other PV alarms:
0.0% of PV
input range.
PV event-2 type
OFF, 1 to 10
1: PV high limit (energized, no stand-by action)
2: PV low limit (energized, no stand-by action)
3: Deviation high limit (energized, no stand-by action)
4: Deviation low limit (energized, no stand-by action)
5: Deviation high limit (de-energized, no stand-by action)
6: Deviation low limit (de-energized, no stand-by action)
7: Deviation high and low limits (energized, no stand-by action)
8: Deviation within high and low limits (energized, no stand-by action)
9: PV high limit (de-energized, no stand-by action)
10: PV low limit (de-energized, no stand-by action)
OFF
Ref.3.4(5)
Ref.3.4(6)
Ref.5.2(1)
Ref.5.1(1)
PV event-2 setpoint
PV alarm: -100.0 to 100.0% of PV input range
Deviation alarm: -100.0 to 100.0% of PV input range span
Use the “HY2” setup parameter to set the hysteresis of PV
event 2.
On time of
Time Event
OFF, 0.00 to 99.59 (hour and minute or minute and second)
Use the TMU setup parameter to set the time unit. The time
unit is the same as that of the program.
OFF
Off time of
Time Event
OFF, 0.00 to 99.59 (hour and minute or minute and second)
Use the TMU setup parameter to set the time unit. The time
unit is the same as that of the program.
OFF
0
Starting target
setpoint
0.0 to 100.0% of PV input range
0.0% of PV
input range
0.0% of PV
input range
Start code
0: Operation begins with the starting target setpoint (1.SSP).
1: Ramp-prioritized PV start
2: Time-prioritized PV start
Segment-1
target setpoint
0.0 to 100.0% of PV input range
Parameter
Symbol
Name of
Parameter
Setting Range and Description
Initial Value
Target Item
in CD-ROM
PV high limit:
0.0% of PV
input range.
Deviation alarm:
0.0% of PV
input range span.
Other PV alarms:
0.0% of PV
input range.
User
Setting
(1.AL1)
(1.A1)
(1.AL2)
(1.A2)
(1.EON)
(1.EOF)
(1.SSP)
(1.STC)
(1.SP1)