<3. Programming>
3-17
IM 05E01D02-41E
1st Edition : May 31,2000-00
<Controller Settings>
Setpoint of TMU (Time Unit of Program) Setup Parameter
When changing the setpoint linearly over an hour
0 (factory-set default)
When changing the setpoint linearly over a minute
1
Note: The “Time Unit of Program (TMU)” parameter is the time unit you use when creating programs.
When creating a soak segment during programming, set a time (“hour and minute” or
“minute and second”) rather than a ramp grade.
Target
setpoint
Time
Setpoint
Segment time
Define as “hour and minute”
or “minute and second.”
Target setpoint set for
segment immediately preceding
or the starting target setpoint if this is
the point of starting program operation
For example, configure segment 1 so the temperature rises in increments of 5
⬚
C per
minute from 50
⬚
C to 100
⬚
C, as shown in the figure below.
Target setpoint
Time
Setpoint
100
°
C
50
°
C
Ramp upgrade of
5
°
C per minute
Segment 1
To change the temperature linearly over a minute, set the TMU parameter to “1” (minute
and second) before you begin programming.
When programming the controller, set the Segment-1 Segment Time (1.TM1) parameter to
5
⬚
C.
This allows the controller to raise the setpoint in increments of 5
⬚
C per minute during the
interval of segment 1.