<4. Operations>
4-5
IM 05E01D02-41E
1st Edition : May 31,2000-00
4.4
Starting (PRG)/Stopping (RESET) the Controller
The following operating procedure starts program operation.
1.
Bring the operating display into view (appears at power-on).
Stop (RESET) state
Program pattern 1 starts running
Program pattern 2 starts running
P V
SP
PVE1
TME
PVE2
PRG1
HLD
PRG2
SET/ENT
1
PRG
2
PRG
RESET
Press key for 2 seconds.
Press key for 2 seconds.
1
PRG
2
PRG
PRG1 and PRG2
lamps OFF.
Displays PV.
2.
Press the
1
PRG
key for more than 2 sec-
onds to start program pattern 1.
Run (PRG) state
P V
SP
PVE1
TME
PVE2
PRG1
HLD
PRG2
SET/ENT
1
PRG
2
PRG
RESET
RPG1 lamp
ON.
2.
Press the
2
PRG
key for more than 2 sec-
onds to start program pattern 2.
Run (PRG) state
P V
SP
PVE1
TME
PVE2
PRG1
HLD
PRG2
SET/ENT
1
PRG
2
PRG
RESET
RPG2 lamp
ON.
3.
To stop program operation, press the
RESET
key for more than 2 seconds.
Stop (RESET) state
P V
SP
PVE1
TME
PVE2
PRG1
HLD
PRG2
SET/ENT
1
PRG
2
PRG
RESET
PRG1 and PRG2
lamps OFF.
When in the RESET state, the controller provides the following input/output values.
PV input
Value of process variable
Control output Preset output value (factory-set to 0%)
Event output
OFF