<Toc>
<4. Operations>
4-7
IM 05E01D02-41E
1st Edition : May 31,2000-00
4.5
Enabling/Disabling Hold Mode of Program
Operation
The following operating procedure brings program pattern 1 into a pause during operation.
This procedure also applies to program pattern 2.
NOTE
If a contact input is on (hold mode is set) when the hold mode is enabled and disabled with
the input, the mode cannot be cancelled by key operation.
1.
Bring the operating display into view
(appears at power-on).
P V
SP
PVE1
TME
PVE2
PRG1
HLD
PRG2
SET/ENT
1
PRG
2
PRG
RESET
PRG1 lamp
ON.
Displays PV.
2.
Press the
SET/ENT
key for more than 3 seconds
to call up the menu “OP.PA”.
P V
SP
PVE1
TME
PVE2
PRG1
HLD
PRG2
SET/ENT
1
PRG
2
PRG
RESET
Displays
menu “OP.PA”.
3.
Press the
SET/ENT
key three times to display
the parameter “HOLD”.
P V
SP
PVE1
TME
PVE2
PRG1
HLD
PRG2
SET/ENT
1
PRG
2
PRG
RESET
Displays
parameter
“HOLD”.
4.
Press the
key once to display “1”.
P V
SP
PVE1
TME
PVE2
PRG1
HLD
PRG2
SET/ENT
1
PRG
2
PRG
RESET
Blinks during
change.
To cancel the hold mode, set as
“HOLD = 0”.
5.
Press the
SET/ENT
key once to register the
setpoint. The HLD lamp ON and the con-
troller under program operation comes to a
pause.
P V
SP
PVE1
TME
PVE2
PRG1
HLD
PRG2
SET/ENT
1
PRG
2
PRG
RESET
HLD lamp
ON.
The controller automatically returns to the
display shown at power-on (figure below).
HOLD state
P V
SP
PVE1
TME
PVE2
PRG1
HLD
PRG2
SET/ENT
1
PRG
2
PRG
RESET
HLD lamp
ON.
If you have cancelled the hold mode, press
the
SET/ENT
key for more than 3 seconds to
return to the display shown at power-on.