<5. Troubleshooting and Maintenance>
5-3
IM 05E01D02-41E
1st Edition : May 31,2000-00
■
If a Power Failure Occurs during Operation
●
Momentary power failures shorter than 20 ms
The controller is not affected at all and continues normal operation.
●
Power failures of 20 ms or longer
•
Setting parameters that have already been configured to retain their settings.
•
Auto-tuning is cancelled.
•
After recovery from a power failure, program operation is stopped. The control output
begins with the preset output value.
•
Event output is OFF.