7-4
<Toc>
<7. Function Block Diagram and Descriptions>
IM 05E01D02-41E
1st Edition : May 31,2000-00
■
Contact Input
Changing the setpoint of the parameter DIS (DI function selection) allows you to change
the function of contact input.
●
When DIS=OFF
No function for contact input.
●
When DIS=1 (factory-set default)
Start program 1 (ON)/Reset program 1 (OFF) switching function is assigned to DI1 (contact
input 1).
Start program 2 (ON)/Reset program 2 (OFF) switching function is assigned to DI2 (contact
input 2).
Preset output value is output when the operation is stopped. PV input remain functioning as
normal.
●
When DIS=2
Hide (ON)/Show (OFF) the parameter LOCK (key lock) switching function is assigned to
DI1 (contact input 1).
No function is assigned to DI2 (contact input 2).
●
When DIS=3
Start program 1 (ON)/Reset program 1 (OFF) switching function is assigned to DI1 (contact
input 1).
Hold program (ON)/Cancel hold (OFF) switching function is assigned to DI2 (contact input
2).
Preset output value is output when the operation is stopped. PV input remain functioning as
normal.
■
Control Output
Control output (OUTPUT) selects the output type among the current output, voltage pulse
output, and relay contact output signal.
Preset output value is output when the operation is stopped by key operation or contact
input.
Each function can be set by the following parameters.
Setup Parameters
Function
Parameter
Control output type selection
OT
Control output cycle time
CT
I/O
FUNC
Menu
Preset output
PO
FUNC
Operating Parameters
Function
Parameter
Output limiter
OL, OH
OP.PA
Menu