3-2
<Toc> <Ind>
TI 05C01E02-01E
1st Edition : Oct. 31, 2001-00
3.2 UT130 Parameter Flowchart and Description
HYS
A1
A2
HC
FL
BS
LOC
AT
P
I
D
MR
COL
P o w e r O N
is displayed
?
Yes
No
CTL=SLF
When LOC= -1,
transfers to the
setup parameter
setting display
CTL
Operating parameter setiing dispaly
Operating Display
CTL=PID
Displayed when I = OFF
Displayed for heating/
cooling type
DB
Displayed for heating/cooling type
CT
) Displayed for time-proportional PID control
CTC
Displayed for time-proportional PID control
of heating/cooling type
CTL=ONF
(on/off control)
Displayed only for the "/HBA" option and when AL1 = 25
LOC=
When LOC=-1
Note: If no key is pressed for a period of 2 minutes or more
while in the operating or setup parameter setting display,
the controller automatically returns to operating display.
CTL=SLF is not
permitted for heating/
cooling type.
Displays PV
Displays SP
To switch between PV and SP,
press the key.
SP display lamp
is on.
Note
The data (PV or SP) selected in "DSP" is
displayed at first. (Default: PV display)
(Dynamic Auto Tune)
(PIDcontrol)
To Page 3-4
SP (target setpoint) can be
changed in the operating display.
* Refert to the Measured Input Ranges on
Page 4-1.
Displayed only for the "/AL" or "/HBA" option.
Not displayed when AL1, AL2 = OFF
Not displayed when AL1, AL2 = 21 or 22
Press the key
for at least 3 seconds.
(To operating parameter
setting display)
Press the key
for at least 3 seconds.
(To operating display)
When the measured input range code has
been already set, the operating display shown
below appears.
Press the
key to move
between items.
Note
N O T E
When IN appears, press the
key to display the measured input
range code you want to use, then
press the key to register it.
After this operation, the controller
shows the operating display.
A
A
B
Set "-1" to enter the setup parameter setting
display. But if "LOC=1 or 2" is already set, the
parameter value can not be changed by setting
"LOC=-1" only. To change the parameter value,
set "LOC=0" at first (for disabling keylock),
then set "LOC=-1" once again.
NOTE