1st Edition : Oct. 31, 2001-00
4.4 Setting Alarms
Alarm function is available only for the controller with “/AL” or “HBA” option.
Heater disconnection function is available only for the controller with “/HBA” option.
Timer function is available only for the controller with “/AL/EX” or “/HBA/EX” option.
4.4.1 Setting Alarm Type and Hysteresis
The table below shows the alarm codes and alarm actions.
Note: The alarms numbered 1 to 10 have no waiting
action, while alarms 11 to 20 have a waiting
action.
The waiting action turns off the PV and deviation
alarms that occur from the start of the control
operation until a stable state is reached.
Alarm type
Alarm
type code
Closed contact
during alarm
Open contact
during alarm
Action
Opn and Cls indicate that the relay contact is
opened and closed; (on) and (off) indicate that
the lamp is on and off; and white triangles indicate
temperature control setpoints.
Alarm type
Alarm
type code
Closed contact
during alarm
Open contact
during alarm
Action
Opn and Cls indicate that the relay contact is
opened and closed; (on) and (off) indicate that
the lamp is on and off; and white triangles indicate
temperature control setpoints.
Hysteresis
Temperature setpoint
Deviation setting
Measured value
Opn (on)
Cls (off)
Hysteresis
Hysteresis
Hysteresis
Hysteresis
Temperature setpoint
Temperature setpoint
Deviation setting
Measured value
Hysteresis
Alarm setting
Measured value
Opn (off)
Opn (off)
Cls (on)
Hysteresis
Alarm setting
Measured value
Opn (off)
Cls (on)
7
17
(See note.)
6
16
(See note.)
De-energized
on deviation
low limit
1
11
(See note.)
No alarm
Deviation
high and low
limit
2
12
(See note.)
8
18
(See note.)
Deviation
within high-
and -low-
limit
3
13
(See note.)
Deviation
high limit
9
19
(See note.)
De-energized
on PV
high limit
4
14
(See note.)
Deviation
low limit
10
20
(See note.)
25
24
De-energized
on PV
low limit
Timer
function
(De-energized)
23
Timer
function
5
15
(See note.)
De-energized
on deviation
high limit
21
The contact is closed at input
burnout.
22
FAIL
output
OFF
Measured value
Opn (off)
Opn (off)
Cls (on)
Deviation setting
Hysteresis
Cls (on)
Measured value
Temperature setpoint
Deviation setting
Cls (on)
Hysteresis
Opn (off)
Measured value
Temperature setpoint
Deviation setting
Hysteresis
Opn (on)
Cls
(off)
Alarm setting
Measured value
Hysteresis
Cls (off)
Opn (on)
Alarm setting
Measured value
Measured value
Temperature setpoint
Hysteresis
Deviation setting
Opn (on)
Cls (off)
The output contact is opened in the following events:
¥ Program error
¥ ROM error
¥ RAM error
¥ power failure
External contact
(TMR)
Opn
(off)
Opn
Opn
(off)
Cls (on)
Timer setting
Time
The output contact closes when the timer setting has passed
since external contact was closed. Then, the output contact
opens immediately when external contact is opened.
External contact
(TMR) Opn
Cls(off)
Opn
Cls
(off)
Opn(on)
Timer setting
Time
The output contact opens when the timer setting has passed
since the contact was closed. Then, the output contact closes
immediately when external contact is opened.
The controller starts measuring the current from
the heater disconnection detector when 100
milliseconds have passed after turning on the
output.
Cls
Cls
(on)
Heater current
Alarm setting
Opn (off)
Abnormal
Alarm output = ON
Normal
Low limit alarm
setpoint
In this area, the alarm output is turned
off even when a measured value falls
below the low limit alarm setpoint.
Time
Power-on
¡C
Taken as
normal.
Waiting action
Cls
Blinking
Blinking
¥ A/D converter error
¥ RJC error
¥ EEPROM error
PV
high limit
PV
low limit
Fault
diagnosis
output
Cls
(on)
Opn
(off)
Cls
(on)
Heater
Disconnection
alarm
Opn
(Energized)