IM 05P08D31-11EN page 10/12
■
Tuning Parameter
Menu symbol:
(TUNE)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(SC)
Super function
OFF: Disable
1: Overshoot suppressing function
(normal mode)
2: Hunting suppressing function
(stable mode)
Enables to answer the wider
characteristic changes compared
with response mode.
3: Hunting suppressing function
(response mode)
Enables quick follow-up and short
converging time of PV for the
changed SP.
4: Overshoot suppressing function
(strong suppressing mode)
Note: Setpoints 2 and 3 must be
used in PID control or PI control.
Disabled in the following controls:
1) ON/OFF control, 2) PD control,
3) P control.
Do not use the function for the
control processes with response
such as flow or pressure control.
OFF
(LP1)
EASY
(LP2)
(AT.TY)
Auto-tuning type
0: Normal
1: Stability
0
(LP1)
STD
(LP2)
(AR)
Anti-reset windup
(excess integration
prevention)
AUTO, 50.0 to 200.0%
AUTO
(LP1)
(LP2)
(OPR)
Output velocity limiter
OFF: Disable
0.1 to 100.0%/s
OFF
(LP1)
(LP2)
(MPON)
Manual preset output
number selection
Select the output used in MAN mode
when switched from AUTO to MAN
mode.
OFF: Hold the control output in AUTO
mode (bumpless)
1: Use manual preset output 1 (output
bump)
2: Use manual preset output 2 (output
bump)
3: Use manual preset output 3 (output
bump)
4: Use manual preset output 4 (output
bump)
5: Use manual preset output 5 (output
bump)
OFF
(LP1)
(LP2)
to
(MPO1 to MPO5)
Manual preset output 1
to 5
-5.0 to 105.0%
However, output is limited to the
output high limit and low limit.
0.0%
Table
below
Use the following table to record the manual preset output setting value.
Parameter
n=1
n=2
n=3
n=4
n=5
Loop-1
MPOn
Loop-2
MPOn
■
Zone Control Parameter
Menu symbol:
(ZONE)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
to
(RP1 to RP3)
Reference point 1 to 3
Set reference points at which switch
-
ing is carried out between groups of
PID constants according to the given
temperature zone.
0.0 to 100.0% of PV input range (EU)
(RP1 ≤ RP2 ≤ RP3)
100.0%
of PV
input
range
Table
below
STD
(RHY)
Zone PID switching
hysteresis
Hysteresis can be set for switching at
a reference point.
0.0 to 10.0% of PV input range span
(EUS)
0.5 %
of PV
input
range
span
(RDV)
Reference deviation
Set a deviation from SP. The PID for
reference deviation is used if there
is a larger deviation than the preset
reference deviation.
OFF: Disable
0.0 + 1 digit to 100.0% of PV input
range span (EUS)
OFF
For Zone control, set the setup parameter ZON (zone PID selection) to Zone PID se-
lection.
Use the following table to record the reference point setting value.
Parameter
Loop-1
Loop-2
n=1
n=2
n=3
n=1
n=2
n=3
RPn
■
P Parameter (for Ladder Program)
Menu symbol:
(PPAR)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
to
(P01 to P10)
P01 to P10 parameter
-19999 to 30000 (Set a decimal point
position using LL50A Parameter Set-
ting Software.)
0
Table
below
STD
Parameter
n=01
n=02
n=03
n=04
n=05
n=06
n=07
n=08
n=09
n=10
Pn
Setup Parameters
Hold down the PARA key and Left arrow key simultaneously for 3 seconds to move
from the Operation Display or Operation Parameter Setting Display to the Setup Pa-
rameter Setting Display.
Press the DISP key once to return to the Operation Display.
Menu
DISP key
SET/ENTER key
PARA key
key
key
key
key
key
Operation Dsipaly
Parameter
Parameter
Parameter
Parameter
Parameter
Parameter
END
Menu
END
Menu
END
END
Menu Display and
Parameter Setting
Display are changed
in a circular pattern.
Move to the Operation Parameter Setting Display:
Hold down the PARA key for 3 sec.
Hold down PARA key and
Left arrow key simultaneously for 3 sec.
Operation for Setting
· To select the parameter setting displayed as the initial value, press the Down arrow
key to move to the next parameter.
· To change and set the parameter setting, press the SET/ENTER key to start the set-
point blinking. The blinking state allows you to make changes (setting mode). Use the
Up/Down/Left/Right arrow keys to change the setpoint. Press the SET/ENTER key to
register the setting.
Note that there are some parameters which are not displayed depending on the Model
and Suffix codes, control type (CNT), etc. The parameters for professional setting mode
(LEVL: PRO) are not described in this manual. See User’s Manual (IM 05P08D31-
01EN).
(LP1): Loop-1, (LP2): Loop-2
■
Control Function Setting Parameter
Menu symbol:
(CTL)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(CNT)
Control type
PID: PID control
ONOF: ON/OFF control (1 point of
hysteresis)
ONOF2: ON/OFF control (2 points of
hysteresis)
PID
EASY
(SPGR.)
Number of SP groups
Set a number of SP groups to use.
1 to 4
4
STD
(ZON)
Zone PID selection
If set to “SP group number selection,”
allows PID constants to be selected
for each SP group.
If set to “Zone PID selection,”
automatically selects PID constants
according to the range set in the
Reference point.
0: SP group number selection 1
1: Zone PID selection (selection by PV)
2: Zone PID selection (selection by
target SP)
3: SP group number selection 2
4: Zone PID selection (selection by SP)
0
(PIDG.)
Number of PID groups
Set a number of PID groups to use.
1 to 4
4
■
PV Input Setting Parameter
Menu symbol:
(PV)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(IN)
PV input type
OFF: Disable
K1: -270.0 to 1370.0
0
C / -450.0 to 2500.0
0
F
K2: -270.0 to 1000.0
0
C / -450.0 to 2300.0
0
F
K3: -200.0 to 500.0
0
C / -200.0 to 1000.0
0
F
J: -200.0 to 1200.0
0
C / -300.0 to 2300.0
0
F
T1: -270.0 to 400.0
0
C / -450.0 to 750.0
0
F
T2: 0.0 to 400.0
0
C / -200.0 to 750.0
0
F
B: 0.0 to 1800.0
0
C / 32 to 3300
0
F
S: 0.0 to 1700.0
0
C / 32 to 3100
0
F
R: 0.0 to 1700.0
0
C / 32 to 3100
0
F
N: -200.0 to 1300.0
0
C / -300.0 to 2400.0
0
F
E: -270.0 to 1000.0
0
C / -450.0 to 1800.0
0
F
L: -200.0 to 900.0
0
C / -300.0 to 1600.0
0
F
U1: -200.0 to 400.0
0
C / -300.0 to 750.0
0
F
U2: 0.0 to 400.0
0
C / -200.0 to 1000.0
0
F
W: 0.0 to 2300.0
0
C / 32 to 4200
0
F
PL2: 0.0 to 1390.0
0
C / 32.0 to 2500.0
0
F
P2040: 0.0 to 1900.0
0
C / 32 to 3400
0
F
WRE: 0.0 to 2000.0
0
C / 32 to 3600
0
F
JPT1: -200.0 to 500.0
0
C / -300.0 to 1000.0
0
F
JPT2: -150.0 to 150.0
0
C / -200.0 to 300.0
0
F
PT1: -200.0 to 850.0
0
C / -300.0 to 1560.0
0
F
PT2: -200.0 to 500.0
0
C / -300.0 to 1000.0
0
F
PT3: -150.00 to 150.00
0
C / -200.0 to 300.0
0
F
0.4-2V: 0.400 to 2.000 V
1-5V: 1.000 to 5.000 V
4-20: 4.00 to 20.00 mA
0-2V: 0.000 to 2.000 V
0-10V: 0.00 to 10.00 V
0-20 : 0.00 to 20.00 mA
-1020: -10.00 to 20.00 mV
0-100: 0.0 to 100.0 mV
OFF
EASY
(UNIT)
PV input unit
-: No unit, C: Degree Celsius
-: No unit, - -: No unit, - - -: No unit,
F: Degree Fahrenheit
C
(RH)
Maximum value of PV
input range
Depends on the input type.
- For temperature input -
Set the temperature range that is
actually controlled. (RL<RH)
- For voltage / current input -
Set the range of a voltage / current
signal that is applied.
The scale across which the voltage/
current signal is actually controlled
should be set using the maximum
value of input scale (SH) and mini-
mum value of input scale (SL).
(Input is always 0% when RL = RH.)
Depends
on the
input type
(RL)
Minimum value of PV
input range
Depends
on the
input type
(SDP)
PV input scale decimal
point position
0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
4: Four decimal places
Depends
on the
input type
(SH)
Maximum value of PV
input scale
-19999 to 30000, (SL<SH),
| SH - SL | ≤ 30000
Depends
on the
input type
(SL)
Minimum value of PV
input scale
Depends
on the
input type
(BSL)
PV input burnout action
OFF: Disable
UP: Upscale
DOWN: Downscale
Depends
on the
input type
STD
(A.BS)
PV analog input bias
-100.0 to 100.0% of each input range
span (EUS)
0.0 % of
PV input
range
span
(A.FL)
PV analog input filter
OFF, 1 to 120 s
OFF
W: W-5% Re/W-26% Re(Hoskins Mfg.Co.). ASTM E988, WRE: W97Re3-W75Re25