background image

IM 05P08D31-11EN  page 6/12

■  Parameters to be set

Control Type (Loop-1/Loop-2)

Parameter Symbol Name of Parameter

Setting Range

CNT

Control type

PID: PID control

ONOF: ON/OFF control (1 point of hysteresis)

ONOF2: ON/OFF control (2 points of hysteresis)

Note:  Some setpoints may not be displayed depending on the model and suffix codes.

Input Function (Loop-1/Loop-2)

Parameter Symbol Name of Parameter

Setting Range

IN

PV input type

OFF: Disable (displayed for loop-1 only)

K1: -270.0 to 1370.0 

0

C / -450.0 to 2500.0

 

0

F

K2: -270.0 to 1000.0 

0

C / -450.0 to 2300.0

 

0

F

K3: -200.0 to 500.0 

0

C / -200.0 to 1000.0

 

0

F

J: -200.0 to 1200.0 

0

C / -300.0 to 2300.0

 

0

F

T1: -270.0 to 400.0 

0

C / -450.0 to 750.0

 

0

F

T2: 0.0 to 400.0 

0

C / -200.0 to 750.0

 

0

F

B: 0.0 to 1800.0 

0

C / 32 to 3300

 

0

F

S: 0.0 to 1700.0 

0

C / 32 to 3100

 

0

F

R: 0.0 to 1700.0 

0

C / 32 to 3100

 

0

F

N: -200.0 to 1300.0 

0

C / -300.0 to 2400.0

 

0

F

E: -270.0 to 1000.0 

0

C / -450.0 to 1800.0

 

0

F

L: -200.0 to 900.0 

0

C / -300.0 to 1600.0

 

0

F

U1: -200.0 to 400.0 

0

C / -300.0 to 750.0

 

0

F

U2: 0.0 to 400.0 

0

C / -200.0 to 1000.0

 

0

F

W: 0.0 to 2300.0 

0

C / 32 to 4200

 

0

F

PL2: 0.0 to 1390.0 

0

C / 32.0 to 2500.0

 

0

F

P2040: 0.0 to 1900.0 

0

C / 32 to 3400

 

0

F

WRE: 0.0 to 2000.0 

0

C / 32 to 3600

 

0

F

JPT1: -200.0 to 500.0 

0

C / -300.0 to 1000.0

 

0

F

JPT2: -150.00 to 150.00 

0

C / -200.0 to 300.0

 

0

F

PT1: -200.0 to 850.0 

0

C / -300.0 to 1560.0

 

0

F

PT2: -200.0 to 500.0 

0

C / -300.0 to 1000.0

 

0

F

PT3: -150.00 to 150.00 

0

C / -200.0 to 300.0

 

0

F

0.4-2V: 0.400 to 2.000 V

1-5V: 1.000 to 5.000 V

4-20: 4.00 to 20.00 mA

0-2V: 0.000 to 2.000 V

0-10V: 0.00 to 10.00 V

0-20: 0.00 to 20.00 mA

-1020: -10.00 to 20.00 mV

0-100: 0.0 to 100.0 mV

UNIT

PV input unit

-: No unit, C: Degree Celsius

-: No unit, - -: No unit, - - -: No unit, F: Degree Fahrenheit

RH

Maximum value of 

PV input range

Depends on the input type.

- For temperature input -

Set the temperature range that is actually controlled. 

(RL<RH)

- For voltage / current input -

Set the range of a voltage / current signal that is applied.

The scale across which the voltage / current signal is 

actually controlled should be set using the maximum value 

of input scale (SH) and minimum value of input scale (SL).

(Input is always 0% when RL = RH.)

RL

Minimum value of 

PV input range

SDP

PV input scale 

decimal point 

position

0: No decimal place

1: One decimal place

2: Two decimal places

3: Three decimal places

4: Four decimal places

SH

Maximum value of 

PV input scale

-19999 to 30000, (SL<SH), | SH - SL | ≤ 30000

SL

Minimum value of 

PV input scale

Note 1: SDP, SH, and SL are displayed only for voltage/current input.

Note 2: W: W-5%Re/W-26%Re (Hoskins Mfg.Co.), ASTM E988

Output Function (Loop-1/Loop-2)

Parameter Symbol

Name of Parameter

Setting Range

OT

Output type selection

Output type

00

Lit when the loop-2 

parameter is displayed

Symbol

The LP2 lamp is lit while the output type 

selection parameter for loop-2 is displayed.

00: OFF

01: OUT terminals (voltage pulse)

02: OUT terminals (current)

03: OUT terminals (relay)

06: OUT2 terminals (relay)

07: OUT2 terminals (voltage pulse)

08: OUT2 terminals (current)

CT

Control output cycle time

The LP2 lamp is lit while the control output 

cycle time parameter for loop-2 is displayed.

0.5 to 1000.0 s

4.  Setting Alarm Type

The following operating procedure shows an example of changing the alarm-1 type 

(factory default: PV high limit alarm) to PV low limit alarm (setpoint: 02).

1.

2.

3.

4.

5.

6.

MODE menu is displayed.

Press the SET/ENTER key.

Press the SET/ENTER key.

Hold down the key for 3 seconds.

Show the Operation Display.

ALRM menu is displayed.

Press the SET/ENTER key.

Energized/De-energized

Latch action

Stand-by action

Symbol

● 

To change the alarm type, change the last 2 digits of the 

   5-digit value.

● 

Stand-by action and excitation are turned on or off by 

   selecting 1 or 0. (See “  Setting Display of Alarm Type.”)

● 

For the latch action, see User ’s   Manual (IM 05P08D31-01EN).

The parameter AL1 (alarm-1 type) is 

displayed.

The last digit of the setpoint blinks.

Change the setpoint using the Up/Down arrow keys 

to increase and decrease the value and 

the Left/Right arrow keys to move between digits. 

Press the Right arrow key until 

ALRM menu appears.

The alarm-1 type setpoint 02 (PV 

low limit)

is registered.

After the setup is completed, press 

the DISP key once to return to the 

Operation Display.

Hysteresis

Alarm setpoint

PV

SP or Target SP

Hysteresis

PV

Deviation setpoint

SP or Target SP

Deviation 

setpoint

PV

Hysteresis Hysteresis

Open 

(

unlit

)

Closed 

(lit)

SP or Target SP

PV

Deviation setpoint

Hysteresis

-

-

SP or Target SP

PV

Hysteresis Hysteresis

Deviation 

setpoint

Open 

(

unlit

)

SP or 

Target SP

Alarm setpoint

Hysteresis

SP or 

Target SP

Hysteresis

Alarm setpoint

Alarm setpoint

Output

Hysteresis

Closed

(lit)

Hysteresis

Alarm setpoint Output

Alarm setpoint

Hysteresis

PV

Hysteresis

Alarm setpoint

PV

SP or Target SP

Hysteresis

PV

Deviation setpoint

SP or Target SP

Deviation 

setpoint

PV

Hysteresis Hysteresis

SP or Target SP

PV

Deviation setpoint

Hysteresis

SP or Target SP

PV

Hysteresis Hysteresis

Deviation 

setpoint

Closed 

(unlit)

SP or 

Target SP

Alarm setpoint

Hysteresis

SP or 

Target SP

Hysteresis

Alarm setpoint

Alarm setpoint

Hysteresis

PV

Alarm setpoint

Output

Hysteresis

Hysteresis

Alarm setpoint Output

No alarm (00)

Alarm Action (De-energized)

PV high limit (01)

Analog input PV high limit (19)

Analog input PV2 high limit (21)

PV low limit (02)

Analog input PV low limit (20)

Analog input PV2 low limit (22)

SP high limit (03)

Target SP high limit (09)

SP low limit (04)

Target SP low limit (10)

Deviation high limit (05)

Target SP deviation high 

limit (11)

Deviation low limit (06)

Target SP deviation low limit (12)

Deviation high and low 

limits (07)

Target SP deviation high and 

low limits (13)

Deviation within high and low 

limits (08) 

Target SP deviation within high 

and low limits (14)

Control output high limit (15)

Control output low limit (16)

PV velocity (29)

Fault diagnosis alarm (30)

FAIL (31)

Alarm Type (Alarm Setpoint)

Alarm Action (Energized)

Open 

(

unlit

)

Open 

(

unlit

)

Open 

(

lit

)

Closed 

(lit)

Open 

(

unlit

)

Open 

(

lit

)

Closed 

(unlit)

Closed 

(unlit)

Open 

(

lit

)

Closed 

(unlit)

Closed 

(unlit)

Open 

(

lit

)

Open 

(

lit

)

Closed 

(lit)

Closed 

(lit)

Closed 

(lit)

Closed 

(lit)

Closed 

(lit)

Closed 

(lit)

Closed 

(lit)

Closed 

(lit)

Open 

(

unlit

)

Open 

(

unlit

)

Open 

(

unlit

)

Open 

(

unlit

)

Open 

(

unlit

)

Open 

(un

lit

)

Open 

(

lit

)

Open 

(

lit

)

Open 

(

lit

)

Open 

(

lit

)

Open 

(

lit

)

Open 

(

lit

)

Closed 

(unlit)

Closed 

(unlit)

Closed 

(unlit)

Closed 

(unlit)

Closed 

(unlit)

Closed 

(unlit)

Burnout of PV input, ADC failure, RJC error.

For the factory default, the contact output is turned ON in normal operation, 

OFF at the time of FAIL. Control output: OFF or 0%, Alarm output: OFF

Note 1: “Open/closed” shows status of relay contact, and “lit/unlit” shows status of EV (event) lamp.
Note 2:        Positive setpoint,        Negative setpoint

Setting Display of Alarm Type 

Stand-by Action

Energized (0) / De-energized (1)

Alarm type

Without (0) or With (1) 

Stand-by action

Latch action (0/1/2/3/4)

See 

User’s

 Manual (IM 05P08D31-01EN).

PV low limit 

alarm setpoint

Treated

as normal

ºC

Power-on

Time

The alarm output does not turn on

in this region even if the PV valule

is below PV low limit alarm setpoint.

Normal

Abnormal

The alarm output

turns on.

6.   Setting Alarm Setpoint

The following operating procedure shows an example of setting the alarm-1 setpoint 

of group 1 to 180.0.

Before setting the alarm setpoint, check the alarm type.

To change the alarm type, see “5. Setting Alarm Type.” 

1.
2.

3.

4.

5.

6.

Press the Right arrow key.

Press the SET/ENTER key.

SP menu is displayed.

Display the parameter and group that need to be changed.

Blinks during the change. 

Press the SET/ENTER key.

Press the Down arrow key until A1 appears.

Press the SET/ENTER key.

Show the Operation Display.

Display MODE menu with the same procedure as described in 

Setting Alarm Type.

Group

The parameter A1 is displayed.

A1 to A4 represent the alarm-1 to -4 setpoints.

Each parameter and group can be changed 

in the Parameter Setting Displays of alarms

using arrow keys.

Up/Down arrow keys: parameters

Left/Right arrow keys: groups

Change the setpoint using the Up/Down arrow 

keys to increase and decrease the value and 

the Left/Right arrow keys to move between digits.

The setpoint has been registered.

After the setup is completed, press 

the DISP key once to return to the 

Operation Display. 

Initializing parameter values

Parameters that you have changed can be initialized to factory default values or user 

default values. For details, see “Parameter Initialization” in the User’s Manual (IM 

05P08D31-01EN).

Changing the parameter display levels

This operation guide does not explain all the parameters. To display all the param-

eters, you need to change the parameter display level to professional setting mode. 

For details, see “Setting Security Functions” in the User’s Manual (IM 05P08D31-

01EN).

Summary of Contents for UT32A-D

Page 1: ...strument has option S and you are not in the possession of FX1 Model code S or IM Model code S where Model code means for example UT55A Accessories sold separately The following is an accessory sold s...

Page 2: ...Time proportional output ON OFF output Time resolution of control output 10 ms or 0 1 of output whichever is larger Note The control output should always be used with a load of 10 mA or more Alarm Re...

Page 3: ...JIS C 1610 For thermocouple input PV input and remote input with direct input shielded compensating lead wire of cross sectional area less than or equal to 0 75 mm2 is recommended If the cross sectio...

Page 4: ...IM 05P08D31 11EN page 4 12 Intentionally blank Intentionally blank...

Page 5: ...l type For Position proportional type 3 Quick Setting Function Setting of Input and Output The Quick setting function is a function to easily set the basic function of the control ler Turn on the cont...

Page 6: ...setpoint PV SP or Target SP Hysteresis PV Deviation setpoint SP or Target SP Deviation setpoint PV Hysteresis Hysteresis Open unlit Closed lit SP or Target SP PV Deviation setpoint Hysteresis SP or Ta...

Page 7: ...range is 1 to 4 represent group numbers or R To perform auto tuning for the PID of group 1 set the parameter AT to 1 To quit the auto tuning set the parameter to OFF During auto tuning The MAN lamp b...

Page 8: ...rror Initialized to calibrated default value because of corrupted factory default value Faulty Contact us for repair Rightmost decimal point on Symbol display blinks Faulty FRAM Data writing storing t...

Page 9: ...eset rate of change The UPR DNR and TMU are used in combination Oper ating conditions 1 MAN AUTO 2 STOP AUTO 3 Power on 4 SP number change 5 SP change OFF ON OFF LP1 LP2 Alarm Function Setting Paramet...

Page 10: ...key to move to the next parameter To change and set the parameter setting press the SET ENTER key to start the set point blinking The blinking state allows you to make changes setting mode Use the Up...

Page 11: ...0 bps 1200 1200 bps 2400 2400 bps 4800 4800 bps 9600 9600 bps 19200 19 2k bps 38400 38 4k bps 19200 PRI Parity NONE None EVEN Even ODD Odd EVEN STP Stop bit 1 1 bit 2 2 bits 1 DLN Data length 7 7 bits...

Page 12: ...s in this manual All other product names mentioned in this manual are trademarks or registered trademarks of their respective companies Authorised Representative in the EEA Yokogawa Europe BV Address...

Reviews: