background image

IM 05P08D31-11EN   page 7/12

Contents

1.  Monitoring-purpose Operation Displays Available during Operation

2.  Setting Target Setpoint (SP)

3.  Performing/Canceling Auto-tuning

4.  Selecting Target Setpoint Numbers (SPNO.)

5.  Switching between AUTO and MAN

6.  Switching between RUN and STOP

7.  Switching between REM (Remote) and LCL (Local)

8.  Manipulating Control Output in Manual Mode

9.  Troubleshooting

1.  Monitoring-purpose Operation Displays Available during Operation

■  Operation Display Switching Diagram

•  SP Display

  Displays the measured input value on PV display. 

  Displays the target setpoint (SP) on Setpoint display (SP can be changed).

•  OUT Display

  Displays the measured input value on PV display.

  Displays the control output value (OUT) on Setpoint display (OUT can be changed 

in manual mode).

  Displays the valve’s feedback input value (at 0 to 100% valve opening) in Position 

proportional control.

 

Loop-1 SP Display

(SP can be changed.)

Loop-1 OUT Display

(OUT can be changed.)

Loop-2 SP Display

(LP2 lamp is lilt)

(SP can be changed.)

Loop-2 OUT Display

(LP2 lamp is lilt)

(OUT can be changed.)

Loop-1/Loop-2 

PV Display

(LP2 lamp is lilt)

(display only)

After showing the OUT Display, press the DISP key to show the following displays 

conditionally. 

For details, see User’s Manual (IM 05P08D31-01EN).

•  PID Number Display (display only) (factory default: non-display)

• 

Heater Break Alarm-1 Current Display (display only) (for heater break alarm option only)

• 

Heater Break Alarm-2 Current Display (display only) (for heater break alarm option only)

•  SELECT Displays 1 to 5 (which appear when registered)

2.  Setting Target Setpoint (SP)

1.

2.

3.

4.

When the required value is displayed, 

press the SET/ENTER key to register 

the setpoint.

Show the SP Display (Operation Display).

(This is an example of setting the target      

 setpoint to 150.0).

Press the SET/ENTER key to start the 

last digit of the setpoint blinking.

Blinking allows you to change the value.

To set the setpoint, use the 

Left/Right arrow keys to move 

between digits and the Up/Down 

arrow keys to increase and 

decrease the value.

3.  Performing/Canceling Auto-tuning

Auto-tuning should be performed after setting a target setpoint for loop-1. To perform 

auto tuning on Loop-2, use the AT parameter setting display showing the LP2 lamp.

Make sure that the controller is in automatic mode (AUTO) and in run mode (RUN) 

before auto-tuning. For setting to AUTO, see “5. Switching between AUTO and 

MAN,” and for setting to RUN, see “6. Switching between RUN and STOP.” 

If the setpoint is known in advance or auto-tuning does not find any appropriate PID 

constants, set the PID manually. For setting the PID manually, see User’s Manual (IM 

05P08D31-01EN).

CAUTION

Do not perform auto-tuning for the following processes.

Tune PID manually.

•  Processes with fast response such as flow rate control and pres-

sure control.

•  Processes which do not allow the output to be turned on and off 

even temporarily.

•  Processes which prohibit severe output changes at control 

valves (or other actuators).

•  Processes in which product quality can be adversely affected if 

PV values fluctuate beyond their allowable ranges.

Press the SET/ENTER key.

OFF blinks.

Press the Up/Down arrow keys to display the required setpoint.

Blinks during the change.

The setpoint has been registered. 

This starts auto-tuning.

The limiter can be set to the output during auto-tuning. 

For details, see User’s Manual (IM 05P08D31-01EN). 

The MAN lamp goes off, which means that 

the auto-tuning completed normally.

The setting range is 1 to 4 (represent group numbers) or R.

To perform auto-tuning for the PID of group 1, set the parameter AT to 1.

To quit the auto-tuning, set the parameter to OFF.

During auto-tuning,

• The MAN lamp blinks.

• The OUT symbol appears.

• The output values at 100.0% and 

0% appear alternately. 

1.

2.

3.

4.

5.

6.

7.

8.

Show the Operation Display.

Hold down the PARA key for 

3 seconds to display MODE menu. 

Press the SET/ENTER key.

Press the SET/ENTER key.

Press the Down arrow key until the parameter AT appears.

The parameter AT (auto-tuning switch) is displayed.

The parameter A.M 

(Automatic/Manual switch) is displayed.

Press the SET/ENTER key.

OFF blinks.

Press the Up/Down arrow keys to display the required setpoint.

Blinks during the change.

The setpoint has been registered. 

This starts auto-tuning.

The limiter can be set to the output during auto-tuning. 

For details, see User’s Manual (IM 05P08D31-01EN). 

The MAN lamp goes off, which means that 

the auto-tuning completed normally.

The setting range is 1 to 4 (represent group numbers) or R.

To perform auto-tuning for the PID of group 1, set the parameter AT to 1.

To quit the auto-tuning, set the parameter to OFF.

During auto-tuning,

• The MAN lamp blinks.

• The OUT symbol appears.

• The output values at 100.0% and 

0% appear alternately. 

1.

2.

3.

4.

5.

6.

7.

8.

Show the Operation Display.

Hold down the PARA key for 

3 seconds to display MODE menu. 

Press the SET/ENTER key.

Press the SET/ENTER key.

Press the Down arrow key until the parameter AT appears.

The parameter AT (auto-tuning switch) is displayed.

The parameter A.M 

(Automatic/Manual switch) is displayed.

4.  Selecting Target Setpoint Numbers (SPNO.)

The following operating procedure shows an example of changing the target setpoint 

number (SPNO.) from 1 to 2. Loop-1 and Loop-2 operate simultaneously.

Each SP has its PID group. The PID group set for the parameter PIDN (PID number 

selection) is used.

1.
2.

3.

4.

5.

6.

7.

Show the Operation Display.

Hold down the PARA key for 

3 seconds to display MODE menu.

Press the SET/ENTER key.

SPNO. has been changed to 2.

Blinks during the change.

Change the setpoint using 

the Up/Down arrow keys.

Press the SET/ENTER key.

Press the SET/ENTER key.

The parameter A.M 

(Automatic/Manual switch) is displayed. 

The parameter SPNO. (SP number selection) 

is displayed.

Press the Down arrow key until the 

parameter SPNO. appears.

The setpoint has been registered.

Press the DISP key once to return 

to the Operation Display.

Operation

Guide

UT32A-D

Digital Indicating Controller 

(Dual-loop type)

Operation Guide

This operation guide describes key entries for operating the UT32A-D.

For operations using external contact inputs, see “DI” of “6. Terminal Wiring Diagrams” 

in “Installation and Wiring.” 

If you cannot remember how to carry out an operation during setting, press the DISP 

key once. This brings you to the display (Operation Display) that appears at power-on. 

The scrolling guide is displayed on PV display in the Parameter Setting Display. 

This guide can be turned on/off with the Fn key.

Operations

For details of the each function, refer to the electronic manual. Manuals can be 

downloaded or viewed at the following URL.

Functional

Enhancement

http://www.yokogawa.com/ns/ut/im/

«Standard Code Model»

1.
2.

3.

4.

5.

6.

7.

Show the Operation Display.

Hold down the PARA key for 

3 seconds to display MODE menu.

Press the SET/ENTER key.

SPNO. has been changed to 2.

Blinks during the change.

Change the setpoint using 

the Up/Down arrow keys.

Press the SET/ENTER key.

Press the SET/ENTER key.

The parameter A.M 

(Automatic/Manual switch) is displayed. 

The parameter SPNO. (SP number selection) 

is displayed.

Press the Down arrow key until the 

parameter SPNO. appears.

The setpoint has been registered.

Press the DISP key once to return 

to the Operation Display.

5.  Switching between AUTO and MAN

AUTO and MAN switching for loop-1 can be performed using any of the following: (1) 

A/M key, (2) Contact input, (3) Communication, and (4) User function key.

To switch between auto and manual modes of Loop-2, use the Operation Display 

showing the LP2 lamp.

The figure below shows a direct operation using the A/M key. 

When AUTO and MAN switching function is assigned to the contact input, and the 

contact input is ON, the switching by key operation cannot be performed.

For details, see User’s Manual (IM 05P08D31-01EN).

MAN lamp is lit 

in MAN mode.

Each time you press the               key,
AUTO and MAN is switched alternately.

When AUTO is switched into MAN, the control output value in AUTO mode is held. 

The controller can be operated manually from the hold value.

If the manual preset output is set (MPON parameter ≠ OFF), the controller can be 

operated manually from the arbitrary output value (MPO1 to MPO5 parameters).

6.  Switching between RUN and STOP

RUN and STOP switching can be performed using any of the following: (1) Contact 

input, (2) Parameter, (3) Communication, and (4) User function key.

The following shows an example of switching using the contact input.

(The switching function is assigned to DI2 contact for the factory default.)

For details of other switching methods and the display appearing when the operation 

is started, see User’s Manual (IM 05P08D31-01EN). 

When the controller is stopped, input and outputs are as follows:

PV input

Displays the PV value.

Control output

Displays the preset output value.

The preset output value is set for each PID group. 

Alarm output

Turns the output on in case of an alarm.

Display in STOP mode

“STOP” is displayed on Symbol display and "preset output value" is displayed on 

Data display.

DI2

DI2

210

212

210

212

OFF: Operation RUN

Display in STOP mode

ON: Operation STOP

Preset output (PO)

STOP lamp is lit.

Summary of Contents for UT32A-D

Page 1: ...strument has option S and you are not in the possession of FX1 Model code S or IM Model code S where Model code means for example UT55A Accessories sold separately The following is an accessory sold s...

Page 2: ...Time proportional output ON OFF output Time resolution of control output 10 ms or 0 1 of output whichever is larger Note The control output should always be used with a load of 10 mA or more Alarm Re...

Page 3: ...JIS C 1610 For thermocouple input PV input and remote input with direct input shielded compensating lead wire of cross sectional area less than or equal to 0 75 mm2 is recommended If the cross sectio...

Page 4: ...IM 05P08D31 11EN page 4 12 Intentionally blank Intentionally blank...

Page 5: ...l type For Position proportional type 3 Quick Setting Function Setting of Input and Output The Quick setting function is a function to easily set the basic function of the control ler Turn on the cont...

Page 6: ...setpoint PV SP or Target SP Hysteresis PV Deviation setpoint SP or Target SP Deviation setpoint PV Hysteresis Hysteresis Open unlit Closed lit SP or Target SP PV Deviation setpoint Hysteresis SP or Ta...

Page 7: ...range is 1 to 4 represent group numbers or R To perform auto tuning for the PID of group 1 set the parameter AT to 1 To quit the auto tuning set the parameter to OFF During auto tuning The MAN lamp b...

Page 8: ...rror Initialized to calibrated default value because of corrupted factory default value Faulty Contact us for repair Rightmost decimal point on Symbol display blinks Faulty FRAM Data writing storing t...

Page 9: ...eset rate of change The UPR DNR and TMU are used in combination Oper ating conditions 1 MAN AUTO 2 STOP AUTO 3 Power on 4 SP number change 5 SP change OFF ON OFF LP1 LP2 Alarm Function Setting Paramet...

Page 10: ...key to move to the next parameter To change and set the parameter setting press the SET ENTER key to start the set point blinking The blinking state allows you to make changes setting mode Use the Up...

Page 11: ...0 bps 1200 1200 bps 2400 2400 bps 4800 4800 bps 9600 9600 bps 19200 19 2k bps 38400 38 4k bps 19200 PRI Parity NONE None EVEN Even ODD Odd EVEN STP Stop bit 1 1 bit 2 2 bits 1 DLN Data length 7 7 bits...

Page 12: ...s in this manual All other product names mentioned in this manual are trademarks or registered trademarks of their respective companies Authorised Representative in the EEA Yokogawa Europe BV Address...

Reviews: