background image

IM 05P08D31-11EN   page 8/12

7.  Switching between REM (Remote) and LCL (Local)

Remote and local switching can be performed using any of the following: 

(1) Contact input, (2) Parameter, (3) Communication, and (4) User function key.

LCL (Local)

Control is performed using the target setpoint set on the controller.

REM (Remote)

Control is performed using a setpoint via communication for the target setpoint. The 

following shows an example of switching from local to remote using the parameter.

(Only in cases where the communication is specified.)

For details of other switching methods, see User’s Manual (IM 05P08D31-01EN).

• The PID group for the local SP number is used as PID in remote mode.

NOTE

When the contact input is ON, operation cannot be performed using the parameter, 

communication, or key. When the contact input is OFF and the setting is switched 

using the parameter, communication, or key, the last switching operation is per-

formed.

1.

2.

3.

4.

5.

Show the Operation Display.

Hold down the PARA key 

for 3 seconds to display MODE menu.

Press the SET/ENTER key.

Press the SET/ENTER key.

The REM lamp is lit.

Change the operation mode using 

the Up/Down arrow keys.

Blinks during the change.

Press the SET/ENTER key.

The parameter R.L (REMOTE/LOCAL switch)

is displayed.

1.

2.

3.

4.

5.

Show the Operation Display.

Hold down the PARA key 

for 3 seconds to display MODE menu.

Press the SET/ENTER key.

Press the SET/ENTER key.

The REM lamp is lit.

Change the operation mode using 

the Up/Down arrow keys.

Blinks during the change.

Press the SET/ENTER key.

The parameter R.L (REMOTE/LOCAL switch)

is displayed.

8.  Manipulating Control Output in Manual Mode

This is an example of operating the Loop-1 control output. To operate the Loop-2 

control output, use the OUT Display showing the LP2 lamp.

NOTE

In manual mode, control output is manipulated by operating the keys (the value is 

changed using the Up/Down arrow keys, then outputted as it is).

Even if the SET/ENTER key is not pressed, the control output value changes ac-

cording to the displayed value.

In stop mode (when the STOP lamp is lit), control output cannot be manipulated.

MAN lamp is lit.

Up arrow key:

     increases control output.

Down arrow key: 

     decreases control output.

9. Troubleshooting

■ Troubleshooting Flow

If the Operation Display does not appear after turning on the controller’s power, check the procedures in the following flowchart.

If a problem appears to be complicated, contact our sales representatives.

Is the controller

defective?

Contact us for repair. Problem solved.

No communication

capability

Completely

inactive?

Yes

Yes

Yes

No

No

No

Key

operation

failure?

Yes

No

Yes

Check wiring of the

power terminals.

Check the key lock

setting.

Display

failure?

*

Yes

No

Turn off power, and

then turn it on again.

I/O signal

failure?

Yes

No

Check the 

supply voltage.

Check the 

specifications and polarity

 of connected devices .

Check the communication-

related parameters.

Check the specifications

of communication 

devices.

Check the

communication wiring.

Communication

failure?

No

With

communi-

cation?

Yes

Yes

Normal?

Is the 

key locked?

Check the specifications

of the controller.

Yes

No

Correct?

Correct the error(s).

Cancel the setting.

Check the I/O specifications

of the controller.

* The LCD (a liquid crystal display) is used for 

   a display portion of this product.

   The LCD has a characteristic that the display action 

   becomes late at the low temperature.

   Additionally, the luminance and contrast degradation

   are caused due to aged deterioration.

   However, the control function is not affected.

■ 

Remedies if Power Failure Occurs 

during Operations

•  Instantaneous power failure within 20 ms.

  A power failure is not detected. Normal 

operation continues.

•  Power failure for less than about 5 seconds, 

or for about 5 seconds or more.

  Affects the "settings" and "operation sta-

tus."

  For  details,  see  User's  Manual  (IM 

05P08D31-01EN).

NOTE

Write down the settings of parameters for a 

repair request.

  Errors at Power On

The errors shown below may occur in the fault diagnosis when the power is turned on. (For details of Setpoint display and input/output action when each error occurs, see User’s Manual (IM 

05P08D31-01EN).)

PV display 

(Operation 

Display)

Setpoint display

(Operation Display)

Status indicator

(Operation Display)

Parameter that displays error 

details

Error description

Cause and diagnosis

Remedy

Indication off Indication off

Faulty MCU RAM / MCU ROM

MCU RAM / MCU ROM are failed.

Faulty. 

Contact us for repair.

ERR

SYS - - - - -

System data error

System data is corrupted.

Faulty. 

Contact us for repair.

PAR 0004

 

(for user default value error 

only)

Setup parameter (PA.ER)

User (parameter) default value 

error

User parameter is corrupted.

Initialized to factory default value.

Check and reconfigure the initialized 

setting parameters. Error indication is 

erased when the power is turned on 

again.

PAR 0010 

(for setup parameter error 

only)

Setup parameter error

Setup parameter data is corrupted.

Initialized to user default value.

PAR 0020 

(for operation parameter error only)

Operation parameter error

Operation parameter data is corrupted.

Initialized to user default value.

SLOT 0001

(0001: Error occurs to all 

hardware of E1-terminal 

areas.)

Setup parameter (OP.ER)

Nonresponding hardware of 

extended function (E1-terminal 

areas)

Inconsistence of system data and 

hardware of extended function.

Nonresponding communication between 

hardware of extended function (E1-terminal 

areas).

Faulty.

Contact us for repair.

Normal 

indication

Normal indication

Rightmost decimal point 

on PV display blinks.

Setup parameter (PA.ER)

Calibration value error

Initialized to calibrated default value because 

of corrupted factory default value.

Faulty.

Contact us for repair.

Rightmost decimal point 

on Symbol display blinks.

Faulty FRAM

Data writing (storing) to FRAM is impossible.

Normal 

indication

Normal indication

LADDER lamp blinks

Setup parameter (LA.ER)

Corrupted ladder program

Ladder program is corrupted. 

Operates without ladder program.

Download the ladder program again.

Normal 

indication

0.000 00000

(Decimal point on the left of 

the Symbol display blinks) 

Setup parameter (OP.ER)

User profile error

User profile is corrupted.

Download the user profile again.

  Errors during Operation

The errors shown below may occur during operation. (For input/output action when each error occurs, see User’s Manual (IM 05P08D31-01EN).)

PV display 

(Operation 

Display)

Setpoint display

(Operation Display)

Status indicator

(Operation Display)

Parameter that displays

error details

Error description

Cause and diagnosis

Remedy

AD.ERR

Normal indication (Note)

Setup parameter (AD1.E)

Analog input terminal ADC error

•PV input

•PV2 input (E1-terminal area)

Analog input terminal AD value error

Faulty.

Contact us for repair.

RJC.E 

(Displays RJC.

E and PV 

alternately.)

Normal indication (Note)

Setup parameter (AD1.E)

Universal input terminal RJC error

•PV input

•PV2 input (E1-terminal area)

Universal input terminal RJC error

Faulty.

Contact us for repair.

Set the parameter RJC to OFF to erase 

error indication.

B.OUT

Normal indication (Note)

Setup parameter (AD1.E)

Analog input terminal burnout error

•PV input

•PV2 input (E1-terminal area)

Analog input terminal sensor burnout

Check wiring and sensor.

Error indication is erased in normal 

operation.

Setup parameter (PV1.E)

PV input burnout error

(Loop-1, Loop-2)

Burnout of analog input connected to PV

Check wiring and sensor of connected 

analog input terminals.

Error indication is erased in normal 

operation.

OVER

-OVER

Normal indication

Setup parameter (PV1.E)

PV input over-scale

PV input under-scale

(PV values out of -5 to 105%)

(Loop-1, Loop-2)

PV input is out of -5 to 105%. Also occurs 

when the data out of range which is the 

ladder calculation result is input.

Check analog input value or ladder 

program.

Normal 

indication

OUT - - - - -

Setup parameter (AD2.E)

Feedback input resistor/current 

burnout

Feedback input burnout

Check wiring of feedback input resistor/

current. Error indication is erased in 

normal operation.

Normal 

indication

Normal indication

LADDER lamp blinks

Setup parameter (LA.ER)

Ladder calculation overflow

Floating point computation for ladder 

calculation is infinite.

Check the ladder program.

Load factor over 100%

Computation does not end within the 

control period (load factor is 100% or 

more).

Change the control period or reduce 

the number of steps for the ladder 

program.

Load factor over 200%

(Forced end)

Computation does not end within the control 

period (load factor is 200% or more).

Change the control period or reduce the 

number of steps for the ladder program.

Ladder program error

Ladder program is corrupted.

Download the ladder program again. If 

the error indication is still not erased, 

there is a fault. Contact us for repair.

0.000 00000

(Decimal point on the left of 

the Symbol display blinks)

Setup parameter (OP.ER)

Peer-to-peer communication error Peer-to-peer communication error

Check that the target devices are 

connected correctly.

Recovery at normal receipt.

AT.E

Normal indication

Setup parameter (PV1.E)

Auto-tuning time-out

(Loop-1, Loop-2)

Auto-tuning does not end even when 24 

hours have elapsed after the start of tuning.

Check the process. Hold down any key to 

erase the error indication

VAT.E

Normal indication

Setup parameter (AD2.E)

Valve position automatic 

adjustment error

Fully-closed valve position is equal to or larger 

than the fully-open valve position after automatic 

valve position adjustment is performed.

Check wiring and valve. Hold down any 

key to erase the error indication.

Normal 

indication

0.000 00000

(Decimal point on the left of 

the Symbol display blinks)

Setup parameter (OP.ER)

Communication error 

(RS-485 communication)

Framing parity error

Buffer overflow 

Inter-character time-out 

Checksum error (PC link communication with 

checksum) 

CRC check error (Modbus/RTU)

LRC check error (Modbus/ASCII)

Check the communication parameters.

Recovery at normal receipt.

Hold down any key to stop blinking.

Normal 

indication

0.000 00000

(Decimal point on the left of 

the Symbol display blinks) 

Setup parameter (OP.ER)

Communication error 

(coordinated operation)

Inconsistence of loop between coordinated 

master and slaves

Check the communication parameters.

Recovery at normal receipt. Change from remote 

to local mode to stop blinking.

When the mode is changed from remote to 

local, SP tracking does not work even if it is 

set to ON.

Communication from coordinated master is 

interrupted for 2 seconds.

Normal 

indication

0.000 00000

(Decimal point on the left of 

the Symbol display blinks) 

Setup parameter (OP.ER)

User profile error 

User profile is corrupted.

Download the user profile again.

Normal 

indication

Normal indication

Rightmost decimal point on 

Symbol display blinks.

Setup parameter (PA.ER)

Faulty FRAM

Writing (storing) data to FRAM is impossible. Faulty. Contact us for repair.

Undefined

Undefined

Faulty MCU / DCU

(ROM / RAM error, corrupted)

MCU / DCU is corrupted.

Faulty. Contact us for repair.

Note: When an error occurs in input shown in Analog input display (Operation display), Setpoint display shows the same symbol as the PV display.

Summary of Contents for UT32A-D

Page 1: ...strument has option S and you are not in the possession of FX1 Model code S or IM Model code S where Model code means for example UT55A Accessories sold separately The following is an accessory sold s...

Page 2: ...Time proportional output ON OFF output Time resolution of control output 10 ms or 0 1 of output whichever is larger Note The control output should always be used with a load of 10 mA or more Alarm Re...

Page 3: ...JIS C 1610 For thermocouple input PV input and remote input with direct input shielded compensating lead wire of cross sectional area less than or equal to 0 75 mm2 is recommended If the cross sectio...

Page 4: ...IM 05P08D31 11EN page 4 12 Intentionally blank Intentionally blank...

Page 5: ...l type For Position proportional type 3 Quick Setting Function Setting of Input and Output The Quick setting function is a function to easily set the basic function of the control ler Turn on the cont...

Page 6: ...setpoint PV SP or Target SP Hysteresis PV Deviation setpoint SP or Target SP Deviation setpoint PV Hysteresis Hysteresis Open unlit Closed lit SP or Target SP PV Deviation setpoint Hysteresis SP or Ta...

Page 7: ...range is 1 to 4 represent group numbers or R To perform auto tuning for the PID of group 1 set the parameter AT to 1 To quit the auto tuning set the parameter to OFF During auto tuning The MAN lamp b...

Page 8: ...rror Initialized to calibrated default value because of corrupted factory default value Faulty Contact us for repair Rightmost decimal point on Symbol display blinks Faulty FRAM Data writing storing t...

Page 9: ...eset rate of change The UPR DNR and TMU are used in combination Oper ating conditions 1 MAN AUTO 2 STOP AUTO 3 Power on 4 SP number change 5 SP change OFF ON OFF LP1 LP2 Alarm Function Setting Paramet...

Page 10: ...key to move to the next parameter To change and set the parameter setting press the SET ENTER key to start the set point blinking The blinking state allows you to make changes setting mode Use the Up...

Page 11: ...0 bps 1200 1200 bps 2400 2400 bps 4800 4800 bps 9600 9600 bps 19200 19 2k bps 38400 38 4k bps 19200 PRI Parity NONE None EVEN Even ODD Odd EVEN STP Stop bit 1 1 bit 2 2 bits 1 DLN Data length 7 7 bits...

Page 12: ...s in this manual All other product names mentioned in this manual are trademarks or registered trademarks of their respective companies Authorised Representative in the EEA Yokogawa Europe BV Address...

Reviews: