6-3
IM 04P02B01-01E
Setup Operations for Convenient Functions (Setting Mode)
6
6.3
Setting the Moving Average (Dot Model)
This section explains the details of setting the moving average function on measurement
channels on the dot model.
Procedure
1.
Hold down the
MENU
key for 3 seconds to enter Setting mode.
2.
Press the
key or
SHIFT
+
key to select
Aux
and then press the
key.
3.
Press the
key or
SHIFT
+
key to select
Moving_AVE
and then press
the
key.
4.
Set each item and press the
key.
Use the
key or
SHIFT
+
key to select values.
For the procedure on how to enter values or characters, see section 4.2.
If you press the
ESC
key in the middle of the operation, the settings entered up
to then are cancelled, and the display returns to a higher level menu.
5.
When the
Setting complete
screen appears, do either of the following:
Press the
key to set other channels.
If you are done, press the
ESC
key.
6.
Hold down the
MENU
key for 3 seconds to return to Operation mode.
Set the channel range.
Set the number of samples of the
moving average. Moving average is
not performed when Off is selected.
The new setting takes effect.
ESC/?
First channel
Last channel
Set=Aux
Aux=Moving_AVE
CH=01-01
Number of samples=Off
01-01 Channel
Setting complete
Explanation
The Number of Samples of Moving Average
The number of samples can be set to a integer between 2 and 16. Select Off when not
using the moving average function.
<Related Topics>
Enabling the moving average function: Section 7.11