7-2
IM 04P02B01-01E
Select On to set relays I01, I02, and I03
to reflash alarm operation.
Select On to set relay I01 to diagnosis
output.
Select the range of relays that are to
operate using AND logic.
Select the relay’s energized or
de-energized operation.
Select the relay’s hold or non-hold
operation.
Select the relay’s hold or non-hold
operation.
Set the interval of the high limit on
rate-of-change alarm.
Set the interval of the low limit on
rate-of-change alarm.
Set the hysteresis of the measurement
channels.
Set the hysteresis of the computation
channels.
The new setting takes effect.
(models with /M1)
ESC/?
Basic=Alarm
Diagnosis=Off
Reflash=Off
AND=None
Act=Energize
Behavior=Nonhold
Indicator=Nonhold
Increase=01
Decrease=01
Hysteresis=0.5%
Math hysteresis=0.0%
Alarm
Setting complete
Applying the Changes and Returning to Operation Mode
Press the
key or
SHIFT
+
key to select
End
and then press the
key. Press
the
key to select
Store
and then press the
key. The changes are applied, and
the screen returns to Operation mode. If you select
Abort
and press the
key, the
changes are discarded, and the screen returns to Operation mode. Press the
ESC
key
to return to the
Basic=
screen.
Explanation
Diagnosis
When set to On, alarm output relay I01 becomes a dedicated diagnosis output relay, and
the operation is fixed to OR, de-energized, and non-hold. Diagnosis output is a function
which outputs a relay signal when an error is detected in the recording section, burnout
detection function, or the A/D converter.
7.1 Changing the Auxiliary Alarm Function