9-21
IM 04P02B01-01E
Operations Related to the Computation Function (/M1 Option)
9
Applying the Changes and Returning to Operation Mode
Press the
key or
SHIFT
+
key to select
End
and then press the
key. Press
the
key to select
Store
and then press the
key. The changes are applied, and
the screen returns to Operation mode. If you select
Abort
and press the
key, the
changes are discarded, and the screen returns to Operation mode. Press the
ESC
key
to return to the
Basic=
screen.
Explanation
Timers
Timer features
• The timer determines the interval used to calculate the report data (the average,
minimum, maximum, sum value), etc.
• The timer is also used to set the interval at which the computed values are printed on
the chart paper.
Number of Timers
There are two timers: Timer No. 1 and 2.
Timer Type
There are two timer modes, absolute time mode and relative time mode.
• Absolute Time Mode
After the computation is started, the timer times out at the times determined by the
reference time (on the hour) and the interval. The reference time is set on the hour
(00 to 23).
Example 1: Reference time: 14:00
Interval:
12h
The timeout times are hour 2 and hour 14.
Example 2: Reference time: 00:00
Interval:
10min
The timeout times are 0 hour, 0 hour 10 min, 0 hour 20 min, ... 23 hour
40 min, and 23 hour 50 min. For example, if computation is started at 9
hour 36 min, the timeout times are 09 hour 40 min, 09 hour 50 min, 10
hour, and so on.
• Relative Time Mode
The clock is started in sync with the starting of the computation, and the timer times
out every specified interval. In this mode, the timer and the clock stop when a power
failure occurs.
Example:
Interval:
00:15
The timer times out every 15 minutes after the computation is started.
Setup Item and Corresponding Display
Display
Description
Absolute
Absolute time mode
Relative
Relative time mode
Ref. Time
Reference time
Interval
Interval
For absolute time mode timers, set the reference time and interval; for relative time mode
timers, set the interval.
Timers That Are Used
The timer that is used can be set for each channel.
<Related Topics>
Setting the timer to be used for each channel: Section 9.6
9.12 Setting the Timer Used in TLOG Computation and Periodic Printout