4-15
IM 04P02B01-01E
Common Operations for Setting Functions and Setup Guide
4
Alarm functions
Item
Description
Reference
Section
Alarms for each channel
Use Alarm in Setting mode.
5.2
Delay high limit alarm/delay low limit alarm
• Alarm type
7.15
Use Personalize > Add function > Alarm delay in Basic Mode and select Use or Not.
If Use is selected, delay high limit alarm and delay low limit alarm become
selectable under Alarm > Type in Setting mode.
5.2
If Not is selected, alarm delay cannot be selected.
• Alarm delay time
6.10
Use Aux > Alm delay T in Setting mode to set the alarm delay time.
High limit on rate-of-change alarm/low limit on rate-of-change alarm
Use Alarm in Setting mode and set the channel to rate-of-change alarm.
5.2
Use Alarm > Increase in Basic Setting mode to set the interval of the high limit on
7.1
rate-of-change alarm; use Alarm > Decrease in Basic Setting mode to set the
interval of the low limit on rate-of-change alarm.
Use the alarm ACK operation
• Relay operation and display operation
7.1
Set Alarm > Behavior in Basic Setting mode to Hold and set Alarm > Indicator
to Hold.
• Executing the alarm ACK operation
3.12
Use FUNC > Alarm ACK in Operation mode to execute the release of the
alarm output.
Set a hysteresis on the alarm occurrence/release value of high limit alarm and low limit alarm
Use Alarm > Hysteresis in Basic Setting mode to set the hysteresis to be applied
7.1
to the high limit alarm and low limit alarm of measurement channels.
Likewise, use Alarm > M_Hysteresis to set the hysteresis to be applied to the high
limit alarm and low limit alarm of computation channels (/M1 option).
Change the alarm output relay operation
If Alarm > Act in Basic Setting mode set to De_energize, alarm output relay is
7.1
energized during normal operation and de-energized when an alarm occurs.
Diagnosis output
Use Alarm > Diagnosis in Basic Setting mode to set the function.
7.1
Recording functions
Item
Description
Reference
Section
Chart speed
Use Chart in Setting mode to set the chart speed.
5.4
Turn trend recording ON/OFF (dot model)
Use Aux > Print out in Setting mode to set whether to trend record on each
6.6
measurement channel.
Change the recording color of measurement channels (dot model).
Use Color in Basic Setting mode to set the recording color of measurement channels. 7.5
Record by compensating for the pen offset along the time axis (pen model)
Use Aux > POC in Setting mode to turn On/Off offset compensation.
7.6
Record by setting recording zone for each channel
Use Aux > Zone in Setting mode to set the recording zone for each channel.
6.4
Partial expanded recording Use Partial in Basic Setting mode and select Use or Not.
7.13
If Use is selected, set the display mode using Aux > Partial in Setting mode.
6.5
If Not is selected, the Aux > Partial item does not appear.
4.4 Function Setup Guide