9-11
IM 04P02B01-01E
Operations Related to the Computation Function (/M1 Option)
9
9.5
Setting the Alarm
This section explains the details of setting alarms for each computation channel.
If you change the computing equation or the recording span, set the alarm again.
Procedure
1.
Hold down the
MENU
key for 3 seconds to enter Setting mode.
2.
Press the
key or
SHIFT
+
key to select
Math
and then press the
key.
3.
Press the
key or
SHIFT
+
key to select
Alarm
and then press the
key.
4.
Set each item and press the
key.
Use the
key or
SHIFT
+
key to select values.
For the procedure on how to enter values or characters, see section 4.2.
If you press the
ESC
key in the middle of the operation, the settings entered up
to then are cancelled, and the display returns to a higher level menu.
5.
When the
Setting complete
screen appears, do either of the following:
Press the
key to set other channels.
If you are done, press the
ESC
key.
6.
Hold down the
MENU
key for 3 seconds to return to Operation mode.
Set the channel range.
The new setting takes effect.
ESC/?
Select the level number between 1 and 4.
Select On to set the alarm. When set
to On, the settings below can be entered.
Select the alarm type.
Select the value used to turn On the alarm.
Turn relay On when outputting alarms on
the relay. This setting is valid only on
models with the /A1, /A2, /A3, /A4, or /A5
option.
Specify the alarm output relay No.
First channel
Last channel
0A-0A CH/level 1
Setting complete
Set=Math
CH=0A-0A
Math=Alarm
Level=1
Alarm=Off
Type=H
Value= 0.00
Relay=Off
Relay number=I01