1-18
IM 04P02B01-01E
Alarm Printout
Alarm information is printed when an alarm occurs or releases.
Time of alarm occurrence/release
Indicates that there are alarms that are not
printed because the alarm printout buffer is full.
Level number
Alarm type
Channel No. or tag
: Alarm occurrence, : Alarm release
• The print condition can be set to (1) print when alarms occur and release, (2) print
only when alarms occur, or (3) do not print.
• Alarms that occur while an alarm printout is in progress are temporarily saved to the
buffer memory in a printout-wait condition. Alarms are cleared from the buffer
memory when they are printed.
• The number alarms that can be stored in the buffer is 8 and 24 on the pen model and
dot model, respectively. Alarms that occur while the buffer is full are not printed. A
buffer overflow mark is printed when there are alarms that cannot be printed because
the buffer is full.
• The time printout format can be selected.
Hour:Minute
Type
* The format of year, month, and day varies depending on the setting (see the next page).
Printout format
Type
Printout format
Hour:Minute:Second
Month:Day:
Hour:Minute
Year:Month:Day:
Hour:Minute:Second
Month:Day:
Hour:Minute:Second
10 : 00
Nov. 09
10 : 00
Nov. 09. 2004
10 : 00 : 00
10 : 00 : 00
Nov. 09
00 : 00 : 00
Periodic Printout
Measured values and other items are printed at the preset interval.
• Printout Contents (for details, see appendix 1)
• Date/time, time ticks (marks that indicate the positions of the date/time on the chart
paper); measured values, alarm status, scale (leftmost and rightmost values of
span) and recording color (pen model) for each channel; and chart speed can be
printed. When pen offset is being executed on the pen model, the pen offset marks
are printed. On the pen model, if a time tick is not printed at the correct position, a
time tick cancel mark (!) is printed.
• Printout of measured values and alarm status can be enabled or disabled for each
channel.
• Printout of the scale and recording colors (pen model) can be enabled or disabled.
The scale can be printed when the recording zone is greater than or equal to 40 mm.
• The measured values for each channel can be selected from the following data types.
Instantaneous value (measured value at the time of periodic printout)
Average value (average of the measured values over an interval)
Minimum value (minimum value of the measured values over an interval)
Maximum value (maximum value of the measured values over an interval)
Minimum value, maximum value, and average value
Sum value (summed value of the measured values over an interval)
• Interval
The printout interval can be set by specifying the value or set automatically in sync
with the chart speed. Periodic printout is disabled at the following chart speeds.
Pen model: Less than or equal to 9 mm/h or greater than or equal to 1600 mm/h
Dot model: 9 mm/h or less, 51 mm/h or greater (18-dot and 24-dot models), and
101 mm/h or greater (6-dot and 12-dot models)
1.4 Recording