5-2
IM 04P02B01-01E
Description
• Selectable Range of Input Range, Span Left, and Span Right
The input range, span left, and span right can be set in the range shown below. Span
left and span right cannot be set to the same value.
DC voltage (Volt)
Range Type
Selectable Span Range
20 mV
–20.00 to 20.00 mV
60 mV
–60.00 to 60.00 mV
200 mV
–200.0 to 200.0 mV
2 V
–2.000 to 2.000 V
6 V
–6.000 to 6.000 V
20 V
–20.00 to 20.00 V
50 V
–50.00 to 50.00 V
Thermocouple (TC)
Range Type
Selectable Span Range (
°
C)
Selectable Span Range (
°
F)
R
0.0 to 1760.0
°
C
32 to 3200
°
F
S
0.0 to 1760.0
°
C
32 to 3200
°
F
B
0.0 to 1820.0
°
C
32 to 3308
°
F
K
−
200.0 to 1370.0
°
C
−
328 to 2498
°
F
E
−
200.0 to 800.0
°
C
−
328.0 to 1472.0
°
F
J
−
200.0 to 1100.0
°
C
−
328.0 to 2012.0
°
F
T
−
200.0 to 400.0
°
C
−
328.0 to 752.0
°
F
N
0.0 to 1300.0
°
C
32 to 2372
°
F
W
0.0 to 2315.0
°
C
32 to 4199
°
F
L
−
200.0 to 900.0
°
C
−
328.0 to 1652.0
°
F
U
−
200.0 to 400.0
°
C
−
328.0 to 752.0
°
F
WRe
0.0 to 2400.0
°
C
32 to 4352
°
F
RTD
Range Type
Selectable Span Range (
°
C)
Selectable Span Range (
°
F)
PT (Pt100)
−
200.0 to 600.0
°
C
−
328.0 to 1112.0
°
F
JPT (JPt100)
−
200.0 to 550.0
°
C
−
328.0 to 1022.0
°
F
Selections
Input Type
/N1 Option
/N3 Option
Cu10 (GE)
Cu10 (L&N)
Cu10 (WEED)
Cu10 (BAILEY)
Cu10: a = 0.00392 at 20
°
C
Cu10: a = 0.00393 at 20
°
C
Cu25*: a = 0.00425 at 0
°
C
Cu1
Cu2
Cu3
Cu4
Cu5
Cu6
Cu25
Selections
Input Type
Note
PR PR40-20
Thermo
PLATI PLATINEL
couple
NiMo NiNiMo
W/WRe W/WRe26
N2
Type N (AWG14)
Kp Kp
vs
Au7Fe
Pt4 Pt25
RTD
Pt3 Pt50
Ni1 Ni100
(SAMA)
Ni2 Ni100
(DIN)
Ni3 Ni120
J263 J263*B
Cu8 Cu53
Cu10 Cu100:
a = 0.00425 at 0
°
C
5.1 Setting the Input range