PAGE 14

MAXA-MI$ER

Ô

UNITARY ENERGY RECOVERY VENTILATOR

MODEL VR011A12H & B12H (STATIONARY) 

 INSTALLATION

INSTRUCTIONS

5257541-UAI-A-0616 / R11A-29YSDW

8.

Press 

ENTER 

again.

Screen will read 

FWU WAIT 

then the program will load.

This could take up to 10 minutes or more. The screen
contents will change several times during the update so 

be

patient…

Wait until base screen reappears. Re-programming is
complete for the firmware. Now that the new firmware is
loaded it is time to restore the backup data from earlier
s t e p .   S c r o l l   t o :  

S t a t u s >   A l a r m s >   S u mm a r y>

Commission> Controller> Update> View Version>
Load Firmware> Backup> Restore 

press 

Enter 

and the

screen will request the user indicate which restore file to
use. The backup files should be named after the units
serial number. Scroll to the appropriate units serial number 
on the screen and press 

Enter

. The restore should only

take 15-20 seconds. Once the restore is complete the SE
unit control will reboot. 

Note: If updating a version "H"

board it may require two firmware updates to take
place. Please verify the active version of firmware after 
updating.

If the unit does not reboot, restart cycle power to the unit
and wait again for re-boot start-up.

If loading more than one file, example upgrading CDR unit
from version 1, you should cycle power after loading the
first file and again after the last file is complete.

It is a good practice to conduct a "RE-LEARN" from within
the menu after the file(s) have been upgraded if the
function of the unit does not appear to be normal. 

Status>

Alarms> Summary> Commission> Controller>

IV - SE Procedures to Setup Operation for ERV

In order for the SE unit controller, SE economizer control
a n d   E R V   t o   o p e r a te   p r o p e r l y   t h e   f o ll o w i n g
changes/settings will need to be performed within the SE
unit control.

1.

Scroll through menus by pressing down on joystick:

Status> Alarms> Summary> Commission> Econ>
Economizer Enable- Make sure this is set to "Yes"

ERV-En

Figure 11

Econ-En

Figure 10

3.

The economizer minimum setting must be set at 50%
or greater.

Status> Alarms> Summary> Commission>
PowerEx>  ERV Enable- Make sure this is set to
"Yes"

4.

Once the  ERV is set to "

Enable

" the ERV will operate

any time the unit is in the occupied mode. The ERV, if
equipped with pivoting wheel, will rotate the wheel out
of the air stream anytime the packaged units
economizer enters the free cooling mode. In order to
test for proper operation the unit must see a call for
cooling (24 vac on the Y1 terminal) and an outdoor
temperature of 55

o

F or less. If the outdoor ambient

temperature is above 55

o

F the unit may not enter free

cooling. If the ambient temperature is above 55

o

F the

packaged unit can be forced into free cooling mode by
doing the following:

5.

Scroll through menus by pressing down on joystick:

Status> Alarms> Summary> Commission>
Controller> Update> Details,

under details press 

Enter 

then scroll to the Service

menu heading, press 

Enter 

then scroll to

 Inputs>

NetworkInputs

, scroll to 

NetOAT

 and change it to a

setting well below the 55

o

F default by toggling the

joystick left or right to increase/decrease the value,
then pressing 

Enter 

to store the new value. If the

setting is now 30

o

F for example the unit should go into

free cooling mode within a few minutes of the
change. Note: Once the NetOAT is forced to a
temperature below 55

o

F

 it will remain at the forced

value for 15 minutes and revert back to default
settings.

For additional details on navigating, changing and
operating the SE unit control board please refer to the 
SE (Smart Equipment) Controls Quick Start Guide
(Document # 1136326-USG-C-0216) that is shipped
with the packaged unit.

2.

Scroll through menus by pressing down on joystick:

Status> Alarms> Summary> Commission>
PowerEx> ERV Enable- Make sure this is set to
"Yes"

Summary of Contents for VR011A12H

Page 1: ...37 Lbs Crated 2 Remove crating and retrieve bag assembly that is inside of UERV 3 All panels must be in place for rigging 4 Lifting straps are needed to lift the unit CAUTION Danger of sharp metallic edges Can cause injury Take care when servicing unit to avoid accidental contact with sharp edges WARNING Electric shock hazard Can cause injury or death Before attempting to perform any service or ma...

Page 2: ...he installation of the UERV 10 Locate provided rolls of and 1 8 gasket material Apply gasket to the middle and bottom decks or the UERV apply the 1 8 gasket to the perimeter of the transition assembly that connects the RTU to the UERV 4 Install the provided balancing damper assembly into the return air section of the RTU See Figure 3 5 Adjusting the balancing damper for the minimum airflow require...

Page 3: ...ee Figure 8 15 Lower the UERV on to the platform support rail then secure the UERV to the adaptor panel using the provided screws 16 On units requiring a top filler panel install panel by tucking the top of the panel under the top of the RTU and angling in so that the bottom of the panel covers the top flange of the UERV Secure with provided screws See Figure 9 Note An equipment support or pressur...

Page 4: ... media is polymeric material that is coated and permanently bonded with a dry desiccant for total enthalpy recovery The wheel is belt driven by PSC motor and drive belt When slowly rotating through counter flowing exhaust and fresh air streams the UERV adsorbs sensible heat and latent heat from the warmer air stream and transfer this total energy to the cooler air stream during the second half of ...

Page 5: ...r dampers installed inside the RTUs return air section Adjustment of the damper is made by loosening the wingnut adjusting the damper blades and then tightening the wingnut before closing the panel and measuring again 4 Once desired the CFM is reached replace the plastic plugs in the access holes in the doors X Maintenance Motor Maintenance All motors use prelubricated sealed bearings no further l...

Page 6: ...Options AA No Options Installed L1 Low Ambient Kit LAK L2 LAK MOA L3 LAK MOA SSJ not used on P models L4 LAK MOA SSJ PS not used on P models L5 LAK SSJ not used on P models L6 LAK SSJ PS not used on P models L7 LAK PS L8 LAK MOA and PS M1 Motorized Outside Air MOA M2 MOA SSJ not used on P models M3 MOA SSJ PS PS not used on P models M4 MOA PS S1 Stop Start Job SSJ not used on P models S2 SSJ PS no...

Page 7: ...PAGE 7 ...

Page 8: ...PAGE 8 ...

Page 9: ...ack Field Harness J160 Jack Damper Motor Harness J161 Jack Damper Exhaust Motor Harness K163 Relay Exhaust Air Motor K164 Relay Fresh Air Motor MPD 1 Missing Pulse Detector Board Optional P48 Plug Fresh Air Motor Harness P50 Plug Wheel Motor Harness P51 Plug Exhaust Air Motor Harness P56 Plug Damper Motor Harness P148 Plug Fresh Air Motor P150 Plug Wheel Motor P151 Plug Exhaust Air Motor P152 Plug...

Page 10: ... p O 5 r e p m a d e k a t n i d e z i r o t o m l a n o i t p O 6 l o r t n o c g o j d n a t r a t s p o t s l a n o i t p O 7 d e e p s O L r o D E M r o f e r i w e r o t p u t e s d e e p s I H e h t s w o h s m a r g a i D s d e e p s O L r o D E M I H r o f d e r i w e b y a m t i n U 1 0 1 K B o t 1 0 1 H W t c e n n o c o s l A O L r o f 1 0 1 D R r o D E M r o f 1 0 1 L B t c e n n o c d...

Page 11: ...EQUIPMENT LAYOUT PAGE 11 ...

Page 12: ... ERV II SE Procedures to Backup Restore 1 Once the packaged unit is powered up the 120 second startup delay begins Once the delay expires there may or may not be a Start Up delay displayed To cancel the second time delay press the Cancel button for six seconds See Figure 1 Startup Figure 1 Update Figure 2 Backup Figure 3 2 Once the control is out of time delay mode press the Joystick down through ...

Page 13: ...ast you return by pressing the joy stick lever up until the Update screen appears Screen will read Contrler Controller Update Enter Cancel Buttons Figure 6 View Ver Figure 7 LoadFirm Figure 8 Confirm Figure 9 USB OK Figure 4 4 Press ENTER Screen will read View Ver Version Load Firm Backup 5 Toggle Joy stick down so the arrow is next to Load Firm 6 Press ENTER Screen shows software versions present...

Page 14: ...it control 1 Scroll through menus by pressing down on joystick Status Alarms Summary Commission Econ Economizer Enable Make sure this is set to Yes ERV En Figure 11 Econ En Figure 10 3 The economizer minimum setting must be set at 50 or greater Status Alarms Summary Commission PowerEx ERV Enable Make sure this is set to Yes 4 Once the ERV is set to Enable the ERV will operate any time the unit is ...

Page 15: ...PAGE 15 MAXA MI ERÔ UNITARY ENERGY RECOVERY VENTILATOR MODEL VR011A12H B12H STATIONARY INSTALLATION INSTRUCTIONS 5257541 UAI A 0616 R11A 29YSDW This Page Intentionally Left Blank ...

Page 16: ...apter panels as required Follow accessory and unit installation manuals q Verify field wiring including the wiring to any accessories q Check all multi tap transformers to insure they are set to the proper incoming voltage q Verify correct belt tension as well as the belt pulley alignment Tighten if needed q Prior to energizing the unit inspect all the electrical connections q Power the unit Bump ...

Reviews: