background image

PAGE 15

MAXA-MI$ER

Ô

UNITARY ENERGY RECOVERY VENTILATOR

MODEL VR028A15M/H & VR028A25H  (STATIONARY) 

 INSTALLATION

INSTRUCTIONS

5257527-UAI-A-0616 / R28A-18YSDW

8.

Press 

ENTER 

again.

Screen will read 

FWU WAIT 

then the program will load.

This could take up to 10 minutes or more. The screen
contents will change several times during the update so 

be

patient…

Wait until base screen reappears. Re-programming is
complete for the firmware. Now that the new firmware is
loaded it is time to restore the backup data from earlier
s t e p .   S c r o l l   t o :  

S t a t u s >   A l a r m s >   S u mm a r y>

Commission> Controller> Update> View Version>
Load Firmware> Backup> Restore 

press 

Enter 

and the

screen will request the user indicate which restore file to
use. The backup files should be named after the units
serial number. Scroll to the appropriate units serial number 
on the screen and press 

Enter

. The restore should only

take 15-20 seconds. Once the restore is complete the SE
unit control will reboot. 

Note: If updating a version "H"

board it may require two firmware updates to take
place. Please verify the active version of firmware after 
updating.

If the unit does not reboot, restart cycle power to the unit
and wait again for re-boot start-up.

If loading more than one file, example upgrading CDR unit
from version 1, you should cycle power after loading the
first file and again after the last file is complete.

It is a good practice to conduct a "RE-LEARN" from within
the menu after the file(s) have been upgraded if the
function of the unit does not appear to be normal. 

Status>

Alarms> Summary> Commission> Controller>

IV - SE Procedures to Setup Operation for ERV

In order for the SE unit controller, SE economizer control
a n d   E R V   t o   o p e r a te   p r o p e r l y   t h e   f o ll o w i n g
changes/settings will need to be performed within the SE
unit control.

1.

Scroll through menus by pressing down on joystick:

Status> Alarms> Summary> Commission> Econ>
Economizer Enable- Make sure this is set to "Yes"

ERV-En

Figure 11

Econ-En

Figure 10

2.

Scroll through menus by pressing down on joystick:

Status> Alarms> Summary> Commission>
PowerEx> ERV Enable- Make sure this is set to
"Yes"

3.

The economizer minimum setting must be set at 50%
or greater.

Status> Alarms> Summary> Commission>
PowerEx>  ERV Enable- Make sure this is set to
"Yes"

4.

Once the  ERV is set to "

Enable

" the ERV will operate

any time the unit is in the occupied mode. The ERV, if
equipped with pivoting wheel, will rotate the wheel out
of the air stream anytime the packaged units
economizer enters the free cooling mode. In order to
test for proper operation the unit must see a call for
cooling (24 vac on the Y1 terminal) and an outdoor
temperature of 55

o

F or less. If the outdoor ambient

temperature is above 55

o

F the unit may not enter free

cooling. If the ambient temperature is above 55

o

F the

packaged unit can be forced into free cooling mode by
doing the following:

5.

Scroll through menus by pressing down on joystick:

Status> Alarms> Summary> Commission>
Controller> Update> Details,

under details press 

Enter 

then scroll to the Service

menu heading, press 

Enter 

then scroll to

 Inputs>

NetworkInputs

, scroll to 

NetOAT

 and change it to a

setting well below the 55

o

F default by toggling the

joystick left or right to increase/decrease the value,
then pressing 

Enter 

to store the new value. If the

setting is now 30

o

F for example the unit should go into

free cooling mode within a few minutes of the
change. Note: Once the NetOAT is forced to a
temperature below 55

o

F

 it will remain at the forced

value for 15 minutes and revert back to default
settings.

For additional details on navigating, changing and
operating the SE unit control board please refer to the 
SE (Smart Equipment) Controls Quick Start Guide
(Document # 1136326-USG-C-0216) that is shipped
with the packaged unit.

Summary of Contents for VR028A15H

Page 1: ...ontact with sharp edges WARNING Electric shock hazard Can cause injury or death Before attempting to perform any service or maintenance turn the electrical power to unit OFF at disconnect switch es Unit may have multiple power supplies MAXA MI ERÔ UNITARY ENERGY RECOVERY VENTILATOR MODEL VR028A15M H VR028A25H STATIONARY INSTALLATION INSTRUCTIONS 5257527 UAI A 0616 R28A 18YSDW ETL Certified per UL ...

Page 2: ... damper frame within reach of field wiring harness See Figure 7 9 Connect the communication wire and power wire located in the accessory wiring bundle in the RTU return air section to the proper terminals on the economizer control board See SSE field harness diagram at the back of this manual See Figure 8 10 Route the provided field wiring harness through the balancing damper into the return air s...

Page 3: ...as the legs will have to be adjusted once the unit is finally set in place 14 Locate provided roll of x 1 gasket material Apply gasket down the center post of the UERV as well as between the platform support rail and adaptor panel 15 Remove screw from the top panel of the RTU in order to enable lifting the top panel of the RTU up at least 2 Note An equipment support or pressure treated 2x6x60 piec...

Page 4: ...transfer surface and laminar flow through the wheel causes this constant flow of recovered energy to represent up to 85 of the difference in total energy contained within the two air streams Sensible and latent heat are the two components of total heat Sensible heat is energy contained in dry air and latent heat is the energy contained within the moisture of the air The latent heat load from the o...

Page 5: ...hould be removed Also if system check out is being conducted at low ambient temperatures technician should be aware that this kit can cause system not to operate 4 Verify that the UERV 3 three phase blower motors are phased sequentially ensuring correct rotation and operation a Disconnect power b Reverse any two field power leads to the UERV c Reapply power MAXA MI ERÔ UNITARY ENERGY RECOVERY VENT...

Page 6: ... rear and unplug J150 and P150 Refer to wiring diagrams in this instruction manual Remove segment and wash with water and or mild detergent To install wheel segments follow steps A through E See Figure 15 Reverse procedure for segment removal A Unlock two segment retainers one on each side of the selected segment opening B With the embedded stiffener facing the motor side insert the nose of the se...

Page 7: ...P models L5 LAK SSJ not used on P models L6 LAK SSJ PS not used on P models L7 LAK PS L8 LAK MOA and PS M1 Motorized Outside Air MOA M2 MOA SSJ not used on P models M3 MOA SSJ PS PS not used on P models M4 MOA PS S1 Stop Start Job SSJ not used on P models S2 SSJ PS not used on P models P1 Pressure Sensor PS Voltage 2 208 230v 3ph 4 460v 3ph 5 575v 3ph 9 208 320v 1ph Duct Type A No Selection on Roo...

Page 8: ...1 04 1 09 1 09 1 09 1 08 1 05 0 99 0 90 0 82 0 75 0 89 0 88 0 87 0 85 0 81 0 75 0 66 0 59 0 5 0 69 0 68 0 65 0 62 0 57 0 5 0 42 0 35 0 25 0 00 0 20 0 40 0 60 0 80 1 00 1 20 1 40 1500 1600 1700 1800 2000 2200 2400 2600 2800 SCFM Equation of line SCFM PD 0 01 0 00036 TABLE 1 PRESSURE DROP in of W C R28 Series 1100 RPM 1000 RPM 900 RPM 800 RPM ...

Page 9: ...PAGE 9 ...

Page 10: ...r Harness J151 Jack Exhaust Air Motor Harness P153 Plug Field Harness P160 Plug Damper Intake Motor Harness P161 Plug Damper Exhaust Motor Harness RS 1 Rotation Sensor Optional S26 Switch Low Ambient Optional S51 Switch Door S52 Switch Damper Intake S53 Switch Damper Exhaust SD Smoke Detector Optional SSJ Climate Smart Board Optional T27 Transformer Control T28 Transformer Step down Optional TB37 ...

Page 11: ... n u r e p o r p r o f l a n i m r e t e g a t l o v e v i t c e l e S 4 h c t i w s t n e i b m a w o l l a n o i t p O 5 r e p m a d e k a t n i d e z i r o t o m l a n o i t p O 6 t r a m S e t a m i l C l o r t n o c g o j d n a t r a t s p o t s l a n o i t p O 7 t i n u p o t f o o r h t i w t c e n n o c o t d e d i v o r p s s e n r a h r e t p a d a g n i h c t a M 8 r e p m a d t s u a h...

Page 12: ...PAGE 12 EQUIPMENT LAYOUT ...

Page 13: ...h an ERV II SE Procedures to Backup Restore 1 Once the packaged unit is powered up the 120 second startup delay begins Once the delay expires there may or may not be a Start Up delay displayed To cancel the second time delay press the Cancel button for six seconds See Figure 1 Startup Figure 1 Update Figure 2 Backup Figure 3 2 Once the control is out of time delay mode press the Joystick down thro...

Page 14: ...ed past you return by pressing the joy stick lever up until the Update screen appears Screen will read Contrler Controller Update Enter Cancel Buttons Figure 6 View Ver Figure 7 LoadFirm Figure 8 Confirm Figure 9 USB OK Figure 4 4 Press ENTER Screen will read View Ver Version Load Firm Backup 5 Toggle Joy stick down so the arrow is next to Load Firm 6 Press ENTER Screen shows software versions pre...

Page 15: ...E unit control 1 Scroll through menus by pressing down on joystick Status Alarms Summary Commission Econ Economizer Enable Make sure this is set to Yes ERV En Figure 11 Econ En Figure 10 2 Scroll through menus by pressing down on joystick Status Alarms Summary Commission PowerEx ERV Enable Make sure this is set to Yes 3 The economizer minimum setting must be set at 50 or greater Status Alarms Summ...

Page 16: ...actor Start Up Mechanic q Inspect the unit for transit damage and report any damage on the carrier s freight bill q Check model number to insure it matches the job requirements q Install field accessories and unit adapter panels as required Follow accessory and unit installation manuals q Verify field wiring including the wiring to any accessories q Check all multi tap transformers to insure they ...

Reviews: