Safety Switch Settings
9.4
Operational Limits
(09/03)
035B09012-100 Rev. 4
9
-
3
60 75 L90 L105 120 150 170 190 210 60 75 90 105 120 150
Low Pressure Switch
bar
0,5
High Pressure Switch
bar
28
Tu¨V High Pressure Switch
bar
25
Anti Freezing Thermostat
°C
4
Evaporator Water Differential
Pressure Switch
kPa
25
4
10,5
Model
YCAA-H (R22)
0,5
YCAA-B (R407C)
0,5
10,5
28
25
4
5
28
YCAA-B and YCAA-H Models
60
75
L90
L105
Min.
Max.
Min.
Max.
Min.
Max.
Min.
Max.
Chilled Liquid outlet
Water outlet
°C
Liquid temperature
Brine outlet
°C
Temperature spread
°K
Flow rate
(1)
l/h 4970 13240 5700 15190 6440 17170 7654 20410
Pressure drop
(1)
kPa 10.0
70.8
10.4
74.2
7.8
55.6
7.7
55.0
Maximum operating pressure
bar
10
Ambient Air entering
Standard control
°C
Air
temperature
ISN control
°C
External static
Standard fans
Pa
0
pressure
High pressure fans
(4)
Pa
80
Recommended system chilled water volume
(2)
l
420
480
510
560
Minimum capacity step
%
50%
Power supply voltage
(5)
V
Min.
Max.
Min.
Max.
Min.
Max.
Min.
Max.
Min.
Max.
Chilled Liquid outlet
Water outlet
°C
+6 to +15
Liquid temperature
Brine outlet
°C
-8 to +15
Temperature spread
°K
3 to 8
Flow rate
(1)
l/h 9482 25280 10800 28810 13115 34910 14405 38413 16018 42713
Pressure drop
(1)
kPa
8.9
63.3
10.5
74.4
14.8 105.6 16.1 114.1 19.9 141.7
Maximum operating pressure
bar
10
Ambient Air entering
Standard control
°C
Air
temperature
ISN control
°C
External static
Standard fans
Pa
0
pressure
High pressure fans
(4)
Pa
80
Recommended system chilled water volume
(2)
l
Minimum capacity step
%
Power supply voltage
(5)
V
(1) Total unit flow rate and pressure drop are given
Caution: Minimum flow rates may only be used with brine solutions after reprogramming unit parameters.
(2) Table shows minimum water / brine volume of system
(3) Maximum ambient air temperature depends on coding:
Standard/Low Noise Units: ISPESL 43°C, SDM 40°C, TUV 40°C, SAQ 38°C, UDT 43°C
High Temperature units: ISPESL 45°C, SDM 43°C
(4) Optional high pressure fans only available on standard YCAA-B units with ISN control
(5) Voltage 400V +/- 10%
400 V, 3 Ø, 50 Hz (nominal)
YCAA-B (R407C)
YCAA-B (R407C)
170
190
120
150
915
800
550
50%
+6 to +15
-8 to +15
3 to 8
400 V, 3 Ø, 50 Hz (nominal)
-5 to + see note (3)
-18 to + see note (3)
210
Not available
-18 to + see note (3)
-5 to + see note (3)
-18 to + see note (3)
575
25%
25%
20%
475
YCAA-B Models
Summary of Contents for YCAA B 120
Page 2: ......
Page 16: ...This Page Left Intentionally Blank 09 03 2 6 035B09012 100 Rev 4 ...
Page 28: ...This Page Left Intentionally Blank 09 03 4 10 035B09012 100 Rev 4 ...
Page 36: ...Page Left Intentionally Blank 09 03 6 6 035B09012 100 Rev 4 ...
Page 40: ...Page Left Intentionally Blank 09 03 7 4 035B09012 100 Rev 4 ...
Page 68: ...Notes 09 03 11 2 035B09012 100 Rev 4 ...
Page 69: ...Notes 09 03 035B09012 100 Rev 4 11 3 ...