(09/03)
035B09012-100 Rev. 4
9
-
13
Fuse/Switch Disconnector Current Ratings
FAN TYPE
SYSTEM
MAXIMUM (gG) FUSE SIZE
PER SYSTEM
SWITCH DISCONNECTOR
FUSE (Ie) RATING
MAX. SECTION mm
2
DIN
DIN
60
STD
1 & 2
63
63
25
75
STD
1 & 2
63
63
25
L90
STD
1 & 2
80
80
35
L105
STD
1 & 2
80
80
35
120
STD
1 & 2
100
100
35
150
STD
1 & 2
120
120
35
170
STD
1 & 2
160
160
70
190
STD
1 & 2
200
200
70
210
STD
1 & 2
200
200
70
STD = Standard Fans
The maximum fuse size given:
1. Means that the conditional short-circuit current of the switch disconnector fuse is 50KA.
2. Ensures a minimum of TYPE 1 co-ordination for contactors to EN 60947-4-1: 1992 with a conditional short-circuit current of 50KA.
3. Ensures that the ultimate allowable short-time conductor temperature under short-circuit conditions is not exceeded
in accordance with EN 60204-1: 1992.