1133383-YIM-A-1014
16
Johnson Controls Unitary Products
Figure 17: Return Downflow Plenum With Panel
Figure 18: Discharge Panel In Place
Side Panels
Units are shipped with side panels to cover the area where an
economizer or motorized damper may be installed. These
panels must be saved and used as tops for the Economizer rain
hoods (See Figure 19)
Figure 19: Save Side Panels For Economizer Hood Tops
Condensate Drain
The side condensate drain is reversible and maybe re-oriented to
the rear of the cabinet to facilitate condensate piping. A
condensate drain connection is available through the base pan
for piping inside the roof curb. Trap the connection per Figure 20.
The trap and drain lines should be protected from freezing.
Plumbing must conform to local codes. Use a sealing compound
on male pipe threads. Install condensate drain line from the 3/4
inch NPT female connection on the unit to an open drain.
Figure 20: Condensate Drain
Compressors
The scroll compressor used in this product is specifically
designed to operate with R-410A Refrigerant and cannot be
interchanged.
The compressor also uses a polyolester (POE oil), Mobil 3MA
POE. This oil is extremely hygroscopic, meaning it absorbs water
readily. POE oil can absorb 15 times as much water as other oils
designed for HCFC and CFC refrigerants. Take all necessary
precautions to avoid exposure of the oil to the atmosphere.
POE (polyolester) compressor lubricants are known to cause
long term damage to some synthetic roofing materials.
This system uses R-410A Refrigerant which operates at
higher pressures than R-22. No other refrigerant may be
used in this system.
Do not leave the system open to the atmosphere. Unit
damage could occur due to moisture being absorbed by
the
POE oil
in the system. This type of oil is highly
susceptible to moisture absorption
3" Minimum