Description for Modbus protocol interface
81
6
Bit5
Fault of Outflow Temperature Sensor of System
Chilled Water
★
6A
7
Bit6
Fault of Backwater Temperature Sensor of
System Cooling Water
★
7A
8
Bit7
Fault of Outflow Temperature Sensor of System
Cooling Water
★
8A
9
Bit8
Exhaust temperature 1-1# sensor fault
9A
10
Bit9
Exhaust temperature 1-2# sensor fault
10A
11
Bit10
Exhaust temperature 2-1# sensor fault
11A
12
Bit11
Exhaust temperature 2-2# sensor fault
12A
13
Bit12
1# suction temperature sensor fault
13A
14
Bit13
2# suction temperature sensor fault
14A
4
Bit3
1# low-pressure sensor
4b
5
Bit4
2# low-pressure sensor
5b
6
Bit5
1# high-pressure sensor
6b
7
Bit6
2# high-pressure sensor
7b
1
Fault Word 3
Bit0
Module’s chilled water flow fault
1d
2
Bit1
Module’s cooling water flow fault
2d
3
Bit2
1# high-voltage switch fault
3d
4
Bit3
1# low-voltage switch fault
4d
5
Bit4
compressor 1-1 overload
5d
6
Bit5
compressor 1-2 overload
6d
9
Bit8
Power supply protection
9d
10
Bit9
2# high-voltage switch fault
10d
11
Bit10
2# low-voltage switch fault
11d
14
Bit13
compressor 2-1 overload
14d
15
Bit14
compressor 2-2 overload
15d
1
Fault Word 5
Bit0
Communication Fault
★
1E
1
Fault Word 6
Bit0
Fault of the communication with the HMI
1F
2
Bit1
Water temperature sensor fault of the controlled
system
2F
3
Bit2
System’s chilled water flow fault
3F
4
Bit3
System’s cooling water flow fault
4F
5
Bit4
External interlock Fault
5F
6
Bit5
Operation time limit protection
6F
7
Bit6
System’s cooling water outlet temperature is too
high
7F
8
Bit7
System’s chilled water outlet temperature is too low
8F
9
Bit8
System’s cooling water outlet temperature is too
low
9F
1
Fault Word 7
Bit0
Module’s chilled water outlet temperature is too low
1p
2
Bit1
Module’s cooling water outlet temperature is too high
2p
3
Bit2
1# Low suction pressure
3p
4
Bit3
1 # Low exhaust pressure
4p
5
Bit4
1# High exhaust pressure
5p
6
Bit5
2# Low suction pressure
6p
7
Bit6
2# Low exhaust pressure
7p
8
Bit7
2# High exhaust pressure
8p
9
Bit8
The exhaust gas temperature is too high 1_1
9p
10
Bit9
The exhaust gas temperature is too high 1_2
10p
11
Bit10
The exhaust gas temperature is too high 2_1
11p