28

YORK INTERNATIONAL

     MON  XX:XX AM  –  PROGRAM  INITIATED  RESET

The chiller is shut down because Micro Board did not

receive a hardware-generated interrupt on schedule.

Typical is an Analog/Digital Converter interrupt. This

message is indicative of a Micro Board hardware fail-

ure or electrical noise on Micro Board. The chiller will

automatically restart. This message indicates that the

watchdog timer-circuit has reset the microprocessor.

This occurs when the time needed to step through pro-

gram is longer than allowable, thus the software pro-

gram is initialized at its beginning.

    SYSTEM  READY  TO  START  –  PRESS  STATUS

The chiller was shut down on a safety shutdown and

will start upon application of a local or remote start sig-

nal. Since the message states that the chiller is “Ready

to Start”, it means that the shutdown no longer exists

and the Control Center has been manually reset. When

the 

STATUS 

key is pressed, a message is displayed

that describes the reason for shutdown. The message

will be displayed for 2 seconds and then return to

SYSTEM  READY  TO  START  –  PRESS  STATUS

Those messages that could be displayed are any of

the previously described safety-shutdown messages

or warning messages. They can be cleared from the

display by entering 

Service 

mode and pressing 

WARN-

ING RESET 

key. Or, the message will be cleared by

initiating a compressor start.

   START  SEQUENCE  INITIATED

Indicates that the Micro Board has received a local or

remote start signal and has initiated the chiller start-up

routine.

This is the compressor pre-lube period. The duration

of this period is controlled by the “Prerun” (JP6) wire

jumper on the Micro Board as follows:

FUNCTION

JUMPER POSITION

  

 50 Sec. Oil Pump Prerun

Installed

 180 Sec. Oil Pump Prerun

   Cut

     SYSTEM  COASTDOWN

Displayed while motor is decelerating after a chiller

shutdown. The oil pump is running during this period.

The duration of this period is 150 seconds.

If unit is configured for a Steam Turbine application

(program jumper JP4 removed), this period is extended

to allow for a longer coastdown time. EPROM version

C.02F(T).11 provides a 6 minute coastdown period.

EPROM version C.02F(T).12 or later provides a 10

minute coastdown period.

     MON  XX:XX AM  –  MTR  PHASE  CURRENT  UNBALANCE

(Solid State Starter applications only)

The chiller is shut down because the compressor-mo-

tor current was unbalanced while the chiller was run-

ning. The current balance is only checked after the

motor has been running for a minimum of 45 seconds

and the motor current is 80% FLA or greater. If the cur-

rent in any phase deviates from the average (

a  +  b+  c 

)

current by greater than 30% for a minimum of 45 con-

secutive seconds, a shutdown is initiated. To restart

the system, press the 

COMPRESSOR 

switch to 

STOP/

RESET 

position and then to the 

START 

position. An

example of the conditions for shutdown is as follows:

IF:

I

A

=  200A

I

B

=  200A

I

c

=  118A

THEN:

I

AV

=  200  +  200  +  118

           3

I

AV

=  173A

I

ACCEPTABLE

  =  173 ± 30%  =  121A or 225A

THEREFORE:

Since I

C

 = 118A which is less than the acceptable

121A, the chiller would shut down if this unbalance

exists for 45 consecutive seconds.

   MON  XX:XX AM  –  LOW  LINE  VOLTAGE

(Solid State Starter applications only)

Chiller is shut down because the voltage in any phase

of line voltage has decreased below the under-voltage-

shutdown threshold for 20 consecutive seconds, or

failed to achieve the minimum required starting line-

voltage. Refer to explanation under “System Setpoints

– SSS Motor Current/Volts”, page 11. The system will

automatically restart when all phases of line voltage

increase to the minimum required starting voltage.

    MON  XX:XX AM  –  HIGH  LINE  VOLTAGE

(Solid State Starter applications only)

Chiller is shut down because the voltage in any phase

of line voltage has increased above the over-voltage

threshold for 20 consecutive seconds. Refer to expla-

nation under “System Setpoints – SSS Motor Current/

Volts”, page 11. The system will automatically restart

when all phases of line voltage decrease to the maxi-

mum allowable line voltage to start the chiller.

    MON  09:30 AM  –  LOW  OIL  TEMPERATURE  –  AUTOSTART

The chiller is running and the oil temperature (as indi-

cated by thermistor RT3) falls below 55°F (12.7°C), the

3

Summary of Contents for 371-01200-010

Page 1: ...ELECTRO MECHANICAL STARTER SOLID STATE STARTER VARIABLE SPEED DRIVE WARNING SYSTEM CONTAINS REFRIGERANT UNDER PRESSURE SERIOUS INJURY COULD RESULT IF PROPER PROCEDURES ARE NOT FOLLOWED WHEN SERVICING...

Page 2: ...Maintenance 43 SECTION 6 Trouble Shooting 45 SECTION 7 Maintenance 50 SECTION 8 Preventive Maintenance 59 Page REFERENCE INSTRUCTIONS DESCRIPTION FORM NO Solid State Starter Operation Maintenance 160...

Page 3: ...B DC DD EB EC ED FB FC FD GB GC GD HB HC HD JB JC JD TB TC TD VB VC VD COOLER CODE CB CC CD CE DB DC DD DE FB FC FD GB GC GD GF GH HB HC HF HH JF JG JH TF TG TH VF VH WF WH MODEL MOTOR CODE 60 HZ 50 H...

Page 4: ...s applied with an electro mechanical starter YORK Solid State Starter optional or Variable Speed Drive optional In operation a liquid water or brine to be chilled flows through the cooler where boilin...

Page 5: ...r components of a chiller are selected for full load capacities therefore capacity must be controlled to maintain a constant chilled liquid temperature leav ing the cooler Prerotation vanes PRV locate...

Page 6: ...Operation of this equipment in a residential area is likely to cause interference in which case the user at his own expense will be required to take whatever action may be required to correct the inte...

Page 7: ...EVAPORATOR AND CONDENSER DISCHARGE TEMPERATURE OIL TEMPERATURE HIGH LOW OIL PRESSURE TRANSDUCER PRESSURE SOLID STATE STARTER MOTOR CURRENT VOLTS When Supplied CONDENSER REFRIGERANT LEVEL The system s...

Page 8: ...VICE 1 Service allows manual PRV control with visual display readout of PRV operation 2 Local allows manual compressor start from the COMPRESSOR switch on the Control Center front 3 Program allows ope...

Page 9: ...the differential pressure The offset pressure calculation will not be performed if either transducer is out of range The offset value will be taken as 0 PSI in this instance To Display OPTIONS This k...

Page 10: ...mmed by the system operator The Setpoints keys are located on the Control Center keypad see Fig 3 To program see Programming System Setpoints page 14 The following is a description of these setpoints...

Page 11: ...ming week are holidays On those designated days the chiller will automatically start and stop via the holi day start and stop times programmed in the DAILY SCHEDULE setpoint It will do this one time o...

Page 12: ...erator programmed The value displayed in the REMOTE mode is that which has been pro grammed by the Energy Management System via the remote current limit setpoint input If chiller is equipped with a YO...

Page 13: ...age REMOTE RESET TEMP RANGE 10 F or REMOTE RESET TEMP RANGE 20 F To Display DATA LOGGER setpoints Refer to YORK Form 160 49 N2 for operation of this key To Display UNDERVOLTAGE setpoints Solid State S...

Page 14: ...THORIZED is displayed NOTE Unless terminated by pressing the AC CESS CODE key again the operator will have access to the PROGRAM key for 10 minutes When 10 minutes have elapsed access to PROGRAM key w...

Page 15: ...MODE SELECT SETPOINT message is displayed To Enter CURRENT LIMIT Setpoint Electro Mechanical Starter refer to Fig 7 1 Press and release CURRENT LIMIT setpoint key The following program prompt message...

Page 16: ...y PROGRAM MODE SELECT SETPOINT message is displayed To Enter CLOCK Setpoint Refer to Fig 9 1 Assure Micro Board Program jumper J57 is in CLKON position 2 Press and release CLOCK setpoint key The follo...

Page 17: ...desired hours and minutes stop time e If necessary press the AM PM key to change AM to PM or vice versa 3 Press and release ADVANCE DAY SCROLL key The following prompt message is displayed MON START X...

Page 18: ...R key PROGRAM MODE SELECT SETPOINT message is displayed To cancel all of the designated holidays perform Step 1 press CANCEL key and then press ENTER key PROGRAM MODE SELECT SETPOINT message is displa...

Page 19: ...13 KEYPAD SERVICE KEYS LOCATION SERVICE KEYS LD00963 HOLD Press and release this key to hold the pre rotation vanes in their present position If the chiller is running SYSTEM RUN VANES HOLDING is dis...

Page 20: ...o reset any safety shutdown mes sage press WARNING RESET key in SERVICE mode with the COMPRESSOR switch in the STOP RESET position MANUAL OIL PUMP This key is operational in any mode Press and release...

Page 21: ...celled or NO 2 ACTUAL LEVEL XXX LEVEL SETP XXX Displays the actual refrigerant level in the condenser and the refrigerant level setpoint programmed by the service technician This message replaces the...

Page 22: ...MODE IN EFFECT is displayed If the Control Center is in SERVICE mode SERVICE OPERATING MODE IN EFFECT is displayed To change operating mode proceed as follows 1 Press ACCESS CODE key 2 ENTER VALID ACC...

Page 23: ...lue the vanes will be driven closed not fully closed only far enough to allow the current to decrease to a value less than 104 of the operator programmed XXX FLA cur rent limit For example With the op...

Page 24: ...rises to 28 PSIG 193 kPa R 134a the vanes will be per mitted to open Low pressure limit feature is not used when program jumper JP3 is cut Brine application SYSTEM RUN HIGH PRESSURE LIMIT IN EFFECT Di...

Page 25: ...wn The flow switch is checked 25 seconds into Start Sequence Initiated and continuously thereafter MON XX XX AM SYSTEM CYCLING AUTOSTART A remote command computer relay contact or manual switch connec...

Page 26: ...ut out settings will vary with the brine applica tion To restart the chiller wait until the safety contacts close press the COMPRESSOR switch to the STOP RESET position and then to the START position...

Page 27: ...arge tem perature has increased to 220 F 104 C The system will be allowed to restart when the temperature has decreased to 219 F 103 C Temperature is sensed by a thermistor RT2 To restart the chiller...

Page 28: ...r JP4 removed this period is extended to allow for a longer coastdown time EPROM version C 02F T 11 provides a 6 minute coastdown period EPROM version C 02F T 12 or later provides a 10 minute coastdow...

Page 29: ...T position and then to the START position MON XX XX AM PROX SENSOR SAFETY SHUTDOWN The chiller is shut down because the Proximity Tem perature Sensor has detected that the distance be tween the compre...

Page 30: ...orientation orientation notch must be UP Refer to Fig 14 MON XX XX AM OPEN DRAIN TEMP THERMOCOUPLE The chiller is shut down because the Proximity Tem perature Sensor thermocouple or high speed drain...

Page 31: ...not start if the oil is less than 71 F 22 C If not possible the compressor oil should be drained and new oil must be charged into the oil sump See Charging Unit With Oil page 44 2 Oil Pump To check pr...

Page 32: ...for a 50 sec ond pre run to establish oil flow and adequate lu brication to all bearings gears and rotating sur faces within the compressor The high and low oil pressure transducers OP and the oil te...

Page 33: ...he Control Center as MON 10 30 AM LOW WATER TEMPERATURE AUTOSTART This occurs when the leaving water temperature falls to 4 F 2 2 C below setpoint or 36 F 2 2 C whichever is higher The LWT is part of...

Page 34: ...erating condi tions temperatures and pressures recorded at regu lar intervals throughout each 24 hour operating period should be kept An optional status printer is available for this purpose or Fig 16...

Page 35: ...ondenser saturation temperature based upon condenser pressure sensed by the condenser transducer Press the DISPLAY DATA key This key may be depressed repeatedly after depressing the DISPLAY HOLD key t...

Page 36: ...Low Evaporator Pressure Low Oil Pressure High Oil Flow High Condenser Pressure Evaporator Transducer or Probe Error High Discharge Temp High Oil Temp Oil Pressure Transducer Starter Malfunction Detect...

Page 37: ...ng temperatures are encountered while the system is idle carefully drain the cooling water from the cooling tower condenser condenser pump and the chilled water system chilled water pump and coils Ope...

Page 38: ...COOLER OIL RESERVOIR PUMP 28778A FRONT VIEW SIGHT GLASS REFRIGERANT CHARGING VALVE 28815A COOLER MOTOR ADAPTER MOTOR SUPPORT COVER MICROCOMPUTER CONTROL CENTER SUCTION DUAL RELIEF VALVES VARIABLE SPE...

Page 39: ...pump oil filter oil cooler and all interconnecting oil piping and passages There are main points within the motor com pressor which must be supplied with forced lubrication as follows 1 COMPRESSOR DRI...

Page 40: ...40 YORK INTERNATIONAL FIG 18 SCHEMATIC DRAWING YK COMPRESSOR LUBRICATION SYSTEM LD03278...

Page 41: ...HANGERS Evaporator and condenser shells are fabricated from rolled carbon steel plates with fusion welded seams Heat exchanger tubes are internally enhanced type The evaporator is a shell and tube flo...

Page 42: ...ared and normal control is resumed OPTIONAL SERVICE ISOLATION VALVES If your chiller is equipped with optional service isola tion valves on the discharge and liquid line these valves must remain open...

Page 43: ...drator to the compressor sump CHANGING THE DEHYDRATOR To change the dehydrator use the following procedure 1 Shut the stop valves on the condenser gas line oil return line to rotor support and inlet...

Page 44: ...valve A located on the remote oil reservoir cover plate See Fig 20 Do not tighten the connection at the charging valve until after the air is forced out by pumping a few strokes of the oil pump This f...

Page 45: ...remote com Automatic Restart Contact connected to Cycling mand computer upon remote the Remote Local relay contact or command cycling input of the manual switch Digital input board MON 10 00 AM Multi...

Page 46: ...n RS1 LCWT minus satu tor RS1 ration temperature is less than 2 5 F or greater than 25 F Checked every 10 minutes following a 10 min bypass at start up MON 10 00 AM Motor Con CM2 or Solid Reset the de...

Page 47: ...r Check motor starter Malfunction 15 for 10 swc STOP RESET operation Motor current Detected with Control Cen switch and then value greater than 15 ter not calling for FLA motor to run MON 10 00 AM Pro...

Page 48: ...n normal with normal discharge temperature Temperature of chilled water too low with Insufficient load for Check prerotation vane motor opera with low motor amperes system capacity tion and setting of...

Page 49: ...ALLY DECREASES Noted by Observation of Daily Log Sheets Oil pressure noted when pressing OIL Oil filter is dirty Change oil filter PRESSURE display key drops to 70 of oil pressure when compressor was...

Page 50: ...or can be used to detect any leaks too small to be found by the soap test To test with R 22 proceed as follows 1 With no pressure in the system charge R 22 gas into the system through the charging val...

Page 51: ...t the vacuum pump leaving the vacuum indicator in place 6 Hold the vacuum obtained in Step 3 in the system for 8 hours the slightest rise in pressure indicates a leak or the presence of moisture or bo...

Page 52: ...to be tight prior to evacuation then the saturation tem perature recordings should follow a curve similar to the typical saturation curve shown as Fig 22 The temperature of the water in the test tube...

Page 53: ...urnished in cylinders contain ing either 30 50 125 or 1750 lbs 207 345 862 or 12 066 kg of refrigerant TABLE 4 REFRIGERANT CHARGE CHECKING THE REFRIGERANT CHARGE DURING UNIT SHUTDOWN The refrigerant c...

Page 54: ...enser or evaporator compressor while making any necessary repairs While the main disconnect switch and compressor motor starter are open meg the motor as follows 1 Using a megohm meter megger meg betw...

Page 55: ...FORM 160 52 O1 55 YORK INTERNATIONAL FIG 24 MOTOR STATOR TEMPERATURE AND INSULATION RESISTANCES LD00476 TEMPERATURE F MEGOHMS Minimum Insulation Resistance vs Temperature per IEEE Std 43 Open Motors...

Page 56: ...time accompanied by a steady rise in con densing temperature and noisy operation These symp toms may also be due to foul gas buildup Purging will remove the foul gas revealing the effect of fouling TU...

Page 57: ...ube heads and the ends of all tubes with water NOTE Do not use carbon tetrachloride for this pur pose since its fumes give the same flame discoloration that the refrigerant does 3 With nitrogen or dry...

Page 58: ...or Low Oil Pressure OP change the oil filter element Examine the oil filter element for the pres ence of aluminum particles Aluminum gas seal rings can contact the impeller and account for some alumi...

Page 59: ...he unit should be leak tested quarterly Any leaks found must be repaired immediately COOLER AND CONDENSER The major portion of maintenance on the condenser and cooler will deal with the maintaining th...

Page 60: ...controls operation and safety not be changed If the set tings are changed without YORK s approval the warranty will be jeopardized 3 A 5 11 year life battery is part of the RTC Real Time Clock To repl...