INTRODUCTION
The YORK MicroComputer Control Center is a micro-
processor based control system for R134a centrifugal
chillers. It controls the leaving chilled water tempera-
ture via pre-rotation vane control and has the ability to
limit motor current via control of the pre-rotation vanes.
Further, it is compatible with YORK Solid State Starter
(optional), Variable Speed Drive (optional), and elec-
tromechanical starter applications.
The Control Center can be equipped with an optional
Chinese language display, either as a field retrofit or
factory supplied option on new units. This display
mounts on the control center door, directly above the
standard display. Both the standard and Chinese dis-
play will be present, providing display messages simul-
taneously in both English and Chinese language. (The
Control Center must be configured for Chinese display
by a qualified service technician. Instructions are con-
tained in YORK service manual, Form 160.49-M2.)
A keypad mounted on the front of the Control Center
(see Fig. 3) allows the operator to display system oper-
ating parameters on a 40 character alphanumeric dis-
play that is part of the keypad. These readings are dis-
played via Display keypad as follows: (In the English
mode; temperatures in °F, pressures in PSIG) (in the
metric mode, temperatures in °C, Pressures in KPa).
CHILLED LIQUID TEMPERATURES LEAVING
AND RETURN
REFRIGERANT PRESSURES EVAPORATOR
AND CONDENSER
DIFFERENTIAL OIL PRESSURE PUMP SPEED
CONDENSER LIQUID TEMPERATURES OP-
TIONAL FIELD INSTALLED LEAVING AND RE-
TURN
* HIGH SPEED THRUST POSITION HIGH SPEED
THRUST OIL TEMPERATURE
OPTIONS
PRINT *
HISTORY PRINT *
MOTOR CURRENT IN % OF FULL LOAD AMPS
SATURATION TEMPERATURES EVAPORATOR
AND CONDENSER
DISCHARGE TEMPERATURE
OIL TEMPERATURE
HIGH & LOW OIL PRESSURE TRANSDUCER
PRESSURE
SOLID STATE STARTER MOTOR CURRENT /
VOLTS (When Supplied)
CONDENSER REFRIGERANT LEVEL
The system setpoints (see Fig. 3) are operator entered
on the front control center
Setpoints
keypad. These
setpoints can also be displayed on the 40 character
alphanumeric display. The system setpoints are:
CHILLED LIQUID TEMPERATURE (LCWT)
% CURRENT LIMIT
PULLDOWN DEMAND LIMIT
CLOCK (TIME-OF-DAY)
DAILY SCHEDULE (7 DAY TIME-CLOCK PRO-
GRAMMING)
HOLIDAY
REMOTE RESET TEMPERATURE RANGE
DATA LOGGER
CONDENSER REFRIGERANT LEVEL
The cause of all system shutdowns (safety or cycling)
is preserved (until the system is reset or restarts) in the
MicroComputers memory for subsequent viewing on
the keypad display. The operator is continually advised
of system operating conditions by various background
and warning messages. The keypad contains special
service keys for use by the service technician when
performing system troubleshooting.
The MicroComputer Control Center is designed to be
compatible with most Energy Management Systems
(EMS) in use today. The standard design allows for the
following EMS interface:
1. Remote Start
2. Remote Stop
3. Remote LCWT Setpoint (Pulse Width Modulated
signal)
4. Remote Current Limit Setpoint (Pulse Width Modu-
lated signal)
5. A Remote Mode Ready to Start Status Contacts
6. Safety Shutdown Status Contacts
7. Cycling Shutdown Status Contacts
As an enhancement to the standard EMS features, an
optional card file with plug-in printed circuit boards is
available. These optional cards will accept a remote
LCWT 0 to 10°F (0 to 5.5°C) or 0 to 20°F (0 to 11.1°C)
setpoint offset and/or remote current limit setpoint in-
terface from three user input choices.
1. 4-20mA
2. 0-10VDC
3. Contact Closures
* These keys provide a print-out when the customer connects a
compatible printer to the Micro Board RS-232 serial port.