661693-UIM-E-1212

Johnson Controls Unitary Products

11

TABLE 8: 

ELECTRICAL DATA FOR SINGLE SOURCE POWER SUPPLY - 208/230-3-60

Air Handler Models

Heater 

Models

Heater

Amps

@ 240V

Field Wiring

Min. Circuit Ampacity

MOP

1

Min. Wire Size (AWG)

2

208V

230V

208V

230V

208V

230V

AHR24B

6HK06501025

23.1

26.8

30.7

30

35

10

10

6HK06501525

34.6

39.2

45.0

40

45

8

8

AHR30B
AHR42C

6HK06501025

23.1

28.8

32.7

30

35

10

8

6HK06501525

34.6

41.2

47.0

45

50

8

8

AHR36B
AHR48D

6HK06501025

23.1

28.8

32.7

30

35

10

8

6HK06501525

34.6

41.2

47.0

45

50

8

8

6HK06501825

41.6

48.8

55.8

50

60

8

6

6HK16502025

3

46.2

53.8

61.5

60

70

6

6

AHR60D

6HK06501025

23.1

28.8

32.7

30

35

10

8

6HK06501525

34.6

41.2

47.0

45

50

8

8

6HK06501825

41.6

48.8

55.8

50

60

8

6

6HK16502025

3

46.2

53.8

61.5

60

70

6

6

6HK16502525

3

57.7

66.3

75.9

70

80

4

4

1. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse.
2. Stated sizes are for 75°C, copper wire only.  If wire other than non-plated, 75°C ambient, copper wire is used, consult applicable tables of the NEC and local codes.
3. The 20kW and 25kW heater models (6HK16502025 and 6HK16502525) come with circuit breakers standard. Single source power MCA and MOP requirements are 

given here only for reference if used with field installed single point power modification.

TABLE 9: 

ELECTRICAL DATA FOR MULTI-SOURCE POWER SUPPLY: 208/230-3-60

Air Handler Models

Heater

Models

Total Heater

Amps

@ 240V

Min. Circuit Ampacity

MOP

1

 Min. Wire Size (AWG)

2

208V

230V

208V

230V

208V

230V

Circuit

Circuit

Circuit

1st

3

2nd

1st

3

2nd

1st

3

2nd

1st

3

2nd

1st

3

2nd

1st

3

2nd

AHR36B
AHR48D

6HK16502025

46.2

28.8

25.0

32.6

28.9

30

25

35

30

10

10

8

10

AHR60D

6HK16502025

46.2

28.8

25.0

32.6

28.9

30

25

35

30

10

10

8

10

6HK16502525

57.7

35.0

31.3

39.8

36.1

35

35

40

40

8

8

8

8

1. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse.
2. Stated sizes are for 75°C, copper wire only.  If wire other than non-plated, 75°C ambient, copper wire is used, consult applicable tables of the NEC and local codes.
3. 1st Circuit includes the blower motor amps.

TABLE 10: 

AIR FLOW DATA (CFM)

1

Models

Blower 

Motor Speed

External Static Pressure (in. wc.)

0.10

0.20

0.30

0.40

0.50

0.60

0.70

208 Volt

AHR18B3XH21

High

1024

1000

970

930

860

810

NA

Medium

756

731

700

670

620

550

NA

Low

557

531

495

445

375

315

195

AHR24B3XH21

High

995

970

935

900

925

795

645

Medium

820

810

780

745

695

545

485

Low

715

695

640

405

370

375

220

AHR30B3XH21

High

1380

1315

1245

1160

1075

990

885

Medium

1060

1040

1005

955

890

860

820

Low

1035

980

910

825

770

685

485

AHR36B3XH21

High

1410

1335

1270

1190

1110

990

820

Medium

1215

1170

1115

1050

935

850

740

Low

950

935

895

855

NA

NA

NA

AHR42C3XH21

High

1800

1725

1645

1545

1360

1200

1050

Medium

1535

1480

1415

1280

1155

1010

870

Low

1225

1195

1095

1025

925

825

680

Continuation on Page 12.

Summary of Contents for 41HP AHR18B

Page 1: ......

Page 2: ...ervice personnel can perform basic maintenance functions such as cleaning and replacing the air filters When work ing on heating cooling equipment observe precautions in the man uals and on the labels...

Page 3: ...secondary drain It should be piped to a loca tion that will give the occupant a visual warning that the primary drain is clogged If the secondary drain is not used it must be capped 5 When an evaporat...

Page 4: ...ort bracket See Figure 5 This positions the deflector below the feeder tubes to channel the condensate to the drain pan DUCT FLANGES Four flanges are provided to attach ductwork to the furnace These f...

Page 5: ...is recommended a block off plate approximately 8 in height and running the full width of the ple num be attached to the supply opening Please refer to Figure 8 as a visual aid The use of this block o...

Page 6: ...ed and piped to a location that will give the occupant a visual warning that the primary drain is clogged If the secondary drain is not used it must be capped The drain pan connections are designed to...

Page 7: ...um wiring to air handlers is not approved If aluminum conductors are present all applicable local and national codes must be followed when converting from aluminum to copper con ductors prior to conne...

Page 8: ...require ments Read and heed all unit caution labels It is possible to vary the amount of electric heat turned on during the defrost cycle of a heat pump Standard wiring will only bring on the first s...

Page 9: ...4 11 5 32 0 39 2 3 1 3 8 9 4 11 5 6HK 1 2 6501506 14 4 10 8 13 2 36 9 45 1 3 6 4 4 10 8 13 2 6HK 1 2 6501806 17 3 13 0 15 9 44 3 54 2 6 5 7 9 13 0 15 9 6HK 1 2 6502006 19 2 14 4 17 6 49 2 60 2 7 2 8...

Page 10: ...and local codes TABLE 6 ELECTRICAL DATA FOR SINGLE SOURCE POWER SUPPLY 208 230 1 60 Continued Air Handler Models Heater Models1 2 Heater Amps 240V Field Wiring Min Circuit Ampacity MOP 3 Min Wire Siz...

Page 11: ...L DATA FOR MULTI SOURCE POWER SUPPLY 208 230 3 60 Air Handler Models Heater Models Total Heater Amps 240V Min Circuit Ampacity MOP1 Min Wire Size AWG 2 208V 230V 208V 230V 208V 230V Circuit Circuit Ci...

Page 12: ...t AHR18B3XH21 High 1145 1100 1055 1005 930 845 725 Medium 755 750 725 665 605 485 435 Low 680 655 625 585 540 395 300 AHR24B3XH21 High 1305 1285 1225 1175 920 915 835 Medium 930 920 890 845 705 760 50...

Page 13: ...661693 UIM E 1212 Johnson Controls Unitary Products 13 SECTION X WIRING DIAGRAM FIGURE 15 Wiring Diagram PSC Single Phase Heat Kits...

Page 14: ...NT CODES GND EQUIPMENT GROUND FL FUSIBLE LINK HE HEATING ELEMENT LS LIMIT SWITCH REL RELAY FIELD POWER WIRING 208 230V FACTORY WIRING 208 230V FACTORY WIRING LOW VOLTAGE L1 L2 L3 L1 L2 L3 GND GND GND...

Page 15: ...661693 UIM E 1212 Johnson Controls Unitary Products 15 SECTION XI TYPICAL THERMOSTAT CONNECTIONS FIGURE 17 Typical Wiring Diagram PSC...

Page 16: ...dry bulb temperature Return air dry bulb temperature Temperature drop 1 2 3 4 5 Low Medium Low Medium Medium High High A B C D Outside air dry bulb temperature Return air wet bulb temperature Supply a...

Page 17: ...he thermostat noting and correcting any problems Operate the unit through mechanical heating cycles from the thermostat noting and correcting any problems Operate the unit through emergency heating cy...

Page 18: ...o change without notice Published in U S A 661693 UIM E 1212 Copyright 2012 by Johnson Controls Inc All rights reserved Supersedes 661693 UIM D 1012 York International Corp 5005 York Drive Norman OK 7...