background image

NOTE: Front door of burner box must be secured when check-

ing gas input.

1.  Turn off all other gas appliances connected to the gas

meter.

2.  With the furnace turned on, measure the time needed for

one revolution of the hand on the smallest dial on the
meter. A typical domestic gas meter usually has a 1/2 or 1
cubic foot test dial.

3.  Using the number of seconds for each revolution and the

size of the test dial increment, find the cubic feet of gas
consumed per hour from Table 9.

To find the BTUH input use the following formula:

Cu. Ft. Gas x meter correction factor x Gas BTU Content  =
BTU Per Hour Input

The gas meter is affected by both the temperature and also the
barometric pressure. The meter should be correct at 60

°

 F, and

30.0" barometric pressure. At all other conditions it will be
inaccurate, although the correction factor is easily calculated.
Higher temperatures (over 60

°

 F) will speed up the meter and

make it read high.

Temperatures under 60

°

 F will slow it and make it read low. The

barometric pressure above 30.0" will slow the meter and below
30.0" speed up the meter. At some conditions the meter may
be off significantly. An error of 

±

 5% is not uncommon. The gas

meter correction factor is calculated as follows:

(Barometric Pressure) x 520     

= Meter Correction Factor

(Temperature 

°

 F + 460) x 30

Example 1: 28.9" Barometric Pressure, 80

°

 F

(28.9) 

520    = 15028

   

= .928 Correction Factor

(80 + 460) x 30    =  16200

Contact your gas supplier for actual BTU content of the gas.

EXAMPLE - CHECKING GAS INPUT

It is found by measurement that it takes 26 seconds for the hand
on the 1 cubic foot dial to make a revolution with only a 120,000
Btuh furnace running. Using this information, locate 26 seconds
in the first column of Table 9.  Read across to the column
headed "1 cubic foot" where you will see that 138 cubic feet of
gas per hour are consumed by the furnace at that rate.

With the barometer at 28.9" and a 70

°

 F temperature, the

correction factor will be .945. If the local gas heating value is
935 BTU per cubic foot the calculations will be as follows:

138 cu. ft/hr x .945 correction factor x 935 BTU/cu. ft. =
121,933 BTU/Hr.

The calculated firing rate of 121,933 BTU per hour is within the

±

 2% tolerance of our nominal 120,000 furnace.

If the actual input is not within 2% of the furnace rating, with
allowance being made for the permissible range of the regula-
tor setting (0.3 inches W.C.), replace the orifice spuds with spud
of the proper size.

CAUTION: Be sure to relight any gas appliances that
were turned off at the start of this input check.

ADJUSTMENT OF MANIFOLD GAS PRES-

SURE

FIGURE 32 - GAS VALVES
       TOP - WHITE-RODGERS 36E24
       BOTTOM - HONEYWELL VR8205

Wiring 

Terminals

Outlet

Main 

Regulator 

Adjust

Wrench

Boss

ON - OFF Switch

Inlet

Outlet

Pressure

Tap

TABLE 9 - GAS RATE (CUBIC FEET PER HOUR)

Seconds for

one Revol.

Size of Test Dial

1/2 cu. ft.

1 cu. ft.

10

180

360

12

150

300

14

129

257

16

113

225

18

100

200

20

90

180

22

82

164

24

75

150

26

69

138

28

64

129

30

60

120

32

56

113

34

53

106

36

50

100

38

47

95

40

45

90

42

43

86

44

41

82

46

39

78

48

37

75

50

36

72

52

35

69

54

34

67

56

32

64

58

31

62

60

30

60

650.75-N4U

Unitary Products Group

21

Summary of Contents for 65075-N4U

Page 1: ...r other flammable vapors and liquids in the vicinity of this or any other appliance WARNING IMPROPER INSTALLATION ADJUSTMENT AL TERATION SERVICE OR MAINTENANCE CAN CAUSE INJURY OR PROPERTY DAMAGE RE F...

Page 2: ...ce since it requires separate properly sized air intake and vent lines The furnace shall not be connected to any type of B BW or L vent or vent connector and not connected to any portion of a factory...

Page 3: ...e access is required for passage to the front when servicing or for inspection or replacement of flue vent connections NOTE In all cases accessibility clearances shall take prece dence over clearances...

Page 4: ...95 2000 C 21 19 3 4 16 5 8 2 2 120 112 2000 D 24 1 2 23 1 4 20 1 8 3 2 3 140 130 2000 D 24 1 2 23 1 4 20 1 8 3 2 3 Vent pipe must be increased to 3 on this model INPUT MBH OUTPUT MBH NOM CFM CAB WIDTH...

Page 5: ...75 1200 17 1 2 91 0 35 65 1370 165 11 8 1 2 9 0 20 14 80 75 1600 21 91 0 30 60 1563 160 11 8 3 4 12 0 20 14 100 95 2000 21 91 0 40 70 1582 170 11 10 1 12 0 20 14 120 112 2000 24 1 2 91 0 40 70 1885 1...

Page 6: ...ambient temperature may drop below 32 F a UL listed self regulated heat tape must be installed It is recommended that self regulating heat tape rated at 3 watts per foot be used This must be installe...

Page 7: ...r sides of the cabinet wall NOTE Air velocity through throw away type filters may not exceed 300 feet per minute All velocities over this require the use of high velocity filters Side Return External...

Page 8: ...n sions Install the plenum following instructions under Ductwork in this instruction SUPPLY AIR DUCTS Installations on combustible material or floors must usea combus tible floor base shown in Figure...

Page 9: ...ezing are possible refer to Page 6 Below Freezing Locations GAS PIPING The gas supply must be installed in accordance with the current National Fuel Gas Code ANSI Z223 1 in the U S or CAN CGA B149 1 o...

Page 10: ...switch should be close to the unit for convenience in servicing With the disconnect switch in the OFF position check all wiring against the unit wiring label Also see the wiring diagram in this instru...

Page 11: ...nnection top right of unit back to the outdoors See Figure 13 or 14 The intake vent should be located either through the wall horizontal or side vent or through the roof vertical vent Care should be t...

Page 12: ...roofor sidewall NOTE Accessory concentric intake vent terminations models 1CT0302 and 1CT0303 are available and approved for use with these furnaces Refer to Form 650 75 N2 4V for installation details...

Page 13: ...ning at the furnace 2 Deburr the piping inside and outside 3 Chamfer the outer edges of the piping 4 Dry fit the entire vent combustion air piping assembly 5 Disassemble the piping and apply cement pr...

Page 14: ...the furnace This may be from within the space in a non confined location or it may be brought into the furnace area from outdoors It is not directly ducted into the furnace A single properly sized pi...

Page 15: ...m dimension of rectangular ducts shall be three inches 2 One permanent opening commencing within 12 inches of the top of the enclosure shall be permitted where the equipment has clearances of at least...

Page 16: ...t connections NOTE An offset using two 45 degree elbows may be required for plenum clearance when the vent is increased to 3 1 Long radius elbows are required for all units 2 Elbows are assumed to be...

Page 17: ...on may require seal ing or shielding of building surfaces with a corrosive resistant material due to vent system corrosive combus tion products PIPING ASSEMBLY The final assembly procedure for the ven...

Page 18: ...e allowable locations shown in Figure 24 and Section 7 8 in the National Fuel Gas Code ANSI Z223 1 current edition Follow all local agency and utility requirements if more restrictive than those shown...

Page 19: ...w the instructions with the coil for trapping the drain SAFETY CONTROLS Control Circuit Fuse A 3 amp fuse is provided to protect the 24 volt transformer from overload caused by control circuit wiring...

Page 20: ...blower motor failure START UP AND ADJUSTMENTS The initial start up of the furnace requires the following addi tional procedures 1 When the gas supply is initially connected to the furnace the gas pip...

Page 21: ...MPLE CHECKING GAS INPUT It is found by measurement that it takes 26 seconds for the hand on the 1 cubic foot dial to make a revolution with only a 120 000 Btuh furnace running Using this information l...

Page 22: ...and electrical supplies ON Start furnace and observe manifold pressure on manometer 5 Adjust manifold pressure by adjusting gas valve regulator screw for natural gas set at 3 5 W C If gas valve regula...

Page 23: ...or lead Place all unused motor leads on Park terminals Two Park terminals are provided CAUTION Do not energize more than one motor speed at a time or damage to the motor will result ADJUSTMENT OF FAN...

Page 24: ...the thermostat circuit opens the ignition control is deener gized Withtheignitioncontroldeenergized thegasflowstopsand the burner flames are extinguished The venter continues to operate for 15 seconds...

Page 25: ...me Lift filter slightly to dislodge and remove for service 3 Remove the filter and follow the cleaning instructions above DO NOT remove the filter stiffener rods if provided When reinstalling the filt...

Page 26: ...blower and the condensate pan The turbulators can then be gently re moved from the secondary heat exchanger 3 With a stiff wire brush brush out loose scale or soot 4 Vacuum the secondary heat exchang...

Page 27: ...e is lost 5 times during the heating cycle This could be caused by low gas pressure or faulty gas valve 9 FLASH TI61F 2 CONTROL ONLY Indicates reversed line voltage polarity Check incoming power wirin...

Page 28: ...985 835 757 665 450 MED 900 887 851 810 752 693 609 403 LOW 581 577 569 542 468 60 55 1000 B HI 1220 1200 1190 1152 1115 1065 1012 950 872 771 MED 920 915 900 880 842 803 740 650 LOW 725 729 715 700...

Page 29: ...UNIT WIRING DIAGRAM UPFLOW 650 75 N4U Unitary Products Group 29...

Page 30: ...UNIT WIRING DIAGRAM DOWNFLOW HORIZONTAL...

Page 31: ...NOTES 650 75 N4U Unitary Products Group 31...

Page 32: ...ect to change without notice Printed in U S A Copyright by Unitary Products Group 1998 All rights reserved 650 75 N4U Supercedes 650 75 N4U 498 5005 York Drive Norman OK 73069 Unitary Products Group 6...

Reviews: