background image

Burner Removal/Cleaning

The main burners should be checked periodically for dirt
accumulation.

If cleaning is required, follow this procedure:

1.  Turn off the electrical power to the unit.

2.  Turn off the gas supply at the external manual shutoff valve

and loosen the ground union joint.

3.  Remove the upper access panel and remove the burner

box cover.

4.  Remove the screws that hold the burner box assembly to

the vest panel and remove the assembly.

5.  Remove burners from the burner assembly.

6.  Burners may be cleaned by rinsing in hot water.

7.  Reassemble the burners in the reverse order.

Cleaning the Heat Exchanger

1.  Turn off the main manual gas valve external to the furnace.

2.  Turn off electrical power to the furnace.

3.  Remove the upper access panel and remove the burner

box cover.

4.  Disconnect wires from flame sensor, rollout switch and HSI

igniter. Remove igniter carefully, as it is easily broken.

CAUTION: Label all wires prior to disconnection when
servicing controls. Wiring errors can cause improper
and dangerous operation. Verify proper operation af-
ter servicing.

5.  Remove the screws that hold the burner box assembly to

the vestibule panel and remove the assembly. The upper
portion of the heat exchanger will now be exposed.

6.  Remove the upper cover plate at the top of the furnace.

Remove the internal baffle.

7.  The upper portion of the heat exchanger is now exposed.

8.  With a long flexible wire brush, clean inside each tube at

both the top and bottom. The brush must pass around the
rear heat exchanger tubes. Vacuum loose scale and dirt
from each tube.

9.  Clean - vacuum all burners.

10.  Replace all components in reverse order. Reconnect all

wiring.

11.  Restore electrical power and gas supply to the furnace.

12.  Check furnace operation.

Cleaning the Secondary Heat Exchanger

1.  Follow steps 1 thru 10 under "Cleaning the Primary Heat

Exchanger."

2.  Remove the vent piping from the venter housing. Discon-

nect the drain lines from the venter and from the conden-
sate drain pan. Remove the venter blower and the
condensate pan. The turbulators can then be gently re-
moved from the secondary heat exchanger.

3.  With a stiff wire brush, brush out loose scale or soot.

4.  Vacuum the secondary heat exchanger.

5.  Finish the cleaning procedure by following steps 10 thru

12 under "Cleaning the Primary Heat Exchanger."

VENT/AIR INTAKE

Should it be necessary to service the vent/air intake system,
the manufacturer recommends this service be conducted by a
qualified service agency.

The operation of this appliance requires the reassembly and
resealing of the vent/air intake system as specified onPage  11.

TROUBLESHOOTING

The following visual checks should be made before trou-
bleshooting:

1.  Check to see that the power to the furnace and the ignition

control module is ON.

2.  The manual shutoff valves in the gas line to the furnace

must be open.

3.  Make sure all wiring connections are secure.

4   Review the sequence of operation.

Start the system by setting the thermostat above the room tem-
perature. Observe the system’s response. Then use the trou-
bleshooting section in this manual to check the system’s operation.

FURNACE CONTROL DIAGNOSTICS

The furnace has built-in, self diagnostic capability. If a system
problem occurs, a fault code is shown by a blinking LED. It is
located behind a clear view port in the blower compartment
door. DO NOT remove the furnace blower compartment panel
OR turn off furnace power as either action will clear the control’s
memory of the fault.

The control continuously monitors its own operation and the
operation of the system. If a failure occurs, the LED will indicate
the failure code. If the failure is internal to the  control, the light
will stay on continuously. In this case, the entire control should
be replaced as the control is not field repairable.

If the sensed failure is in the system (external to the control),
the LED will flash in the following flash-pause sequences to
indicate failure status.

Flash sequence codes 2 thru 9 are as follows. LED will turn "on"
for 1/4 second and "off" for 1/4 second. This pattern will be
repeated the number of times equal to the code. For example,
six "on" flashes equals a number 6 fault code.

650.75-N4U

26

Unitary Products Group

Summary of Contents for 65075-N4U

Page 1: ...r other flammable vapors and liquids in the vicinity of this or any other appliance WARNING IMPROPER INSTALLATION ADJUSTMENT AL TERATION SERVICE OR MAINTENANCE CAN CAUSE INJURY OR PROPERTY DAMAGE RE F...

Page 2: ...ce since it requires separate properly sized air intake and vent lines The furnace shall not be connected to any type of B BW or L vent or vent connector and not connected to any portion of a factory...

Page 3: ...e access is required for passage to the front when servicing or for inspection or replacement of flue vent connections NOTE In all cases accessibility clearances shall take prece dence over clearances...

Page 4: ...95 2000 C 21 19 3 4 16 5 8 2 2 120 112 2000 D 24 1 2 23 1 4 20 1 8 3 2 3 140 130 2000 D 24 1 2 23 1 4 20 1 8 3 2 3 Vent pipe must be increased to 3 on this model INPUT MBH OUTPUT MBH NOM CFM CAB WIDTH...

Page 5: ...75 1200 17 1 2 91 0 35 65 1370 165 11 8 1 2 9 0 20 14 80 75 1600 21 91 0 30 60 1563 160 11 8 3 4 12 0 20 14 100 95 2000 21 91 0 40 70 1582 170 11 10 1 12 0 20 14 120 112 2000 24 1 2 91 0 40 70 1885 1...

Page 6: ...ambient temperature may drop below 32 F a UL listed self regulated heat tape must be installed It is recommended that self regulating heat tape rated at 3 watts per foot be used This must be installe...

Page 7: ...r sides of the cabinet wall NOTE Air velocity through throw away type filters may not exceed 300 feet per minute All velocities over this require the use of high velocity filters Side Return External...

Page 8: ...n sions Install the plenum following instructions under Ductwork in this instruction SUPPLY AIR DUCTS Installations on combustible material or floors must usea combus tible floor base shown in Figure...

Page 9: ...ezing are possible refer to Page 6 Below Freezing Locations GAS PIPING The gas supply must be installed in accordance with the current National Fuel Gas Code ANSI Z223 1 in the U S or CAN CGA B149 1 o...

Page 10: ...switch should be close to the unit for convenience in servicing With the disconnect switch in the OFF position check all wiring against the unit wiring label Also see the wiring diagram in this instru...

Page 11: ...nnection top right of unit back to the outdoors See Figure 13 or 14 The intake vent should be located either through the wall horizontal or side vent or through the roof vertical vent Care should be t...

Page 12: ...roofor sidewall NOTE Accessory concentric intake vent terminations models 1CT0302 and 1CT0303 are available and approved for use with these furnaces Refer to Form 650 75 N2 4V for installation details...

Page 13: ...ning at the furnace 2 Deburr the piping inside and outside 3 Chamfer the outer edges of the piping 4 Dry fit the entire vent combustion air piping assembly 5 Disassemble the piping and apply cement pr...

Page 14: ...the furnace This may be from within the space in a non confined location or it may be brought into the furnace area from outdoors It is not directly ducted into the furnace A single properly sized pi...

Page 15: ...m dimension of rectangular ducts shall be three inches 2 One permanent opening commencing within 12 inches of the top of the enclosure shall be permitted where the equipment has clearances of at least...

Page 16: ...t connections NOTE An offset using two 45 degree elbows may be required for plenum clearance when the vent is increased to 3 1 Long radius elbows are required for all units 2 Elbows are assumed to be...

Page 17: ...on may require seal ing or shielding of building surfaces with a corrosive resistant material due to vent system corrosive combus tion products PIPING ASSEMBLY The final assembly procedure for the ven...

Page 18: ...e allowable locations shown in Figure 24 and Section 7 8 in the National Fuel Gas Code ANSI Z223 1 current edition Follow all local agency and utility requirements if more restrictive than those shown...

Page 19: ...w the instructions with the coil for trapping the drain SAFETY CONTROLS Control Circuit Fuse A 3 amp fuse is provided to protect the 24 volt transformer from overload caused by control circuit wiring...

Page 20: ...blower motor failure START UP AND ADJUSTMENTS The initial start up of the furnace requires the following addi tional procedures 1 When the gas supply is initially connected to the furnace the gas pip...

Page 21: ...MPLE CHECKING GAS INPUT It is found by measurement that it takes 26 seconds for the hand on the 1 cubic foot dial to make a revolution with only a 120 000 Btuh furnace running Using this information l...

Page 22: ...and electrical supplies ON Start furnace and observe manifold pressure on manometer 5 Adjust manifold pressure by adjusting gas valve regulator screw for natural gas set at 3 5 W C If gas valve regula...

Page 23: ...or lead Place all unused motor leads on Park terminals Two Park terminals are provided CAUTION Do not energize more than one motor speed at a time or damage to the motor will result ADJUSTMENT OF FAN...

Page 24: ...the thermostat circuit opens the ignition control is deener gized Withtheignitioncontroldeenergized thegasflowstopsand the burner flames are extinguished The venter continues to operate for 15 seconds...

Page 25: ...me Lift filter slightly to dislodge and remove for service 3 Remove the filter and follow the cleaning instructions above DO NOT remove the filter stiffener rods if provided When reinstalling the filt...

Page 26: ...blower and the condensate pan The turbulators can then be gently re moved from the secondary heat exchanger 3 With a stiff wire brush brush out loose scale or soot 4 Vacuum the secondary heat exchang...

Page 27: ...e is lost 5 times during the heating cycle This could be caused by low gas pressure or faulty gas valve 9 FLASH TI61F 2 CONTROL ONLY Indicates reversed line voltage polarity Check incoming power wirin...

Page 28: ...985 835 757 665 450 MED 900 887 851 810 752 693 609 403 LOW 581 577 569 542 468 60 55 1000 B HI 1220 1200 1190 1152 1115 1065 1012 950 872 771 MED 920 915 900 880 842 803 740 650 LOW 725 729 715 700...

Page 29: ...UNIT WIRING DIAGRAM UPFLOW 650 75 N4U Unitary Products Group 29...

Page 30: ...UNIT WIRING DIAGRAM DOWNFLOW HORIZONTAL...

Page 31: ...NOTES 650 75 N4U Unitary Products Group 31...

Page 32: ...ect to change without notice Printed in U S A Copyright by Unitary Products Group 1998 All rights reserved 650 75 N4U Supercedes 650 75 N4U 498 5005 York Drive Norman OK 73069 Unitary Products Group 6...

Reviews: