294604-YTG-G-0511
14
Johnson Controls Unitary Products
115°F
125°F
750
77
29.0
3.3
14.3
11.4
8.5
-
-
-
27.2
3.5
15.5
10.8
7.9
-
-
-
72
25.7
3.2
18.3
15.4
12.5
9.6
-
-
23.5
3.4
17.7
14.7
11.7
8.8
-
-
67
22.5
3.1
22.3
19.4
16.5
13.7
10.8
-
19.9
3.3
19.9
18.6
15.6
12.7
9.7
-
62
20.3
3.1
20.3
20.3
18.4
15.6
12.7
9.8
17.9
3.3
17.9
17.9
16.6
13.6
10.6
7.6
57
22.0
3.1
22.0
22.0
19.9
17.0
14.1
11.3
20.2
3.3
20.2
20.2
18.0
15.1
12.1
9.1
875
77
29.3
3.3
16.8
12.3
9.0
-
-
-
27.1
3.5
18.1
12.2
8.3
-
-
-
72
26.0
3.2
19.7
16.5
13.3
10.1
-
-
23.4
3.4
18.9
15.7
12.4
9.1
-
-
67
22.8
3.1
22.7
20.8
17.6
14.4
11.1
-
19.8
3.3
19.8
19.7
16.5
13.2
9.9
-
62
20.5
3.1
20.5
20.5
19.6
16.4
13.2
10.0
17.7
3.2
17.7
17.7
17.4
14.1
10.8
7.6
57
22.2
3.1
22.2
22.2
21.2
17.9
14.7
11.5
20.1
3.3
20.1
20.1
19.0
15.7
12.4
9.1
1000
77
29.6
3.3
19.3
13.1
9.6
-
-
-
27.0
3.5
20.7
13.5
8.7
-
-
-
72
26.3
3.2
21.2
17.6
14.1
10.5
-
-
23.3
3.4
20.2
16.6
13.0
9.4
-
-
67
23.0
3.1
23.0
22.1
18.6
15.1
11.5
-
19.6
3.3
19.6
19.6
17.3
13.7
10.1
-
62
20.7
3.0
20.7
20.7
20.7
17.2
13.7
10.1
17.6
3.2
17.6
17.6
17.6
14.7
11.1
7.5
57
22.5
3.1
22.5
22.5
22.4
18.9
15.3
11.8
20.0
3.2
20.0
20.0
19.9
16.3
12.7
9.1
1125
72
27.1
3.2
22.6
18.8
15.0
11.2
-
-
24.4
3.4
21.9
17.9
14.0
10.1
-
-
67
23.7
3.1
23.7
23.2
19.8
16.0
12.2
-
20.6
3.3
20.6
20.6
18.7
14.8
10.9
-
62
21.3
3.1
21.3
21.3
21.3
17.5
13.7
9.9
18.4
3.3
18.4
18.4
18.4
14.9
10.9
7.0
57
23.1
3.1
23.1
23.1
23.1
19.3
15.5
11.7
20.9
3.3
20.9
20.9
20.8
16.9
13.0
9.1
1250
72
27.8
3.3
24.1
20.0
15.9
11.8
-
-
25.4
3.5
23.5
19.3
15.1
10.9
-
-
67
24.4
3.2
24.4
24.4
21.0
17.0
12.9
-
21.5
3.4
21.5
21.5
20.1
15.8
11.6
-
62
21.9
3.1
21.9
21.9
21.9
17.8
13.8
9.7
19.3
3.3
19.3
19.3
19.3
15.0
10.8
6.6
57
23.8
3.2
23.8
23.8
23.8
19.7
15.6
11.5
21.8
3.4
21.8
21.8
21.8
17.5
13.3
9.1
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
DEZ030 (2.5 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Net
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Net
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F)
Return Dry Bulb (°F)
90
85
80
75
70
65
90
85
80
75
70
65