294604-YTG-G-0511
18
Johnson Controls Unitary Products
115°F
125°F
1050
77
37.8
4.2
21.3
15.2
10.9
-
-
-
34.0
4.4
22.8
14.3
9.8
-
-
-
72
33.1
4.0
24.9
20.6
16.3
12.0
-
-
29.0
4.3
23.4
19.1
14.9
10.6
-
-
67
28.4
3.9
28.4
26.0
21.7
17.4
13.1
-
24.0
4.1
24.0
24.0
20.0
15.7
11.5
-
62
26.8
3.9
26.8
26.8
24.1
19.8
15.5
11.2
23.5
4.1
23.5
23.5
21.0
16.7
12.4
8.1
57
26.5
3.9
26.5
26.5
23.9
19.6
15.3
11.0
23.4
4.1
23.4
23.4
20.9
16.6
12.4
8.1
1225
77
40.2
4.2
26.4
17.7
12.2
-
-
-
36.3
4.5
28.0
18.1
11.1
-
-
-
72
35.2
4.1
28.3
23.3
18.3
13.3
-
-
30.9
4.3
26.8
21.8
16.9
11.9
-
-
67
30.2
4.0
30.2
29.0
24.4
19.4
14.4
-
25.6
4.2
25.6
25.6
22.7
17.7
12.7
-
62
28.4
3.9
28.4
28.4
27.1
22.1
17.1
12.2
25.0
4.1
25.0
25.0
23.8
18.8
13.8
8.9
57
28.2
3.9
28.2
28.2
26.8
21.9
16.9
11.9
25.0
4.2
25.0
25.0
23.7
18.7
13.8
8.8
1400
77
42.5
4.2
31.5
20.1
13.6
-
-
-
38.5
4.5
33.2
21.8
12.4
-
-
-
72
37.2
4.1
31.7
26.0
20.3
14.7
-
-
32.9
4.4
30.2
24.5
18.9
13.2
-
-
67
31.9
4.0
31.9
31.9
27.1
21.4
15.7
-
27.2
4.2
27.2
27.2
25.3
19.6
14.0
-
62
30.1
4.0
30.1
30.1
30.1
24.4
18.7
13.1
26.6
4.2
26.6
26.6
26.6
20.9
15.2
9.6
57
29.8
4.0
29.8
29.8
29.8
24.1
18.4
12.8
26.5
4.2
26.5
26.5
26.5
20.8
15.2
9.5
1550
72
37.2
4.2
33.9
27.7
21.5
15.3
-
-
32.9
4.5
32.5
26.3
20.1
13.8
-
-
67
31.9
4.1
31.9
31.9
28.7
22.5
16.3
-
27.2
4.3
27.2
27.2
26.9
20.7
14.4
-
62
30.1
4.1
30.1
30.1
30.1
23.9
17.7
11.5
26.6
4.3
26.6
26.6
26.6
20.4
14.1
7.9
57
29.8
4.1
29.8
29.8
29.8
23.6
17.4
11.2
26.5
4.3
26.5
26.5
26.5
20.3
14.0
7.8
1700
72
37.2
4.3
36.2
29.4
22.7
16.0
-
-
32.9
4.6
32.9
28.1
21.3
14.4
-
-
67
31.9
4.2
31.9
31.9
30.2
23.5
16.8
-
27.2
4.5
27.2
27.2
27.2
21.7
14.9
-
62
30.1
4.2
30.1
30.1
30.1
23.4
16.6
9.9
26.6
4.4
26.6
26.6
26.6
19.8
13.0
6.2
57
29.8
4.2
29.8
29.8
29.8
23.1
16.3
9.6
26.5
4.4
26.5
26.5
26.5
19.7
12.9
6.1
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
DEZ042 (3.5 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Net
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Net
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F)
Return Dry Bulb (°F)
90
85
80
75
70
65
90
85
80
75
70
65