294604-YTG-G-0511
22
Johnson Controls Unitary Products
115°F
125°F
1500
77
59.3
6.7
27.4
21.9
16.4
-
-
-
54.7
7.3
25.1
19.7
14.4
-
-
-
72
52.9
6.6
35.4
29.9
24.4
18.9
-
-
48.2
7.1
33.0
27.6
22.3
16.9
-
-
67
46.5
6.4
43.4
37.9
32.4
27.0
21.5
-
41.7
7.0
40.9
35.5
30.2
24.8
19.5
-
62
41.1
6.3
41.1
41.1
39.8
34.3
28.9
23.4
36.3
6.8
36.3
36.3
36.3
31.5
26.2
20.8
57
42.5
6.3
42.5
42.5
41.1
35.6
30.1
24.6
39.0
6.9
39.0
39.0
37.9
32.6
27.2
21.9
1550
77
60.0
6.7
28.2
22.5
16.8
-
-
-
55.3
7.3
26.4
20.4
14.8
-
-
-
72
53.5
6.5
36.4
30.8
25.1
19.4
-
-
48.7
7.1
34.0
28.5
22.9
17.3
-
-
67
47.0
6.4
44.7
39.0
33.3
27.7
22.0
-
42.1
7.0
42.1
36.6
31.0
25.4
19.8
-
62
41.6
6.3
41.6
41.6
40.9
35.2
29.6
23.9
36.7
6.8
36.7
36.7
36.7
32.2
26.7
21.1
57
42.9
6.3
42.9
42.9
42.2
36.5
30.9
25.2
39.4
6.9
39.4
39.4
38.9
33.3
27.8
22.2
1600
77
60.6
6.7
29.0
23.2
17.3
-
-
-
55.8
7.2
27.7
21.0
15.1
-
-
-
72
54.1
6.5
37.5
31.6
25.8
19.9
-
-
49.2
7.1
35.1
29.3
23.5
17.6
-
-
67
47.5
6.4
46.0
40.1
34.2
28.4
22.5
-
42.5
6.9
42.5
37.6
31.8
26.0
20.1
-
62
42.0
6.2
42.0
42.0
42.0
36.1
30.3
24.4
37.0
6.8
37.0
37.0
37.0
33.0
27.2
21.3
57
43.4
6.2
43.4
43.4
43.3
37.5
31.6
25.7
39.8
6.8
39.8
39.8
39.8
34.1
28.3
22.5
1800
72
54.3
6.7
39.8
33.4
27.0
20.6
-
-
49.1
7.3
37.2
30.9
24.6
18.3
-
-
67
47.7
6.5
46.9
42.2
35.8
29.4
23.0
-
42.5
7.1
42.5
39.6
33.3
27.0
20.7
-
62
42.2
6.4
42.2
42.2
42.2
35.8
29.4
23.0
37.0
7.0
37.0
37.0
37.0
31.7
25.4
19.2
57
43.5
6.4
43.5
43.5
43.5
37.1
30.7
24.3
39.7
7.0
39.7
39.7
39.7
33.5
27.3
21.0
2000
72
54.5
6.9
42.0
35.1
28.2
21.2
-
-
49.1
7.4
39.3
32.5
25.8
19.0
-
-
67
47.9
6.7
47.9
44.4
37.4
30.5
23.5
-
42.5
7.3
42.5
41.6
34.9
28.1
21.4
-
62
42.3
6.6
42.3
42.3
42.3
35.4
28.5
21.5
37.0
7.1
37.0
37.0
37.0
30.5
23.7
17.0
57
43.7
6.6
43.7
43.7
43.7
36.8
29.8
22.9
39.7
7.2
39.7
39.7
39.7
33.0
26.2
19.5
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
DEZ060 (5.0 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Net
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Net
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F)
Return Dry Bulb (°F)
90
85
80
75
70
65
90
85
80
75
70
65