294604-YTG-G-0511
30
Johnson Controls Unitary Products
115°F
125°F
1200
77
42.0
4.0
28.4
18.7
12.5
-
-
-
37.4
4.2
29.6
18.3
11.0
-
-
-
72
37.6
3.8
30.8
25.1
19.5
13.8
-
-
32.9
4.0
29.0
23.4
17.7
12.1
-
-
67
33.2
3.7
33.2
31.5
26.4
20.7
15.1
-
28.5
3.9
28.5
28.5
24.5
18.9
13.2
-
62
30.1
3.6
30.1
30.1
27.6
22.0
16.3
10.7
25.5
3.8
25.5
25.5
23.5
17.9
12.3
6.6
57
31.2
3.6
31.2
31.2
29.2
23.5
17.9
12.2
27.1
3.9
27.1
27.1
25.4
19.7
14.1
8.5
1300
77
42.4
4.0
31.1
19.9
13.1
-
-
-
38.0
4.2
32.2
20.3
11.5
-
-
-
72
38.0
3.8
32.3
26.3
20.3
14.4
-
-
33.5
4.0
30.6
24.6
18.7
12.7
-
-
67
33.5
3.7
33.5
32.7
27.6
21.6
15.7
-
29.0
3.9
29.0
29.0
25.8
19.8
13.8
-
62
30.4
3.6
30.4
30.4
28.9
22.9
16.9
11.0
26.0
3.8
26.0
26.0
24.8
18.8
12.8
6.8
57
31.5
3.6
31.5
31.5
30.5
24.5
18.6
12.6
27.5
3.9
27.5
27.5
26.7
20.7
14.7
8.8
1400
77
42.9
4.0
33.8
21.2
13.7
-
-
-
38.6
4.2
34.9
22.3
12.1
-
-
-
72
38.4
3.8
33.9
27.5
21.2
14.9
-
-
34.0
4.1
32.2
25.9
19.6
13.2
-
-
67
33.9
3.7
33.9
33.9
28.8
22.5
16.2
-
29.5
3.9
29.5
29.5
27.0
20.7
14.4
-
62
30.8
3.6
30.8
30.8
30.2
23.9
17.6
11.3
26.4
3.8
26.4
26.4
26.0
19.7
13.4
7.0
57
31.9
3.6
31.9
31.9
31.9
25.6
19.3
13.0
28.0
3.9
28.0
28.0
28.0
21.7
15.4
9.0
1500
72
38.0
3.8
34.5
27.8
21.0
14.3
-
-
33.3
4.0
32.6
25.8
19.1
12.3
-
-
67
33.5
3.7
33.5
33.5
28.5
21.8
15.1
-
28.8
3.9
28.8
28.8
26.4
19.6
12.8
-
62
30.4
3.6
30.4
30.4
29.9
23.1
16.4
9.7
25.9
3.8
25.9
25.9
25.3
18.5
11.8
5.0
57
31.5
3.6
31.5
31.5
31.5
24.8
18.1
11.3
27.4
3.9
27.4
27.4
27.4
20.7
13.9
7.2
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
DEQ042 (3.5 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Net
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Net
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F)
Return Dry Bulb (°F)
90
85
80
75
70
65
90
85
80
75
70
65