294604-YTG-G-0511

Johnson Controls Unitary Products

41

Airflow Performance

Side Duct Application

DEY/DEX024-060  

Size

(Tons)

Model

Mode

Thermostat

Input

Speed

Tap

CFM

External Static Pressure (Inch Water Gauge)

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

Watts

Watts

Watts

Watts

Watts

Watts

Watts

Watts

Watts

024

(2.0)

DEX

Cool

Low

Y1

COOL-A

600

57

74

91

108

126

143

161

179

197

Y1

COOL-B

450

39

54

69

84

100

117

134

152

171

Y1

COOL-C

525

47

63

79

95

112

129

146

164

182

Y1

COOL-D

675

71

88

106

124

142

161

179

198

216

High

Y1+Y2

COOL-A

800

99

117

137

156

176

196

217

237

258

Y1+Y2

COOL-B

600

57

74

91

108

126

143

161

179

197

Y1+Y2

COOL-C

700

76

94

112

130

148

167

186

205

224

Y1+Y2

COOL-D

900

126

146

166

187

208

231

253

277

300

Heat

W1

HEAT-A

800

99

117

137

156

-

-

-

-

-

W1

HEAT-B

720

80

98

116

135

-

-

-

-

-

W1

HEAT-C

880

120

140

160

180

-

-

-

-

-

030

(2.5)

DEX

Cool

Low

Y1

COOL-A

670

61

78

95

113

130

148

166

184

201

Y1

COOL-B

620

54

70

87

104

121

138

156

173

191

Y1

COOL-C

720

70

88

106

124

142

160

178

197

215

Y1

COOL-D

770

81

99

118

136

155

174

193

213

232

High

Y1+Y2

COOL-A

1000

159

179

200

222

246

270

296

323

350

Y1+Y2

COOL-B

925

129

148

169

190

211

233

256

280

304

Y1+Y2

COOL-C

1075

194

214

236

260

285

312

341

371

403

Y1+Y2

COOL-D

1150

233

254

277

302

330

360

392

427

463

Heat

W1

HEAT-A

1000

159

179

200

222

-

-

-

-

-

W1

HEAT-B

900

120

139

159

180

-

-

-

-

-

W1

HEAT-C

1100

206

227

249

274

-

-

-

-

-

W1

HEAT-D

1000

159

179

200

222

-

-

-

-

-

036

(3.0)

DEX

Cool

Low

Y1

COOL-A

900

120

139

159

180

201

222

244

267

291

Y1

COOL-B

750

76

94

113

131

150

168

187

206

225

Y1

COOL-C

830

97

116

135

155

174

194

215

236

256

Y1

COOL-D

980

150

170

191

213

236

260

285

311

337

High

Y1+Y2

COOL-A

1200

261

283

306

333

362

394

429

467

507

Y1+Y2

COOL-B

1000

159

179

200

222

246

270

296

323

350

Y1+Y2

COOL-C

1100

206

227

249

274

300

328

357

389

422

Y1+Y2

COOL-D

1300

325

346

372

401

434

471

511

556

604

Heat

W1

HEAT-A

1200

261

283

306

333

-

-

-

-

-

W1

HEAT-B

1080

196

217

239

263

-

-

-

-

-

W1

HEAT-C

1275

308

330

355

383

-

-

-

-

-

W1

HEAT-D

1200

261

283

306

333

-

-

-

-

-

042

(3.5)

DEX

Cool

Low

Y1

COOL-A

920

139

166

195

224

255

286

319

352

386

Y1

COOL-B

790

100

124

149

176

205

235

266

299

333

Y1

COOL-C

850

117

143

170

198

227

257

289

322

356

Y1

COOL-D

980

159

188

218

249

281

313

346

379

414

High

Y1+Y2

COOL-A

1400

338

383

426

468

509

549

589

627

664

Y1+Y2

COOL-B

1200

245

281

318

354

390

426

462

497

533

Y1+Y2

COOL-C

1300

290

330

370

409

447

485

523

560

596

Y1+Y2

COOL-D

1500

391

439

486

532

576

618

660

700

739

Heat

W1

HEAT-A

1225

256

293

330

367

-

-

-

-

-

W1

HEAT-B

1100

203

237

270

304

-

-

-

-

-

W1

HEAT-C

1350

314

356

397

438

-

-

-

-

-

W1

HEAT-D

1225

256

293

330

367

-

-

-

-

-

048

(4.0)

DEX

Cool

Low

Y1

COOL-A

1050

184

216

248

280

313

346

380

414

449

Y1

COOL-B

920

139

166

195

224

255

286

319

352

386

Y1

COOL-C

980

159

188

218

249

281

313

346

379

414

Y1

COOL-D

1120

211

245

279

313

348

382

417

452

486

High

Y1+Y2

COOL-A

1600

448

500

551

600

647

693

736

779

819

Y1+Y2

COOL-B

1400

338

383

426

468

509

549

589

627

664

Y1+Y2

COOL-C

1500

391

439

486

532

576

618

660

700

739

Y1+Y2

COOL-D

1700

508

565

620

672

723

772

818

863

905

Heat

W1

HEAT-A

1600

448

500

551

600

647

-

-

-

-

W1

HEAT-B

1440

359

405

449

493

535

-

-

-

-

W1

HEAT-C

1760

546

606

663

718

771

-

-

-

-

W1

HEAT-D

1600

448

500

551

600

647

-

-

-

-

060

(5.0)

DEY

Cool

Low

Y1

COOL-A

1170

235

283

328

368

404

435

463

485

505

Y1

COOL-B

1110

205

258

304

345

381

410

434

451

465

Y1

COOL-C

1210

255

301

344

384

420

454

483

509

533

Y1

COOL-D

1270

286

329

371

410

448

483

516

547

576

High

Y1+Y2

COOL-A

1750

559

608

658

710

762

815

870

925

981

Y1+Y2

COOL-B

1650

498

542

588

634

683

732

783

835

888

Y1+Y2

COOL-C

1800

590

643

696

750

805

860

916

973

1030

Y1+Y2

COOL-D

1900

654

715

775

836

895

955

1013

1072

-

Heat

W1

HEAT-A

1900

654

715

775

836

895

-

-

-

-

W1

HEAT-B

1975

703

772

839

904

968

-

-

-

-

W1

HEAT-C

2150

823

913

999

1079

1154

-

-

-

-

W1

HEAT-D

2070

767

847

923

997

1066

-

-

-

-

Summary of Contents for AFFINITY DEZ024

Page 1: ...y packaged air conditioners are designed for outdoor installation Only utility and duct connections are required at the point of installation Field installed electric heater accessories are available...

Page 2: ...ponent Location Cooling Only Direct Drive Condenser Fan Motor Highly Efficient Enhanced Copper Tube Aluminum Fin Indoor Coil Highly Efficient Enhanced Copper Tube Enhanced Aluminum Fin OR Micro Channe...

Page 3: ...ate condensate will build up The condensate pan conforms to ASHRAE 62 89 standards Ventilation for Acceptable Indoor Air Quality Condensate Drain The heavy duty 3 4 inch NPTI copper connection is more...

Page 4: ...rtment has an additional large panel with a built in handle tab Removing this panel will allow the blower assembly to slide out for easy removal for maintenance and ease of trouble shooting Replacemen...

Page 5: ...vable when required to lower unit height Filters shall be furnished and be accessible through a removable access door sealed airtight Units vertical discharge and return duct configuration shall be de...

Page 6: ...18 0 71 18 0 71 18 0 71 18 0 71 18 Circuitry Type 2 pass Microchannel 2 pass Microchannel 2 pass Microchannel 2 pass Microchannel 2 pass Microchannel 2 pass Microchannel EVAPORATOR COIL DATA Face area...

Page 7: ...0 Tube diameter in 3 8 3 8 3 8 3 8 3 8 3 8 Circuitry Type Interlaced Interlaced Interlaced Interlaced Interlaced Interlaced EVAPORATOR COIL DATA Face area Sq Ft 4 38 4 38 4 38 5 63 5 63 5 63 Rows 2 2...

Page 8: ...ins per inch 20 20 20 20 20 Tube diameter in 3 8 3 8 3 8 3 8 3 8 Circuitry Type Interlaced Interlaced Interlaced Interlaced Interlaced EVAPORATOR COIL DATA Face area Sq Ft 4 38 4 38 4 38 5 63 5 63 Row...

Page 9: ...SORS Type Scroll 2 spd Quantity 1 CONDENSER COIL DATA Face area Sq Ft 16 4 Rows 2 Fins per inch 20 Tube diameter in 3 8 Circuitry Type Interlaced EVAPORATOR COIL DATA Face area Sq Ft 5 63 Rows 3 Fins...

Page 10: ...1 60 187 252 125 208 230 3 60 187 252 125 460 3 60 432 504 125 575 3 60 540 630 125 DEX 208 230 1 60 187 252 115 208 230 3 60 187 252 115 460 3 60 432 504 115 048 4 0 DEZ 208 230 1 60 187 252 115 208...

Page 11: ...32 4 1 9 21 2 17 5 13 9 10 2 29 7 2 0 21 8 18 2 14 6 11 0 67 30 3 2 1 30 3 26 1 22 5 18 8 15 2 27 2 2 1 27 2 24 8 21 2 17 6 13 9 62 27 4 1 9 27 4 27 4 23 7 20 1 16 4 12 8 24 6 1 9 24 6 24 6 22 7 19 1...

Page 12: ...1 17 5 17 5 17 5 14 4 11 3 8 1 15 5 2 3 15 5 15 5 15 5 12 4 9 2 6 0 57 17 6 2 1 17 6 17 6 17 0 13 9 10 7 7 6 15 3 2 3 15 3 15 3 14 7 11 5 8 3 5 1 900 72 20 8 2 3 19 0 15 6 12 1 8 7 17 7 2 4 17 7 14 4...

Page 13: ...6 34 6 2 7 25 6 22 0 18 4 14 7 67 34 9 2 5 32 2 28 3 24 8 21 3 17 8 32 5 2 7 31 2 27 5 23 9 20 2 16 6 62 32 4 2 4 32 4 32 4 30 1 26 6 23 2 19 7 29 8 2 6 29 8 29 8 28 7 25 1 21 4 17 8 57 32 4 2 4 32 4...

Page 14: ...3 0 20 7 20 7 20 7 17 2 13 7 10 1 17 6 3 2 17 6 17 6 17 6 14 7 11 1 7 5 57 22 5 3 1 22 5 22 5 22 4 18 9 15 3 11 8 20 0 3 2 20 0 20 0 19 9 16 3 12 7 9 1 1125 72 27 1 3 2 22 6 18 8 15 0 11 2 24 4 3 4 21...

Page 15: ...40 4 3 0 29 7 25 6 21 4 17 3 67 40 1 2 8 37 8 32 8 28 8 24 8 20 9 37 4 3 0 36 2 32 1 27 9 23 8 19 6 62 37 3 2 7 37 3 37 3 36 4 32 4 28 5 24 5 35 0 2 9 35 0 35 0 34 6 30 4 26 3 22 1 57 37 4 2 7 37 4 37...

Page 16: ...6 5 3 4 26 5 26 5 26 5 22 5 18 4 14 4 23 5 3 6 23 5 23 5 23 5 19 5 15 4 11 2 57 26 5 3 4 26 5 26 5 26 5 22 4 18 4 14 3 23 4 3 6 23 4 23 4 23 4 19 3 15 1 10 9 1300 72 31 4 3 6 26 4 22 1 17 8 13 5 28 1...

Page 17: ...49 6 3 6 39 5 33 1 26 7 20 3 67 48 9 3 2 48 9 42 3 36 1 29 9 23 7 45 1 3 5 45 1 41 3 34 9 28 5 22 1 62 44 9 3 2 44 9 44 9 44 9 38 7 32 5 26 3 41 0 3 5 41 0 41 0 41 0 34 6 28 2 21 8 57 41 5 3 2 41 5 41...

Page 18: ...2 30 1 4 0 30 1 30 1 30 1 24 4 18 7 13 1 26 6 4 2 26 6 26 6 26 6 20 9 15 2 9 6 57 29 8 4 0 29 8 29 8 29 8 24 1 18 4 12 8 26 5 4 2 26 5 26 5 26 5 20 8 15 2 9 5 1550 72 37 2 4 2 33 9 27 7 21 5 15 3 32 9...

Page 19: ...56 4 4 1 39 9 34 5 29 0 23 5 67 56 6 3 7 49 7 44 5 39 2 34 0 28 8 52 9 4 0 48 8 43 3 37 9 32 4 26 9 62 51 5 3 7 51 5 51 5 45 2 40 0 34 8 29 5 48 9 4 0 48 9 48 9 45 3 39 8 34 3 28 9 57 53 3 3 7 53 3 53...

Page 20: ...37 5 4 7 37 5 37 5 37 5 31 9 26 3 20 7 33 4 5 0 33 4 33 4 33 4 28 6 22 8 17 1 57 37 2 4 7 37 2 37 2 37 2 31 6 26 0 20 4 32 4 5 0 32 4 32 4 32 4 27 5 21 8 16 0 1700 72 46 2 5 0 36 4 30 5 24 6 18 7 42...

Page 21: ...70 4 5 3 49 7 42 4 35 2 27 9 67 68 8 4 6 61 7 54 5 47 2 40 0 32 7 63 7 5 1 59 4 52 1 44 8 37 6 30 3 62 61 9 4 5 61 9 61 9 57 0 49 8 42 5 35 3 57 5 5 0 57 5 57 5 54 8 47 5 40 2 32 9 57 54 1 4 5 54 1 54...

Page 22: ...42 0 6 2 42 0 42 0 42 0 36 1 30 3 24 4 37 0 6 8 37 0 37 0 37 0 33 0 27 2 21 3 57 43 4 6 2 43 4 43 4 43 3 37 5 31 6 25 7 39 8 6 8 39 8 39 8 39 8 34 1 28 3 22 5 1800 72 54 3 6 7 39 8 33 4 27 0 20 6 49...

Page 23: ...19 1 15 8 12 5 9 2 28 4 1 7 20 4 17 1 13 7 10 4 67 29 1 1 5 27 0 21 7 18 4 15 1 11 8 26 7 1 7 25 6 22 2 18 9 15 6 12 2 62 27 3 1 5 27 3 27 3 20 6 17 3 14 0 10 7 24 7 1 6 24 7 24 7 21 6 18 2 14 9 11 6...

Page 24: ...1 6 5 72 19 4 2 1 17 2 14 0 10 8 7 6 16 6 2 3 16 3 13 1 9 9 6 6 67 17 0 2 1 17 0 17 0 14 3 11 1 7 9 14 1 2 2 14 1 14 1 13 2 10 0 6 8 62 16 0 2 1 16 0 16 0 16 0 12 8 9 6 6 4 13 6 2 2 13 6 13 6 13 6 10...

Page 25: ...36 7 2 4 26 5 22 6 18 7 14 8 67 38 8 2 1 34 4 30 2 26 5 22 8 19 0 36 0 2 3 33 5 29 6 25 7 21 7 17 8 62 34 9 2 1 34 9 34 9 32 3 28 6 24 9 21 1 32 1 2 3 32 1 32 1 30 6 26 7 22 7 18 8 57 33 3 2 1 33 3 3...

Page 26: ...9 14 1 8 6 72 28 1 3 0 23 6 19 6 15 6 11 7 25 1 3 2 22 5 18 5 14 5 10 5 67 25 7 2 9 26 1 25 8 21 8 17 8 13 9 22 2 3 1 22 2 22 6 20 4 16 4 12 0 62 22 7 2 9 22 7 22 7 23 6 19 6 15 7 11 7 19 6 3 1 19 6 1...

Page 27: ...42 1 2 6 32 5 27 4 22 3 17 2 67 42 8 2 3 41 5 34 8 29 8 24 7 19 7 39 9 2 5 39 2 34 1 29 0 23 9 18 8 62 39 6 2 3 39 6 39 6 38 1 33 1 28 0 23 0 36 3 2 5 36 3 36 3 35 5 30 4 25 3 20 2 57 33 4 2 3 33 4 33...

Page 28: ...29 1 19 2 11 5 72 31 7 3 3 27 4 22 5 17 6 12 7 27 9 3 5 26 2 21 2 16 3 11 3 67 27 7 3 2 27 7 27 7 23 2 18 3 13 4 23 3 3 4 23 3 23 3 21 0 16 0 11 0 62 26 2 3 1 26 2 26 2 26 2 21 3 16 4 11 5 23 0 3 4 23...

Page 29: ...5 3 1 39 8 33 4 27 0 20 5 67 51 8 2 8 51 1 44 1 38 0 31 8 25 7 47 4 3 0 47 0 41 8 35 4 29 0 22 6 62 47 2 2 7 47 2 47 2 46 6 40 5 34 3 28 2 43 4 2 9 43 4 43 4 42 9 36 5 30 0 23 6 57 46 2 2 5 46 2 46 2...

Page 30: ...34 9 22 3 12 1 72 38 4 3 8 33 9 27 5 21 2 14 9 34 0 4 1 32 2 25 9 19 6 13 2 67 33 9 3 7 33 9 33 9 28 8 22 5 16 2 29 5 3 9 29 5 29 5 27 0 20 7 14 4 62 30 8 3 6 30 8 30 8 30 2 23 9 17 6 11 3 26 4 3 8 2...

Page 31: ...53 3 3 2 38 5 32 9 27 3 21 7 67 52 8 2 8 48 7 43 2 37 8 32 4 27 0 50 6 3 2 48 2 42 6 36 9 31 3 25 7 62 49 7 2 8 49 7 49 7 45 1 39 8 34 4 29 0 47 5 3 2 47 5 47 5 44 9 39 3 33 7 28 1 57 48 1 2 8 48 1 48...

Page 32: ...32 4 20 3 14 3 72 45 3 4 5 36 1 30 1 24 2 18 3 42 4 4 9 35 2 29 2 23 1 17 1 67 41 4 4 4 41 4 38 9 33 0 27 1 21 2 38 0 4 8 38 0 38 0 32 0 25 9 19 9 62 38 3 4 4 38 3 38 3 38 3 32 3 26 4 20 5 34 8 4 9 34...

Page 33: ...68 2 4 2 49 2 41 6 34 1 26 5 67 68 1 3 6 63 3 55 7 48 1 40 4 32 8 63 1 4 1 60 9 53 3 45 8 38 2 30 7 62 60 1 3 7 60 1 61 6 51 5 43 8 36 2 28 5 57 1 4 1 57 1 58 6 51 1 43 5 36 0 28 4 57 56 4 3 7 56 4 56...

Page 34: ...8 43 8 42 0 35 5 29 1 22 6 57 46 7 5 4 46 7 46 7 45 6 39 1 32 6 26 1 44 1 5 9 44 1 44 1 43 1 36 7 30 2 23 8 1800 77 59 0 5 7 36 5 25 7 18 7 53 8 6 3 38 7 25 2 18 2 72 53 8 5 7 42 6 35 6 28 6 21 6 48...

Page 35: ...24 0 1 5 24 0 24 0 24 0 20 6 17 1 13 7 22 7 1 7 22 7 22 7 22 7 19 2 15 7 12 3 57 24 4 1 5 24 4 24 4 24 4 20 8 17 3 13 7 23 0 1 7 23 0 23 0 23 0 19 5 15 9 12 4 95 F 105 F 600 77 21 8 1 4 12 1 8 8 7 0...

Page 36: ...28 8 24 8 20 7 16 6 29 2 2 1 29 2 29 2 28 0 23 9 19 8 15 7 57 30 5 1 9 30 5 30 5 30 5 26 3 22 1 17 9 28 9 2 1 28 9 28 9 28 8 24 7 20 5 16 3 95 F 105 F 675 77 26 3 1 7 12 6 10 6 8 6 24 3 2 0 12 7 9 3 7...

Page 37: ...4 31 4 26 4 21 4 35 7 2 5 35 7 35 7 34 7 29 7 24 7 19 7 57 37 6 2 3 37 6 37 6 37 8 32 6 27 4 22 3 35 7 2 5 35 7 35 7 35 7 30 5 25 4 20 3 95 F 105 F 800 77 31 4 1 9 16 9 13 6 10 7 28 7 2 2 16 5 12 0 9...

Page 38: ...4 36 2 30 1 23 9 41 8 3 2 41 8 41 8 40 8 34 6 28 4 22 3 57 46 0 2 9 46 0 46 0 45 5 39 2 32 8 26 4 42 9 3 1 42 9 42 9 42 7 36 4 30 1 23 8 95 F 105 F 925 77 34 4 2 4 17 5 14 0 10 6 31 7 2 6 17 7 12 8 9...

Page 39: ...1 6 34 2 26 8 48 7 3 5 48 7 48 7 47 2 39 8 32 4 24 9 57 50 8 3 2 50 8 50 8 50 7 43 0 35 4 27 7 47 8 3 5 47 8 47 8 47 7 40 2 32 6 25 1 95 F 105 F 1050 77 42 1 2 7 21 6 17 3 13 2 38 2 3 1 22 1 16 4 12 0...

Page 40: ...0 61 0 54 7 47 2 39 6 32 0 57 1 4 5 57 1 57 1 52 2 44 9 37 6 30 3 57 58 9 3 9 58 9 58 9 58 2 50 7 43 3 35 8 56 4 4 5 56 4 56 4 55 6 48 0 40 4 32 8 95 F 105 F 1150 77 51 8 3 5 23 5 19 9 16 3 48 4 3 9 2...

Page 41: ...389 422 Y1 Y2 COOL D 1300 325 346 372 401 434 471 511 556 604 Heat W1 HEAT A 1200 261 283 306 333 W1 HEAT B 1080 196 217 239 263 W1 HEAT C 1275 308 330 355 383 W1 HEAT D 1200 261 283 306 333 042 3 5 D...

Page 42: ...669 711 Y1 COOL D 1700 467 524 579 632 683 732 779 825 868 Heat W1 HEAT A 1600 408 461 512 562 610 657 W1 HEAT B 1440 313 359 405 450 494 537 W1 HEAT C 1760 503 562 619 674 726 777 W1 HEAT D 1600 408...

Page 43: ...2 COOL A 1000 159 179 200 222 246 270 296 323 350 Y1 Y2 COOL B 925 129 148 169 190 211 233 256 280 304 Y1 Y2 COOL C 1075 194 214 236 260 285 312 341 371 403 Y1 Y2 COOL D 1150 233 254 277 302 330 360 3...

Page 44: ...0 159 179 200 222 036 3 0 DEQ Cool Y1 COOL A 1200 261 283 306 333 362 394 429 467 507 Y1 COOL B 1000 159 179 200 222 246 270 296 323 350 Y1 COOL C 1100 206 227 249 274 300 328 357 389 422 Y1 COOL D 13...

Page 45: ...45 1170 349 913 1070 372 981 964 393 1048 High 5 1458 354 797 1362 379 859 1262 402 923 1156 423 986 1040 436 1048 042 3 5 DEZ Low 1 1241 221 702 1151 245 778 1058 268 853 Low Medium 2 1406 299 759 13...

Page 46: ...2 0 03 0 06 1300 0 07 0 03 0 17 036 3 0 DEZ DEQ DEX 700 0 01 0 00 0 02 0 03 800 0 01 0 01 0 02 0 03 900 0 01 0 01 0 02 0 04 1000 0 02 0 01 0 02 0 04 1100 0 03 0 01 0 03 0 05 1200 0 04 0 02 0 03 0 06 1...

Page 47: ...225 1225 460 3 60 1225 1225 1225 1225 575 3 60 1225 1225 1225 1225 048 4 0 DEX 208 230 1 60 1200 1430 1430 1430 208 230 3 60 1200 1430 1430 1430 460 3 60 1200 1430 1430 1430 DEZ DEQ 208 230 1 60 1200...

Page 48: ...nd Rating1 dB A 1 Rated in accordance with ARI 270 standard Octave Band Centerline Frequency Hz 125 250 500 1000 2000 4000 8000 024 2 0 DEZ DEQ 80 72 70 65 76 66 72 58 DEX 73 61 5 64 5 68 5 66 5 62 60...

Page 49: ...15 2NH04501058 10 1 9 6 19 5 20 2NH04501558 15 1 14 4 25 5 30 042 3 5 208 230 1 60 15 7 88 25 1 7 6 0 None 27 3 35 2NH04500506 3 8 5 1 18 1 20 8 30 1 33 5 40 40 2NH04500706 5 6 7 5 2 27 1 31 3 41 4 46...

Page 50: ...1 74 7 84 7 80 90 460 3 60 9 6 70 15 1 1 7 6 None 20 7 25 2NH04501046 10 1 12 24 5 30 2NH04501546 15 1 18 32 1 35 2NH04502046 20 2 24 1 39 6 40 2NH04502546 25 2 30 1 47 1 50 575 3 60 7 4 53 12 0 8 7 6...

Page 51: ...H04501058 10 1 9 6 14 2 15 2NH04501558 15 1 14 4 20 2 25 042 3 5 208 230 1 60 15 7 88 25 1 4 6 8 None 27 8 35 2NH04500506 3 8 5 1 18 1 20 8 31 1 34 5 40 40 2NH04500706 5 6 7 5 2 27 1 31 3 42 4 47 6 45...

Page 52: ...30 35 2NH04500706 5 6 7 5 2 27 1 31 3 39 2 44 4 40 45 2NH04501006 7 5 10 2 36 1 41 7 50 5 57 5 60 60 030 2 5 208 230 1 60 14 1 70 22 1 2 4 3 None 23 1 30 2NH04500506 3 8 5 1 18 1 20 8 27 9 31 4 35 35...

Page 53: ...upply Blower Motor Electric Heat Option MCA1 Amps 1 Minimum Circuit Ampacity Max Fuse2 Breaker3 Size Amps 2 Maximum Over Current Protection per standard UL 1995 3 Fuse or HACR circuit breaker size ins...

Page 54: ...294604 YTG G 0511 54 Johnson Controls Unitary Products Typical Wiring Diagrams Typical DEZ024 060 Cooling Only 208 230 1 60 volt Wiring Diagram...

Page 55: ...294604 YTG G 0511 Johnson Controls Unitary Products 55 Typical DEZ036 060 Cooling Only 208 230 3 60 volt Wiring Diagram...

Page 56: ...294604 YTG G 0511 56 Johnson Controls Unitary Products Typical DEZ036 060 Cooling Only 460 575 3 60 volt Wiring Diagram...

Page 57: ...294604 YTG G 0511 Johnson Controls Unitary Products 57 Typical DEQ024 048 Cooling Only 208 230 1 60 volt Wiring Diagram...

Page 58: ...294604 YTG G 0511 58 Johnson Controls Unitary Products Typical DEQ060 Cooling Only 208 230 1 60 volt Wiring Diagram...

Page 59: ...294604 YTG G 0511 Johnson Controls Unitary Products 59 Typical DEQ036 048 Cooling Only 208 230 3 60 volt Wiring Diagram...

Page 60: ...294604 YTG G 0511 60 Johnson Controls Unitary Products Typical DEQ060 Cooling Only 208 230 3 60 volt Wiring Diagram...

Page 61: ...294604 YTG G 0511 Johnson Controls Unitary Products 61 Typical DEQ036 048 Cooling Only 460 575 3 60 volt Wiring Diagram...

Page 62: ...294604 YTG G 0511 62 Johnson Controls Unitary Products Typical DEQ060 Cooling Only 460 575 3 60 volt Wiring Diagram...

Page 63: ...294604 YTG G 0511 Johnson Controls Unitary Products 63 Typical DEX024 048 DEY060 Cooling Only 208 230 1 60 volt Wiring Diagram...

Page 64: ...294604 YTG G 0511 64 Johnson Controls Unitary Products Typical DEX036 048 DEY060 Cooling Only 208 230 3 60 volt Wiring Diagram...

Page 65: ...294604 YTG G 0511 Johnson Controls Unitary Products 65 Typical DEX036 048 DEY060 Cooling Only 460 3 60 volt Wiring Diagram...

Page 66: ...1 396 22 25 25 108 94 91 104 DEX 405 400 22 25 25 109 95 92 105 042 3 5 DEZ 405 400 23 21 25 90 83 109 118 DEQ 411 406 22 25 25 110 96 93 106 DEX 415 410 22 25 25 111 97 94 108 048 4 0 DEZ 406 401 21...

Page 67: ...0 Bottom2 3 2 Units may be installed on combustable floors made from wood or class A B or C roof covering materials 3 Minimum Clearance of 1inch all sides of supply air duct for the first 3 foot of du...

Page 68: ...LTAGE CONN 7 8 DIA KNOCKOUT 4 5 8 26 3 4 CONDENSATE DRAIN 3 4 NPTF HIGH VOLTAGE CONN 1 3 32 DIA KNOCKOUT LOW VOLTAGE CONN 7 8 DIA KNOCKOUT HIGH VOLTAGE CONN 1 31 32 x 7 8 KNOCKOUT 22 1 2 43 1 2 40 1 2...

Page 69: ...ons Unit Typical Slab on Ground Installation ROOF CURB INSTALLATION REAR DUCT ROOF CURB INSTALLATION BOTTOM DUCT SLAB ON GROUND INSTALLATION TO POWER SUPPLY SUPPLY AIR DUCT RETURN AIR DUCT FIELD SUPPL...

Page 70: ...rb also available SUPPLY AIR DUCT RETURN AIR DUCT CONTROL WIRING TO INDOOR THERMOSTAT TO POWER SUPPLY FIELD SUPPLIED DISCONNECT SWITCH MOUNTED ON UNIT 1 RECOMMENDED DUCT SIZE 17 1 8 x 21 1 2 RECOMMEND...

Page 71: ...b Cross Section 1 UNIT BASE RAIL COUNTERFLASHING CANT STRIP INSULATION AND ROOFING MATERIAL ROOF DECK AND ROOFING MATERIAL INSULATION CURB FRAME 14 8 MIN ABOVE FINISHED ROOF WOOD NAILER UNIT BASE 3 4...

Page 72: ...ject to change without notice Printed in U S A 294604 YTG G 0511 Copyright 2011 by Johnson Controls Inc All rights reserved Supersedes 294604 YTG F 1210 Johnson Controls Unitary Products 5005 York Dri...

Reviews: