18
Accessories and Options
IntelliStart (Model 040 only)
IntelliStart is a single phase compressor soft starter which
reduces the normal start current (LRA) by 60-70%. It should
be used in applications that require low starting amps,
reduced compressor start-up noise, off-grid, and improved
start-up behavior. IntelliStart is available as a factory
installed option or a field installed kit. IntelliStart is available
on 208-230/60/1 voltage.
Water Connection Kits (Field Installed)
Water connection kits are available to facilitate loop side and
load side water connections.
• MA4FPT
-
Forged brass 1" MPT x 1" FPT square street elbow
with P/T plug for 040 water side connections
• MA5FPT
-
Forged brass 1.25" MPT x 1.25" FPT square
street elbow with P/T plug for 050-066 water side
connections
• WFI-HKM-100-24-MO
- 1 inch x 24 inch stainless steel
braided hose kit
• WFI-HKM-125-24-MO
- 1
1
⁄
4
inch x 24 inch stainless steel
braided hose kit
Earth Loop Pump Kit (Field Installed)
A specially designed one or two-pump module provides all
liquid flow, fill and connection requirements for independent
single unit systems (230/60/1 only). The one-pump module
(FC1-FPT or FC1-GL) is capable of 25 feet of head at 12.0
GPM, while the two-pump module (FC2-FPT or FC1-GL) is
capable of 50 feet of head at 12.0 GPM.
Load-side Pump Kit (Field Installed)
Four (4) load pump kits are available to provide all liquid
flow requirements for independent single unit systems
(230/60/1 only). Part number
24S516-10
(Grundfos UPS15-
42RU) is a composite body pump.
EWPK2
(Grundfos
UP26-99SF) is stainless steel body pump. Part number
EWPK1 and EWPK3 come with a cast iron body pump
(Grundfos UP26-99F) that can be used for hydronic
heating applications.
Calculate the system pressure drop then refer to the
pump curves in figure 8 to select the proper pump. All
four (4) of the pump kits can be used for hydronic heating
applications as long as they meet the flow requirements.
If the flow requirements are outside the pump curve, an
alternate pump will need to be obtained to maintain the
necessary flow.
• 24S516-10
- UPS15-42RU composite PPS,
3
⁄
4
inch union
sweat connection
• EWPK1
- UP26-99F cast iron volute, 1 inch FPT
flange connection
• EWPK2
- UP26-99SF Stainless Steel volute, 1 inch FPT
flange connection
• EWPK3
- UP26-99F cast iron volute, 1-
1
⁄
4
inch FPT
flange connection
Figure 8:
UPS15-42RU and UP26-99F Pump Curve
UPS15-42RU, and UP26-99F Single Pump Curve
26-99F Two Pump Curve
0
5
10
15
20
25
30
35
0 5 10 15 20 25 30 35
Feet of Head
GPM
Pump Curve - Single Pump
UP26-99F
UPS15-42RU
0
10
20
30
40
50
60
70
0 5 10 15 20 25 30 35
Feet of Head
GPM
Pump Curve - Two Pumps
UP26-99F (2 pumps)
NOTE:
Never use piping smaller than 1 inch. Limit length of
pipe to 50 feet or less.
Type L Copper Tube
GPM
3/4
1
1-1/4
1-1/2
2
2
1.5
3
3.2
4
5.5
1.4
5
8.5
2.1
6
2.9
1.1
7
3.9
1.4
8
5.0
1.8
9
6.1
2.3
0.9
10
7.5
2.8
1.1
12
3.9
1.6
14
5.2
2.1
16
6.6
2.7
18
8.2
3.4
20
10.0
4.1
1.1
22
5.0
1.3
25
6.3
1.6
30
2.2
35
2.9
40
3.8
45
4.7
50
5.7
Type L Copper Pressure Loss
Ft of Hd per 100 ft
NOTE:
Standard piping practice limits pressure drop to 4
feet of hd per 100 feet in 2 inch and larger pipe.