172988-YUM-A-0106

Unitary Products Group

5

If, during the inspection of your furnace, you find any of the following
conditions:

Excessive amounts of dust and lint on components.

Damaged or deteriorated components or surfaces.

Leaks or blockage in the vent pipe passages.

Water on any surface inside or outside of the furnace.

Do not operate the furnace, call a certified dealer / servicing contractor
to check and / or clean your furnace, or for more information if you have
questions about the operation of your furnace.
If all components appear to be in good operating condition, replace the
front panels. Turn ON the gas and electrical power supplies to the fur-
nace, and set thermostat to the desired temperature.

Motor Lubrication

The motors in these furnaces are permanently lubricated, and do not
require periodic oiling.

SECTION II: SERVICE AND MAINTENANCE 

MANUAL

SAFETY

The following safety rules must be followed when servicing the
furnace.

FURNACE MAINTENANCE

The furnace should be cleaned and adjusted by a certified dealer or
qualified service contractor once a year or before the start of every
heating season. The following items must be cleaned and serviced or
replaced if there are signs of deterioration.

1.

The vent terminal screen (if applicable).

2.

The furnace vent and combustion air intake passageways. Should
it be necessary to service the vent/air intake system, the manufac-
turer recommends this service be conducted by a qualified service
agency. The operation of this appliance requires the reassembly
and resealing of the vent/air intake system.

3.

The furnace burners, ignitor and flame sensor.

4.

The condensate collection and disposal system. If any disassem-
bly of components containing flue or vent gases is required, a
qualified service agency must perform the service.

FURNACE CLEANING

NOTE: The cleaning operations listed below must be performed

only by a qualified service agency.

Burner Removal/Cleaning

The main burners should be checked periodically for dirt accumulation.
If cleaning is required, follow this procedure:

1.

Turn off the electrical power to the unit.

2.

Turn off the gas supply at the external manual shut-off valve and
loosen the ground union joint.

3.

Remove the burner door and remove the burner box cover.

4.

Disconnect wires from flame sensor, rollout switch and HSI igniter.
Remove igniter carefully, as it is easily broken.

5.

Remove the screws that hold the burner box assembly to the vest
panel and remove the assembly.

6.

Remove burners from the burner assembly.

7.

Burners may be cleaned by rinsing in hot water.

8.

Reassemble the burners in the reverse order.

Cleaning the Heat Exchanger

1.

Turn off the electrical power to the unit.

2.

Turn off the gas supply at the external manual shut-off valve and
loosen the ground union joint.

3.

Remove the burner door and remove the burner box cover.

4.

Disconnect wires from flame sensor, rollout switch and HSI igniter.
Remove igniter carefully, as it is easily broken.

5.

Remove the screws that hold the burner box assembly to the vest
panel and remove the assembly.

6.

Remove the vent pipe assembly, vent blower and condensate pan.

7.

The heat exchanger is now exposed.

8.

With a long flexible wire brush, clean inside each tube at both the
top and bottom. The brush must pass around the rear heat
exchanger tubes. Then vacuum loose the scale and dirt from each
tube.

9.

Replace all components in reverse order. Reconnect all wiring.

10. Restore electrical power and gas supply to the furnace.

11.

Check furnace operation.

Cleaning the Secondary Heat Exchanger

1.

Follow steps 1 - 7 under cleaning the Heat Exchanger.

2.

Remove the vent piping from the vent blower housing. Disconnect
the drain lines from the vent blower housing and from the conden-
sate drain pan. Remove the vent blower housing blower and the
condensate pan.

3.

Using a stiff wire brush, remove the loose scale or soot from each
tube.

4.

Vacuum the secondary heat exchanger.

5.

Finish the cleaning procedure by following steps 9 - 11 under
cleaning the Heat Exchanger.

Cleaning the Vent / Air Intake System

Should it be necessary to service the vent / air intake system, the man-
ufacturer recommends this service be conducted by a qualified service
agency.

The operation of this appliance requires the reassembly and resealing
of the vent / air intake system as specified in the “Combustion Air and
Vent System”
 located in the Installation Manual.

NORMAL OPERATION SEQUENCE

The furnace control calculates the optimum firing rate each time the
wall thermostat R and W contacts close or open (at the beginning and
at the end of each call for heat) based on information from the thermo-
stat and past demand. UNLIKE CONVENTIONAL SYSTEMS, THE
WALL THERMOSTAT DOES NOT SIMPLY TURN THE FURNACE ON
AND OFF. THE FURNACE CONTROL CALCULATES THE DEMAND
AND MAY CONTINUE TO FIRE THE FURNACE DURING PORTIONS
OF THE THERMOSTAT "OFF" CYCLE. 

When the wall thermostat R and W contacts close, indicating a call for
heat, the following sequence occurs:

ELECTRIC SHOCK, FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in
dangerous operation, serious injury, death or property
damage.
Improper servicing could result in dangerous operation,
serious injury, and death or property damage.

Before servicing, disconnect all electrical power to the fur-
nace. 

When servicing controls, label all wires prior to discon-
necting. Reconnect wires correctly. 

Verify proper operation after servicing.

Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and danger-
ous operation. Verify proper operation after servicing.

Summary of Contents for Affinity PC9

Page 1: ...if deemed necessary FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury death or property damage Do not store or use gasoline or other flammable vapors a...

Page 2: ...furnace casing making sure the physical support is sound without sagging cracks or gaps Examine the furnace base making sure it is physically sound without cracks gaps or sagging and has a good seal...

Page 3: ...nformation above 2 Set the thermostat to the lowest setting 3 Turn off all electric power to the appliance 4 Remove burner door 5 Move gas control switch to the OFF position Do not force 6 Wait five 5...

Page 4: ...lations may have the air filter in a rack attached to the cas ing of the furnace or placed in the return air duct You can gain access to the filter by pulling on the door or unscrewing the retaining s...

Page 5: ...the gas supply at the external manual shut off valve and loosen the ground union joint 3 Remove the burner door and remove the burner box cover 4 Disconnect wires from flame sensor rollout switch and...

Page 6: ...ovides a 30 second ramp up from zero airflow to full capacity and a 30 second ramp down from full capacity back to zero airflow Whenever there is a change in airflow mode such as from low heat to high...

Page 7: ...witch on the side of the burner box It is a manual reset switch To reset push the small button in the center of the switch If it cannot be reset or if the switch trips again contact a qualified servic...

Page 8: ...Group SECTION III REPLACEMENT PARTS LIST 2 7 13 14 11 5 9 37 10 80 46 45 47 54 64 19 18 27 28 33 30 35 72 71 69 68 1 2 4 5 6 14 15 16 62 55 56 54 21 23 22 31 26 25 59 48 57 60 53 44 43 51 52 49 50 18...

Page 9: ...PLUG WINDOW CLEAR 1 5 44 COMBUSTION AIR TRANSITION 3 WAY 45 TUBING SILICONE Gray 188 ID 2 83 ft Req d 46 TUBING SILICONE Preformed 47 TUBING SILICONE Gray 188 ID 1 25 ft Req d 48 GASKET COMBUSTION BL...

Page 10: ...ET 1CB0324 24 1 2 CABINET 1TK0917 COIL TRANSITION KIT 17 1 2 CABINET 1TK0921 21 CABINET 1TK0924 24 1 2 CABINET REPLACEMENT PART CONTACT INFORMATION This is a generic parts list To request a complete p...

Page 11: ...172988 YUM A 0106 Unitary Products Group 11 SECTION IV WIRING DIAGRAM FIGURE 9 Wiring Diagram...

Page 12: ...ly to products installed in the United States and Canada EXCLUSIONS This warranty does not cover any 1 Shipping labor or material charges 2 Damages resulting from transportation installation or servic...