background image

278432-YTG-A-0407

Unitary Products Group

5

NOTES:

1. Airflow expressed in standard cubic feet per minute (CFM).

2. Return air is through side opposite motor (left side).

3. Motor voltage at 115 V.

4. Airflow through across motor side (right side) may be slightly less than the data shown above.

BLOWER PERFORMANCE CFM - UPFLOW (WITHOUT FILTER) - LEFT SIDE RETURN

Models

Speed

Left Side Airflow Data (SCFM)

Ext. Static Pressure (in. H2O)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

PS8A12(N,L)040UH11

High

1810

1730

1660

1570

1480

1390

1300

1200

1090

930

Medium High

1390

1390

1350

1320

1270

1210

1150

1080

970

790

Medium Low

1120

1120

1120

1110

1080

1080

1020

930

830

690

Low

880

910

920

920

910

870

820

740

650

510

PS8A12(N,L)060UH11

High

1770

1690

1630

1560

1490

1390

1290

1190

1050

920

Medium High

1400

1380

1350

1320

1280

1230

1160

1060

930

780

Medium Low

1120

1130

1150

1130

1120

1080

1000

950

790

630

Low

880

900

900

900

880

850

790

730

660

530

PS8A12(N,L)080UH11

High

1790

1720

1670

1590

1530

1450

1350

1260

1140

1000

Medium High

1420

1370

1350

1320

1280

1230

1170

1090

990

840

Medium Low

1080

1120

1110

1100

1080

1040

1000

920

820

690

Low

N/A

900

900

890

870

850

800

730

670

560

PS8B16(N,L)080UH11

High

2000

1960

1930

1900

1800

1760

1710

1640

1550

1460

Medium

1440

1440

1430

1420

1400

1380

1340

1300

1220

1150

Low

1220

1230

1230

1230

1200

1190

1170

1160

1110

1050

PS8C22N080UH11

PS8C20L080UH11

High

2710

2640

2560

2480

2360

2260

2160

2010

1860

1650

Medium High

2110

2110

2070

2030

1980

1910

1850

1710

1570

1300

Medium Low

1690

1690

1650

1610

1540

1480

1410

1280

1170

1030

Low

1350

1330

1310

1290

1260

1220

1150

1050

970

860

PS8B12(N,L)100UH11

High

1780

1710

1640

1560

1490

1390

1290

1180

1030

820

Medium High

1430

1410

1370

1340

1280

1220

1140

1040

890

730

Medium Low

1140

1170

1150

1120

1080

1040

970

890

760

630

Low

920

940

950

940

920

890

850

770

660

560

PS8B16(N,L)100UH11

High

1950

1890

1840

1790

1730

1660

1570

1480

1390

1300

Medium

1440

1420

1400

1390

1350

1320

1270

1210

1150

1060

Low

1230

1210

1190

1180

1150

1130

1090

1050

990

920

PS8C20(N,L)100UH11

High

2770

2670

2610

2540

2450

2340

2210

2070

1890

1730

Medium High

2120

2060

2030

2000

1950

1880

1810

1720

1580

1370

Medium Low

1690

1660

1630

1610

1560

1490

1420

1350

1240

1070

Low

1390

1370

1330

1290

1250

1200

1120

1010

910

850

PS8C16N115UH11

High

2160

2070

1990

1900

1800

1690

1580

1430

1260

1000

Medium

1760

1720

1690

1630

1560

1480

1390

1250

1080

890

Low

1510

1490

1470

1440

1380

1300

1210

1110

950

780

PS8C20(N,L)115UH11

High

2740

2650

2560

2480

2380

2280

2170

1990

1840

1650

Medium High

2120

2090

2040

2000

1940

1870

1780

1680

1550

1370

Medium Low

1690

1670

1650

1610

1560

1510

1440

1310

1160

1030

Low

1390

1360

1330

1300

1250

1190

1100

1020

940

840

PS8D20(N,L)130UH11

High

2680

2600

2520

2410

2300

2180

2050

1910

1730

1550

Medium High

2140

2110

2070

1990

1930

1850

1770

1670

1530

1370

Medium Low

1660

1640

1620

1570

1530

1470

1400

1310

1220

1090

Low

1370

1350

1320

1290

1240

1190

1140

1040

930

860

Summary of Contents for AFFINITY PS8*UH

Page 1: ...appliance as allowed by the National Fuel Gas Code WARRANTY 20 year limited warranty on the heat exchanger 10 year heat exchanger warranty on commercial applica tions 5 year limited parts warranty FEA...

Page 2: ...12 N L 040UH11 1200 A 14 1 2 13 1 4 11 1 2 10 1 8 PS8A12 N L 060UH11 1200 A 14 1 2 13 1 4 11 1 2 10 1 8 PS8A12 N L 080UH11 1200 A 14 1 2 13 1 4 11 1 2 10 1 8 PS8B16 N L 080UH11 1600 B 17 1 2 16 1 4 14...

Page 3: ...N L 100UH11 100 80 1200 17 1 2 12 0 80 0 40 70 PS8B16 N L 100UH11 100 80 1600 17 1 2 12 0 80 0 35 65 PS8C20 N L 100UH11 100 80 2000 21 14 0 80 0 25 55 PS8C16N115UH11 115 92 1600 21 12 0 80 0 35 65 PS...

Page 4: ...970 1840 1730 1680 1570 1460 1260 Medium Low 1720 1700 1670 1620 1570 1500 1430 1310 1160 1000 Low 1410 1390 1360 1330 1280 1220 1170 1060 930 840 PS8B12 N L 100UH11 High 1700 1620 1560 1480 1390 1300...

Page 5: ...High 2710 2640 2560 2480 2360 2260 2160 2010 1860 1650 Medium High 2110 2110 2070 2030 1980 1910 1850 1710 1570 1300 Medium Low 1690 1690 1650 1610 1540 1480 1410 1280 1170 1030 Low 1350 1330 1310 129...

Page 6: ...ters may not exceed 300 feet per minute All velocities over this require the use of high velocity filters 2 Air flows above 1800 CFM require either return from two sides or one side plus bottom RECOMM...

Page 7: ...Cool Y Single Stage Cool DN11C00124 C 24 Volt Common C 24 Volt Common Optional w Batteries BN11C01124 DP11C40124 PSC 2 STAGE COOLING READY FURNACE CONTROL SINGLE STAGE AIR CONDITIONING BN11C00124 BP11...

Page 8: ...CFM 33 4 m3 min Subtract the airflow 0 50 w c 125 Pa from the airflow 0 60 w c 150 Pa to obtain airflow difference 1180 1250 70 CFM 12 m3 min Subtract the total system static from 0 50 w c 125 Pa and...

Reviews: