background image

036-21610-002 Rev. A (1104)

Unitary Products Group

3

Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes.
The furnace shall be installed so that the electrical components are protected from water.
Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.

 * ESP (External Static Pressure) .5" WG is at furnace outlet ahead of cooling coil.

NOTES: 

1. All filters must be high velocity cleanable type.

RATINGS & PHYSICAL / ELECTRICAL DATA

Models

Input

MBH

Output

MBH

Nominal CFM

AFUE

Air Temp. 

Rise °F

PS8A12N040DN11

40

32 1200  80.0 

20-50

PS8A12N060DN11

57

48 1200  80.0 

25-55

PS8A12N080DN11

80

64 1200  80.0 

35-65

PS8B16N080DN11

80

64 1600

80.0 

25-55

PS8B12N100DN11

100

80 1200  80.0 

40-70

PS8C20N100DN11

100

80 2000

80.0 

25-55

PS8C16N115DN11

115

92 1600  80.0 

35-65

PS8C20N115DN11

115

92 2000  80.0 

30-60

PS8D20N130DN11

130

104 2000  80.0 

40-70

Models

Max. Outlet

Air Temp °F

Blower

Blower

Size In.

Total Unit 

Amps

Max 

Over-current

protect

Min.

Wire Size (awg) 

@ 75 ft. one way 

Operation
WGT. LBS

Hp

Amps

PS8A12N040DN11

150

1/3

6.2

10 x 8 

9.0

15

14

100

PS8A12N060DN11

155 

1/3

6.2

10 x 8 

9.0

15

14

110

PS8A12N080DN11

165

1/3

6.2

10 x 8 

9.0

15

14

120

PS8B16N080DN11

160

3/4

11.0

11 x10 

12.0

15

14

130

PS8B12N100DN11

170 

1/2

7.0

10 x 8 

12.0

15

14

125

PS8C20N100DN11

155

1

12.2

11 x 10 

14.0

20

12

140

PS8C16N115DN11

165

3/4

11.0

11 x 10 

12.0

15

14

150

PS8C20N115DN11

160

1

12.2

11 x 10 

14.0

20

12

150

PS8D20N130DN11

170

1

12.2

11 x 10 

14.0

20

12

160

FILTER SIZES

Models

Cabinet Size

Top Return Filter (in)

PS8A12N040DN11

A

(2) 14 x 20

PS8A12N060DN11

A

(2) 14 x 20

PS8A12N080DN11

A

(2) 14 x 20

PS8B16N080DN11

B

(2) 14 x 20

PS8B12N100DN11

B

(2) 14 x 20

PS8C20N100DN11

C

(2) 14 x 20

PS8C16N115DN11

C

(2) 14 x 20

PS8C20N115DN11

C

(2) 14 x 20

PS8D20N130DN11

D

(2) 14 x 20

Summary of Contents for AFFINITY PS8

Page 1: ...its are Category I listed and may be common vented with another gas appliance as allowed by the National Fuel Gas Code ANSI Z223 1 latest edition WARRANTY 20 year limited warranty on the heat exchanger 10 year heat exchanger warranty on commercial applica tions 5 year limited parts warranty FEATURES Dedicated downflow models may be easily applied with out any field conversion Top vent connection a...

Page 2: ...16N080DN11 17 1 2 B 17 1 2 16 1 4 13 1 8 4 0 11 5 8 3 3 4 PS8B12N100DN11 17 1 2 B 17 1 2 16 1 4 13 1 8 4 0 11 5 8 3 3 4 PS8C20N100DN11 21 C 21 19 3 4 16 5 8 4 0 13 3 8 3 3 4 PS8C16N115DN11 21 C 21 19 3 4 16 5 8 4 0 13 3 8 3 3 4 PS8C20N115DN11 21 C 21 19 3 4 16 5 8 4 0 13 3 8 3 3 4 PS8D20N130DN11 24 1 2 D 24 1 2 23 1 4 20 1 8 4 0 15 1 8 3 3 4 HORIZONTAL SIDEWALL VENTING CLEARANCES MUST USE FIELDS C...

Page 3: ...0 0 25 55 PS8C16N115DN11 115 92 1600 80 0 35 65 PS8C20N115DN11 115 92 2000 80 0 30 60 PS8D20N130DN11 130 104 2000 80 0 40 70 Models Max Outlet Air Temp F Blower Blower Size In Total Unit Amps Max Over current protect Min Wire Size awg 75 ft one way Operation WGT LBS Hp Amps PS8A12N040DN11 150 1 3 6 2 10 x 8 9 0 15 14 100 PS8A12N060DN11 155 1 3 6 2 10 x 8 9 0 15 14 110 PS8A12N080DN11 165 1 3 6 2 10...

Page 4: ...50 940 810 700 Medium High 1400 1360 1290 1220 1150 1060 970 860 730 590 Medium Low 1230 1210 1170 1120 1060 990 910 810 680 560 Low 980 970 960 930 890 830 760 680 550 450 PS8B16N080DN11 High 2070 2000 1930 1850 1770 1670 1580 1470 1360 1250 Medium 1650 1630 1610 1560 1490 1420 1360 1270 1170 1040 Low 1410 1400 1370 1340 1320 1270 1210 1140 1050 950 PS8B12N100DN11 High 1710 1650 1580 1510 1420 13...

Page 5: ...total system static is 0 58 w c To determine the system airflow complete the following steps 1 Obtain the airflow values at 0 50 0 60 ESP Airflow 0 50 2110 CFM Airflow 0 60 2020 CFM 2 Subtract the airflow 0 60 from the airflow 0 5 to obtain airflow difference 2020 2110 90 CFM 3 Subtract the total system static from 0 50 and divide this difference by the difference in ESP values in the table 0 60 0...

Page 6: ...1PS0311 115 92 1PS0312 1PS0311 130 104 1PS0312 1PS0311 FIELD INSTALLED ACCESSORIES ELECTRICAL MODEL NO DESCRIPTION USED WITH 2TB17700424 SUBBASE 24V One stage Heat Cool Manual changeover System Switch Cool Off Heat Fan Switch Auto On ALL MODELS 2TH13700424 THERMOSTAT One stage Heat Deluxe 24V with heat only subbase does not include fan switch NOTE For one stage cool or one stage heat cool must be ...

Page 7: ...036 21610 002 Rev A 1104 Unitary Products Group 7 NOTES ...

Page 8: ...e without notice Printed in U S A 036 21610 002 Rev A 1104 Copyright by York International Corp 2004 All rights reserved Supersedes 036 21610 001 Rev A 0804 Unitary 5005 Norman Products York OK Group Drive 73069 NOTES ...