background image

036-21581-001 Rev. B (0904)

4

Unitary Products Group

NOTES:

1. Airflow expressed in standard cubic feet per minute (CFM) and in cubic meters per minute (m

3

/min).

2. Return air is through side opposite motor (left side).
3. Airflows above 1800 CFM (50.97 m

3

/min) require either return from two sides or one side plus bottom.

4. Motor voltage at 115 V.
5. NR = Operation at this static pressure is not recommended.

BLOWER PERFORMANCE CFM

AIRFLOW WITH BOTTOM OR ONE SIDE RETURN

MODELS

Speed

Tap

EXTERNAL STATIC PRESSURE, INCHES W.C. (kPa)

Input/

Airflow/cabinet

0.1

0.2 0.3

0.4

0.5

0.6

0.7 0.8

0.9

1.0

CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM 

PT9A12N040UP11

HIGH 1395

1330

1265

1200

1120

1030

940

820

NR

NR

M-HI 1025

990

960

925

885

825

750

660

NR

NR

M-LO 785

765

745

715

670

625

545

NR

NR

NR

LOW 640

605

590

565

530

465

405

NR

NR

NR

PT9B12N060UP11
PT9B12N080UP11

HIGH 1650 1605 1570 1525 1465 1410 1350 1275 1170 1060 

M-HI 1165 1185 1175 1165 1150 1140 1100 1050  970  875 

M-LO 

895 915 935 940 940 920 905 860 815 750 

LOW 

710 725 725 725 720 700 685 660 625 560 

PT9C20N100UP11

HIGH 2300

2210

2120

2020

1930

1830

1715

1595

1480

1350

M-HI 1950

1900

1830

1755

1680

1595

1500

1390

1270

1155

M-LO 1610

1545

1490

1440

1390

1315

1230

1155

1050

920

LOW 1325

1270

1225

1175

1105

1045

990

905

890

790

PT9C16N080UP11
PT9C16N100UP11

HIGH 1960 1955 1925 1890 1830 1765 1695 1615 1600 1485 

M-HI 1565 1560 1560 1575 1545 1530 1475 1425 1365 1260 

M-LO 1230 1275 1285 1300 1310 1300 1280 1245 1190 1070 

LOW 

930 945 965 975 975 975 975 950 910 850 

PT9D20N120UP11

HIGH 2560 2485 2410 2320 2220 2135 2035 1920 1785 1650 

M-HI 2090 2050 1990 1970 1885 1820 1760 1675 1545 1405 

M-LO 1695 1675 1665 1615 1565 1510 1460 1385 1285 1140 

LOW 1175 1150 1135 1110 1085 1055 1005  980  970  845 

AIRFLOW WITH TWO SIDE RETURNS OR WITH BOTTOM AND ONE SIDE RETURN

MODELS

Speed

Tap

EXTERNAL STATIC PRESSURE, INCHES W.C. (kPa)

Input/

Airflow/cabinet

0.1

0.2 0.3

0.4

0.5

0.6

0.7 0.8

0.9

1.0

CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM 

PT9C20N100UP11

HIGH 2465

2380

2295

2195

2095

1995

1875

1760

1620

1470

M-HI 2085

2035

1960

1880

1800

1705

1605

1485

1360

1235

M-LO 1725

1625

1595

1540

1485

1405

1315

1235

1125

995

LOW 1420

1360

1310

1255

1180

1120

1070

970

950

845

PT9D20N120UP11

HIGH 2615 2535 2450 2385 2285 2175 2075 1945 1825 1670 

M-HI 2055 2045 2015 1985 1932 1855 1785 1730 1605 1470 

M-LO 1690 1650 1620 1600 1570 1525 1470 1395 1300 1200 

LOW 1345 1335 1335 1285 1250 1230 1180  1115 1010  850 

BLK

WHT

GRN

BLK (HOT)

WHT (NEUTRAL)

GRN

NOMINAL
120 VOLT

LINE WIRING CONNECTIONS

SINGLE STAGE HEATING

THERMOSTAT CONNECTIONS

SINGLE STAGE HEATING AND TWO-STAGE COOLING

THERMOSTAT CONNECTIONS

ROOM
THERMOSTAT

FURNACE
CONTROL

CONDENSING
UNIT

TO AIR CONDITIONER
CONTROLS

R

W

G

Y1

C

R

G

C
COMMON T’STAT CONNECTION

Y2

Y1

W1/W

Y/Y2

ROOM
THERMOSTAT

FURNACE
CONTROL

CONDENSING
UNIT

TO AIR CONDITIONER
CONTROLS

R

W

G

Y
C

R

G

C

COMMON T’STAT CONNECTION

W1/W

Y/Y2

ROOM
THERMOSTAT

FURNACE
CONTROL

CONDENSING
UNIT

TO AIR CONDITIONER
CONTROLS

R

W1
W2

G

Y2

R

G

COMMON T’STAT CONNECTION

Y1

Y1

W1/W

C

C

W2

Y/Y2

TWO-STAGE HEATING AND TWO-STAGE COOLING

THERMOSTAT CONNECTIONS

Summary of Contents for AFFINITY PT9

Page 1: ...ludes Two stage gas valve Two stage inducer operation Provides increased comfort level very quiet unit oper ation Adjustable delay timer allows two stage operation with single stage thermostat Compact...

Page 2: ...mension A in B in C in D in PT9A12N040UP11 1200 A 14 1 2 13 1 4 12 1 8 6 1 4 PT9B12N060UP11 1200 B 17 1 2 16 1 4 15 1 8 8 1 2 PT9B12N080UP11 1200 B 17 1 2 16 1 4 15 1 8 8 1 2 PT9C16N080UP11 1600 C 21...

Page 3: ...1PS0503 PT9C20N100UP11 1PS0505 PT9D20N120UP11 1PS0503 ELECTRICAL AND PERFORMANCE DATA Model Input High Low Output High Low Nominal Airflow AFUE Air Temp Rise Max Outlet Air Temp Blower Blower Size Tot...

Page 4: ...280 1245 1190 1070 LOW 930 945 965 975 975 975 975 950 910 850 PT9D20N120UP11 HIGH 2560 2485 2410 2320 2220 2135 2035 1920 1785 1650 M HI 2090 2050 1990 1970 1885 1820 1760 1675 1545 1405 M LO 1695 16...

Page 5: ...al system static falls between ESP values in the table i e 0 58 0 75 etc the static pressure may be rounded to the nearest value in the table determining the airflow using Step 5 or calculate the airf...

Page 6: ...e bottom of the furnace 1BR0314 For 14 1 2 cabinets 1BR0317 For 17 1 2 cabinets 1BR0321 For 21 cabinets 1BR0324 For 24 1 2 cabinets HIGH ALTITUDE PRESSURE SWITCHES These accessory kits may be used to...

Page 7: ...036 21581 001 Rev B 0904 Unitary Products Group 7 NOTES...

Page 8: ...without notice Printed in U S A 036 21581 001 Rev B 0904 Copyright by York International Corp 2004 All rights reserved Supersedes 036 21581 001 Rev A 0904 Unitary 5005 Norman Products York OK Group D...

Reviews: