Johnson Controls Unitary Products
3
505591-YTG-A-0909
PROCEDURES
1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of interconnecting line tubing.
2. Verify the TXV and additional charge required for specific evaporator coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the Physical and Electrical Data
Table.
4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for evaporator
+ adder for line set.
System Charge for Various Matched Systems
Outdoor Unit
YZH02411(C)
YZH03611(C)
YZH04811(C)
YZH06011(C)
Approved System Thermal Expansion Valve
1
1TVM4G1
1TVM4G1
1TVM4H1
1TVM4K1
Factory R-410A Charge, lbs-oz
14 - 12
12 - 7
12 - 13
14 - 8
Indoor Coil
2
TXV Kit
3
- Additional Charge, Oz
AHX36
0
0
–
–
AHX48
–
9
4
–
AHX60
–
–
7
7
AV*36
0
0
–
–
AV/SV*48
–
9
4
–
AV/SV*60
–
–
4
0
FC/MC/PC37A
0
0
–
–
FC/MC/PC43BC
0
0
–
–
FC/MC/PC48CD
5
5
0
–
FC/MC/PC60CD
9
9
4
0
FC/MC62D
–
16
7
7
FC64D
–
25
15
14
HC42
0
0
–
–
HC60
–
–
4
0
HD48
–
5
0
–
HD60
–
–
4
0
FOOTNOTES:
1. Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit 2FD06700224.
2. PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.
3. A TXV kit must be used with these coils to obtain system performance.
Note:
If a TXV is factory installed on the coil, it must be replaced with the listed TXV.
COOLING CAPACITY - With Air Handler Coils
UNIT
MODEL
AIR HANDLER
COIL
1
MODEL
COOLING
MODEL
W
STAGE
RATED
CFM
NET MBH
SEER
EER
TOTAL
SENSIBLE
18 SEER HP WITH MV - VARIABLE SPEED
YZH02411
MV12B 17 FC/MC43B
1
645
18.2 13.5
16.40 13.60
2 835 23.6 18.8
MV12D 24 FC/MC48D
1 645 18.5 14.0
17.00 14.00
2 835 24.0 19.5
MV12D 24 FC/MC60D
1 645 18.5 14.0
17.00 14.00
2 835 24.0 19.5
YZH03611(C)
MV16C 21 FC/MC43C
1 775 24.8 18.2
17.10 13.10
2 1200 35.4 26.6
MV16C 21 FC/MC48C
1 775 25.0 18.6
17.30 13.35
2 1200 35.8 26.8
MV12D 24 FC/MC48D
1 845 24.8 18.0
17.35 13.35
2 1245 35.2 26.2
MV12D 24 FC/MC60D
1 845 24.8 18.3
17.50 13.35
2 1245 35.4 26.4
MV12D 24 FC/MC62D
1 845 25.6 19.7
18.00 13.35
2 1245 36.0 27.8
MV12D
24
FC64D
1
780
25.8
19.6
18.20
13.50
2
1155
36.0
27.6
For Notes See Page 4.