APPENDIX A – START-UP CHECKLIST
start-up
recOrd data
pOWer supplY:
Unit Nameplate V___ pH___ CYC, ____ Verify V
_________/ _________ / __________
data
sUppLY FAN MoToR
EXHAUsT/RETURN FAN
MOTOR
Nameplate
Volts ____________ Amps _______________
Volts _______________ Amps ____________
Run Amps
___________ / ____________/ __________
___________ / ___________ / ___________
Catalog Number
_____________________________________
______________________________________
Spec Number
_____________________________________
______________________________________
Horse power
_____________________________________
______________________________________
RPM Nameplate __________ Actual____________
Nameplate __________ Actual ____________
Frame size
_____________________________________
______________________________________
Service Factor
_________________________________
_________________________________
Jump (Skip) Frequencies
___________ / ____________/ __________
___________ / ___________ / ___________
sUppLY FAN dRIVE KIT
EXHAUsT/RETURN FAN dRIVE KIT
B
elts (Qty & ID #)
_____________________________________
______________________________________
Belt Tension
Tag________________ Actual ____________
Tag________________ Actual _____________
Fan RPM (DN)
Tag________________ Actual ____________
Tag________________ Actual _____________
Other utilities
steam pressure Heating Coils _____psI, Humidifier _____psI
Hot Water pressure/Temp. supply _____psI, _____°F, Return _____psI, _____°F
Chilled Water pressure/Temp. supply _____psI, _____°F, Return _____psI, _____°F
Potable Water Pressure _____PSI, Pneumatic Air Pressure _____PSI
sUppLY FAN
EXHAUsT/RETURN FAN
Manufacture Name
_____________________________________
______________________________________
Type or Model Number
_____________________________________
______________________________________
Code or Shop Order Number
_____________________________________
Serial Number
_____________________________________
______________________________________
perfOrm the fOllOWing steps in Order:
Refer to safety standards. Ensure all door latches are secured before starting.
□
1. With all Electric Power off, all disconnect switches open and
fuses removed, check each circuit with an Ohm meter to
ground observing no continuity. Reinstall fuses.
□ 8. Immediately check current draw of each leg of each motor.
□ 2. Energize power to the unit disconnect switch.
□ 9. VFd, refer to manufactures start up guide
□ 3. Verify correct voltage, phase and cycles.
□ 10. Check doors and latches for air leaks.
□ 4. Energize fan motor(s) briefly (bump) and check for correct fan
rotation.
□ 11. Check for obvious audible leaks.
□ 5. Check operation of dampers. Insure unit will not operate with
all dampers closed.
□ 12. Apply steam to cold coils slowly to prevent damage.
□ 6. Energize fan motor(s). observe fan(s) for smooth operation.
□ 13. observe energy recovery wheel rotation is correct.
□ 7. Check motor nameplate Full Load Amp rating.
□ 14. purge on energy recovery wheel is set to specification.
fan inspectiOn
□
Check bearings and locking collars for properly tightened
setscrews, bolts and nuts.
□
Fan wheel properly aligned, tight on shaft and freely
moving.
□
Sheaves properly aligned and tight on shaft.
□
Check fan base isolators and thrust restraints for proper
adjustment.
note: do not remove functional bolts
from seismic isolators.
□
Belt tension adjusted properly per drive pkg. label on fan.
□
Check fan alignment with unit discharge. Adjust with
isolation.
□
Fan bearings have been re-lubricated properly.