8
Johnson Controls Unitary Products
5151060-YTG-F-1116
48D
6HK(0,1)6500206
10
19.9
20.7
25
25
6HK(0,1)6500506
20
30.8
32.7
35
35
6HK(0,1)6500806
32
44.0
47.3
45
50
6HK(0,1)6501006
40
52.4
56.6
60
60
6HK(1,2)6501306
52
65.6
71.3
70
80
6HK(1,2)6501506
60
74.0
80.5
80
90
6HK(1,2)6501806
72
87.3
95.2
90
100
6HK(1,2)6502006
80
95.7
104.4
100
110
6HK(1,2)6502506
100
117.3
128.3
125
150
60C
6HK(0,1)6500206
10
19.9
20.7
25
25
6HK(0,1)6500506
20
30.8
32.7
35
35
6HK(0,1)6500806
32
44.0
47.3
45
50
6HK(0,1)6501006
40
52.4
56.6
60
60
6HK(1,2)6501306
52
65.6
71.3
70
80
6HK(1,2)6501506
60
74.0
80.5
80
90
6HK(1,2)6501806
72
87.3
95.2
90
100
6HK(1,2)6502006
80
95.7
104.4
100
110
60D
6HK(0,1)6500206
10
19.9
20.7
25
25
6HK(0,1)6500506
20
30.8
32.7
35
35
6HK(0,1)6500806
32
44.0
47.3
45
50
6HK(0,1)6501006
40
52.4
56.6
60
60
6HK(1,2)6501306
52
65.6
71.3
70
80
6HK(1,2)6501506
60
74.0
80.5
80
90
6HK(1,2)6501806
72
87.3
95.2
90
100
6HK(1,2)6502006
80
95.7
104.4
100
110
6HK(1,2)6502506
100
117.3
128.3
125
150
1. (0,1) - maybe 0 (no service disconnect) or 1 (with service disconnect).
2. (1,2) maybe 1 (with service disconnect, no breaker jumper bar) or 2 (with service disconnect & breaker jumper bar).
3. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse. Refer to the latest edition of the
National Electric Code or in Canada the Canadian electrical Code and local codes to determine correct wire sizing.
ELECTRICAL DATA FOR SINGLE SOURCE POWER SUPPLY: 208/230-1-60 (Continued)
Air Handler Models
Heater Models
1,2
Heater
Amps
@240V
Field Wiring
Min. Circuit Ampacity
MOP.
3
208V
230V
208V
230V